Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LMCVR_20V-4-A 2507 XXXXX HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION AND SETTING

  • BEFORE INSTALLATION, ISOLATE THE SUPPLY.
  • Connect the Auxiliary and Monitored Inputs as required. Setting the unit.
  • Set the “Hyst. / Mode” selector ➐ to the required position depending whether under or over monitoring is required. Select either a suitable hysteresis setting of 2% or 10% or choose Latch if required.
  • Set the “Range” ➏ to the required position (depending on monitored input voltage to be monitored).
  • Set the “Trip Level %” ➎ and “Delay” ➍ to suit the selected monitoring range and delay to tripping period. Applying power.
  • Apply power and the green LED ➊ will illuminate. If Under voltage mode is selected:
  • Relay energises / red LED ➌ illuminate if the voltage is above the set “Trip Level”. If the voltage falls below the “Trip Level”, yellow LED ➋ flashes for the set “Delay” then remains lit. Red LED extinguishes / relay de-energises. If Over voltage mode is selected:
  • Relay energises / red LED ➌ illuminate if the voltage is below the set “Trip Level”. If the voltage rises above the “Trip Level”, yellow LED ➋ flashes for the set “Delay” then remains lit. Red LED extinguishes / relay de-energises. TECHNICAL SPECIFICATION Auxiliary supply voltage U (A1, A2) : 24 – 230V AC/DC Frequency range: 48 - 63Hz (AC supplies) Supply variation: +15%/-10% Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Power consumption (max.): 24V 48V 115V 230V AC: 0.84 VA 0.82 VA 1.1 VA 1.4 VA DC: 0.6 W 0.47 W 0.46 W 0.53 W Monitoring mode: Under or Over voltage (selectable) Hysteresis: 2 or 10% (selectable) Latch: Enabled using Mode selector switch Monitoring ranges: 0.1 – 1V, 0.2 – 2V, 0.5 – 5V, 1 – 10V, 2 – 20V Trip level: 10 – 100% of selected monitoring range Time delay (t): 0.1 – 30S (from fault occurring to relay de-energising) Power up delay (Td): 1 second (fixed) Reset time: 100mS Accuracy: ± 1% of maximum full scale Adjustment accuracy: < 5% of maximum full scale Repeat accuracy: ± 0.5% at constant conditions Drift with temperature: ± 0.05% / °C Drift with voltage: ± 0.2% / V Monitoring input (B1, B2) : 0.1 to 20V AC/DC Frequency: DC, 48 – 500Hz Maximum input rating: 1.2 x 20V Overload: TBC Overvoltage category: TBC Rated impulse withstand voltage: TBC Power on indication: Green LED Alarm status indication: Yellow LED Relay status indication: Red LED Ambient temp: -20 to +60 °C Relative humidity: +95% Output (15, 16, 18) : SPDT relay Output rating: AC1 250V 10A (2500VA) AC15 250V 5A (no), 3A (nc) DC1 25V 10A (250W) Electrical life: ≥ 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947-1 Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Housing: Grey flame retardant UL94 V0 Weight: 63g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit Terminal conductor size: ≤ 2 x 2.5mm 2 solid or stranded Terminal screw: M3 Tightening torque: 0.4Nm Max. Approvals: CE, UKCA and RoHS Compliant. EMC: Immunity: EN 61000-6-2 (EN 61000-4-3 10V/m 80MHz - 2.7GHz) Emissions: EN 61000 -6-4 FUNCTION DIAGRAMS Under Voltage Monitoring (with and without Latch enabled) Over Voltage Monitoring (with and without Latch enabled) t Supply A1, A2 Output 15 16 Monitored Voltage B1, B2 %Hyst. % Level Td UVM1013 t Supply A1, A2 Output 15 16 %Hyst. % Level Td UVML1013 Monitored Voltage B1, B2 t Supply A1, A2 Output 15 16 %Hyst. % Level Td OVM1013 Monitored Voltage B1, B2 t Supply A1, A2 Output 15 16 %Hyst. % Level Td OVML1013 Monitored Voltage B1, B2 Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Installation work must be carried out by qualified personnel.  *NEW* 17.5mm DIN rail housing  Microprocessor based  True R.M.S. monitoring  7 Selectable monitoring ranges (0.1 – 20V AC/DC)  Selectable Under or Over Voltage monitoring  Selectable hysteresis or latch option  Adjustable trip level and time delay  Isolated Auxiliary supply (24 – 230V AC/DC)  1 x SPDT relay output 8A  Green LED indication for supply status  Yellow LED indication for alarm status  Red LED indication for relay status SETTING DETAILS 1. Power supply status (Green) LED 2. Alarm status (Yellow) LED 3. Relay output status (Red) LED 4. Time delay adjustment 5. Trip level adjustment 6. Monitoring range selector 7. Hysteresis / Mode selector CONNECTION DIAGRAM Supply L/+ve N/-ve Monitored Voltage N/-ve L/+ve 16 18 R B2 B1 15 16 18 A1 A2 ➊ ➏ Type: LMCVR -20V Multifunction, Combined Voltage Relay Wiring Information and Product Demonstration Videos can also be found on our YouTube channel https://www.youtube.com/user/BroyceControlLtd