Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LDOB-3-A 2506 XXXXX HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION
- BEFORE INSTALLATION, ISOLATE ALL SUPPLIES
- Connect the unit as per the diagram below.
- The timer should be connected so that it is in seri es with the Thermostat and Contactor. Applying power/operation
- Apply power to the application and providing the th ermostat is closed, the contactor will energise and load (compressor) will operate.
- As soon as the thermostat opens, the contactor and load will de-energise. The time delay period “t” will now commence.
- Even if the thermostat closes again, the time delay period must have finished before the contactor/load are energised again. Troubleshooting
- Check all connections are good to the timer and ext ernal devices.
- If the contactor/load fails to operate, ensure the voltage is within the operating limits as specified in the technical specification on the right.
- Ensure that the time delay period has completed. TECHNICAL SPECIFICATION Voltage rating Un: 24VAC Frequency range: 48 – 63Hz Supply variation: 75 – 125% Un Time delay (t)*: 3 minutes (Model LDOB-3) 5 minutes (Model LDOB-5) Time delay tolerance: ± 20% Repeat accuracy: ± 5% at constant conditions Reset time: 60ms Ambient temp: -20 to +60 °C Relative humidity: +95% Output: Solid state Load current rating: Min. Max. 40mA 1.5A Load type: Inductive or Resistive Housing: Grey flame retardant UL94 Weight: <45g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit. Terminal conductor size ≤ 2 x 2.5mm 2 solid or stranded Approvals: Conforms to: IEC 60664-1, IEC 60947-1, UL508 CE, UKCA and RoHS Compliant. * Model to be specified when ordering FUNCTION DIAGRAM Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Installation work must be carried out by qualified personnel. Protects compressor in refrigeration, air conditioning and heat pumps against premature cycling Prevents re-starting of compressor until time delay “lockout” period has completed Works with anticipator thermostats Two fixed time delays to choose from - 3 or 5 minutes* (factory set) Simple 2-wire connection Solid state control with 1.5A max. switching capacity Designed for 24VAC low voltage control Easy to install Compact dimensions DIN Rail or Surface mounting CONNECTION DIAGRAM LDOB Timer Contactor Load 24VAC Thermostat 24VAC t o Line Voltage Control Transformer Type: L DOB Delay On Break Timer