Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LBVR_A-4-A 2507 XXXXX HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION AND SETTING
- BEFORE INSTALLATION, ISOLATE THE SUPPLY.
- Connect the unit as required taking note of the polarity of the connections. Terminal A1 is the positive connection and A2 the negative. Setting the unit.
- Set the Under voltage “Trip Level (V)” ➍ adjustment to the voltage required.
- Set the “Delay (t)” ➌ to minimum. Applying power.
- Apply power and the green “Power supply” ➊ and red “Relay” ➋ LED’s will illuminate, the relay will energise and contacts 15 and 18 will close. Refer to the troubleshooting table if the unit fails to operate correctly.
- If the supply voltage drops below the trip level setting, the green LED will start to flash. The relay will then de-energise (contacts 15 and 18 open) after the delay period “t” and the red LED will extinguish. The green LED will then remain permanently lit.
- When the voltage increases above the trip level + hysteresis, then relay will re-energise and red LED illuminate. Troubleshooting. The table below shows the status of the unit during a fault condition. Supply fault Green LED Red LED Relay No supply Off Off De-energised Under voltage condition (during timing) Flashing On Energised for set delay (t) Under voltage condition (after timing) On Off De-en ergised TECHNICAL SPECIFICATION Supply/monitoring voltage U (A1, A2): 12 – 24V DC Supply variation: 75 – 125% U Power consumption (max.): 3W Monitoring mode: Under voltage Trip level: 9 – 28V DC Hysteresis: ≈ 5% of trip level (factory set) Setting accuracy: ± 10% Repeat accuracy: ± 0.5% at constant conditions Response time: ≈ 100mS Time delay (t): 0 – 30 Sec. ( ± 5%) Note: actual delay (t) = adjustable delay + response time Power on delay (Td): ≈ 1 sec. (worst case = Td x 2) Power on indication: Green LED Relay status indication: Red LED Ambient temp: -20 to +60 °C Relative humidity: +95% Output (15, 16, 18) : SPDT relay Output rating: AC1 250V 8A (2000VA) AC15 250V 5A (no), 3A (nc) DC1 25V 8A (200W) Electrical life: ≥ 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947-1 Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Housing: Grey flame retardant UL94 Weight: 70g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit. Terminal conductor size: ≤ 2 x 2.5mm 2 solid or stranded Terminal screw: M3 (Designed for use with PZ1 “pozi-driver”) Tightening torque: 0.6Nm Max. Approvals: Conforms to IEC. CE, UKCA, and RoHS Compliant. EMC: Immunity/Emissions to EN 61000-6 FUNCTION DIAGRAM t Supply A1, A2 Output 15 16 % Hyst. Trip Level BVRA0215 Monitored Voltage LED Off LED Flashing LED On Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Installation work must be carried out by qualified personnel. *NEW* 17.5mm DIN rail housing Microprocessor based Suited to 12V and 24V batteries Monitors own supply and detects and Under voltage condition Adjustment for Under voltage trip level (9 – 28V) Adjustment for Time delay (from an Under voltage condition) 1 x SPDT relay output 8A Green LED indication for supply status Red LED indication for relay status SETTING DETAILS 1. Power supply status (Green) LED 2. Relay output status (Red) LED 3. “Delay” adjustment 4. “Under” trip level adjustment CONNECTION DIAGRAM 16 18 R +ve -ve Supply / Monitored Voltage 16 18 LED operation: Type: LBVR/A Battery Voltage Relay Wiring Information and Product Demonstration Videos can also be found on our YouTube channel https://www.youtube.com/user/BroyceControlLtd