PUVR44-2-A BROYCE | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 1
Technical content
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. PUVR44-2-A.DOCX XXXXX Dims: to DIN 43880 W. 44mm INSTALLATION AND SETTING
- BEFORE INSTALLATION, ISOLATE THE SUPPLY.
- Connect the unit as required. The Connection Diagram below shows a typical installation, whereby the supply to a load is being monitored by the Phase monitoring relay. If a fault should occur (i.e. fuse blowing), the relay will de-energise and assuming control of the external Contactor, de-energise the Contactor as well. Setting the unit and applying power.
- Set the “Nominal Voltage (Un)” ➌ voltage adjustment to match that of the supply voltage being monitored.
- Set the “Trip Level” ➎ and “Differential” ➏ adjustments to minimum. Set the “Time Delay” ➍ to minimum.
- Apply power and the green “Power supply” ➊ LED will illuminate and relay will energise after the short Power on delay (Td). The red “UNDER” LED ➋ will remain extinguished.
- Refer to the troubleshooting table if the unit fails to operate correctly. Setting the unit (with power applied).
- Accurate setting can be achieved by adjusting the “Trip Level” until the unit trips (relay de-energises/red LED lit) then by decreasing the “Trip Level” until the relay re-energises again (red LED extinguished). Close setting of the trip level ensures the unit will detect a phase loss even with a large percentage of re-generative voltage.
- In order to set the unit as previously described but without causing disruption to the equipment being controlled/monitored, set the “Time Delay” to maximum. It will now be possible to establish the trip point when the red LED starts to flash. Decrease the trip level setting to stop the LED flashing. (Note: If the time delay is allowed to expire, the output relay will de-energise)
- If large supply variations are anticipated, the trip level should be set further from the nominal voltage.
- Set the “Delay (t)” as required. (Note that the delay is only effective should the supply drop below the set trip level. However, if during an under voltage condition the supply drops below the fixed “Uoff ” trip level any set time delay is automatically cancelled and the relay de-energises). Testing on single phase
- For the purpose of testing/checking the unit where 3-phase is not available, wire the unit as shown in the diagram on the right. The procedure further up (Setting the unit and applying power) still applies. Troubleshooting. The table below shows the status of the unit during a particular fault condition. Supply fault Green LED ➊ Red LED ➋ Relay Under voltage condition (during timing) On Flashing Energised for delay (t) Under voltage condition (after timing) On On De-ene rgised Phase missing/below supply threshold (U off ) LED’s flash alternately De-energised Neutral missing Off Off De-energised TECHNICAL SPECIFICATION Supply/monitoring voltage U n Frequency range: 45 – 65 Hz Supply variation: 132 - 346 V AC (L>N) Maximum overload (L>N): 416V for 10s Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Power consumption (max.): 3VA/1.7W Monitoring mode: Under voltage Trip levels: Supply threshold (U off ): 140V ± 2% (fixed) Under: 70 – 100 % of Un Measuring ranges: Nominal (Un) Under 220V 154 - 220V 230V 161 - 230V 240V 168 - 240V 254V 178 - 254V 265V 185 - 265V 277V 194 - 277V Differential: 1 – 15% of Un Setting accuracy: ± 3% Repeat accuracy: ± 0.5% at constant conditions Immunity from micro power cuts: <50ms Delay from Phase loss (t r): <300ms (150ms typical) Delay from Neutral loss (t p): <300ms (150ms typical) Delay to relay re -energising: <500ms (after fault clearing) Time delay (t): 0.5 – 10s ( ± 5%) Power on delay (Td): ≈ 0.5s (worst case = Td x 2) Reset time: 50 – 100ms Power on indication: Green LED Fault/timing status indication: Red LED Ambient temperature: -20 to +60 °C Relative humidity: +95% max. Output (8, 9, 10 / 12, 13, 14 ): DPDT relay Output rating: AC1 250V 8A ( 200 0VA) AC15 250V 3 A DC1 25V 8A (200 W) Electrical life: ≥ 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947 -1 Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Housing: Grey flame retardant Lexan UL94 V0 Weight: 10 0g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 Terminal conductor size ≤ 2 x 2.5mm 2 solid or stranded Approvals: Conforms to IEC. CE, and RoHS Compliant. EMC: Immunity: EN 61000-6-2 Emissions: EN 61000-6-4 FUNCTION DIAGRAM Terminal Protection to IP20 DIMENSIONS 63.5mm 45mm 61mm 85mm 49.5mm 30mm 44mm Designed to withstand overloads up to 125% (cont.), 150% (10s) Microprocessor based True R.M.S. monitoring Selectable nominal voltages (220, 230, 240, 254, 265, 277V (L>N)) Monitors own supply and detects an Under voltage condition on one or more phases Adjustment for Differential and Under voltage trip level Adjustment for Time delay DPDT relay output 8A Green LED indication for supply status Red LED indication for fault/timing status Can be tested on single phase when 3-phase not available i.e. during commissioning SETTING DETAILS 1. Power supply status (Green) LED 2. Fault / Timing status (Red) LED 3. “Nominal Voltage (Un)” selector 4. “Time Delay (s)” adjustment 5. “Trip Level (% x Un)” adjustment^ 6. “Differential (% x Un)” adjustment^ ^scaled as % of the selected “Nominal Voltage” CONNECTION DIAGRAM (3-PHASE) Type: PUVR44 Phase Under Voltage plus Time Delay CONNECTION FOR TESTING ON SINGLE PHASE Link the terminals as shown in the diagram below for single phase operation/testing purposes.