LDRT-3-A BROYCE | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 1
Technical content
Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LDRT-3-A 2507 HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION AND SETTING
- BEFORE INSTALLATION, ISOLATE THE SUPPLY.
- Connect the unit as required. The Connection Diagram below shows a typical installation, whereby the supply to a load is being monitored by the unit. If a fault should occur (i.e. fuse blowing), the relay will de-energise and assuming control of the external Contactor, de-energise the Contactor as well. Applying power.
- Apply power and the green LED ➊ will illuminate. The relay will remain de-energised.
- Assuming the supply voltage is above the fixed trip level (plus hysteresis) the delay period (t) will commence and the red LED ➋ will flash during this period.
- After the set delay has elapsed, the relay will energise and red LED ➋ remain on. Setting the unit
- Set the “Delay (t)” ➌ adjustment as required. Troubleshooting. The table below shows the status of the unit during a particular condition. Supply status Green LED ➊ Red LED ➋ Relay No supply Off Off De-energised Under voltage condition On Off De-energised Following supply loss or voltage returning > 80% of Un On Flashing De-energised for delay period (t) TECHNICAL SPECIFICATION Supply/monitoring voltage Un^ (A1, A2): 115, 230V AC Frequency range: 48 – 63Hz Supply variation: 75 – 115% Un Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 2.5kV (115V), 4kV (1.2/50 µ S) IEC 60664 Power consumption (max.): 11VA @ 1.15 x Un Monitoring mode: Under voltage Trip levels: Under: 80% of Un (Fixed) Trip accuracy: ± 5% Hysteresis: ≈ 5% of fixed trip level (factory set) Time delay (t): 2 – 60s (± 5%) Setting accuracy: ± 5% Repeat accuracy: ± 0.5% at constant conditions Reset time (t r): ≈ 100ms LED indication: Green LED (Power supply) Red LED (Relay/timing status) Ambient temperature: -20 to +60 °C Relative humidity: +95% max. Output (15, 16, 18) : SPDT relay Output rating: AC1 250V 8A (2000VA) AC15 250V 5A (no), 3A (nc) DC1 25V 8A (200W) Electrical life: ≥ 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947-1 Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Housing: Grey flame retardant UL94 Weight: 61g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit. Terminal conductor size ≤ 2 x 2.5mm 2 solid or stranded Terminal screw: M3 (Designed for use with PZ1 “pozi-driver”) Tightening torque: 0.6Nm Max. Approvals: Conforms to IEC. CE, UKCA and RoHS Compliant. EMC: Immunity: EN 61000-6-2 Emissions: EN 61000-6-4 FUNCTION DIAGRAM Monitored Supply Under trip Hyst. A1- A2 LDRT -0121 t Output tr t t Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Detects voltage dips and momentary loss/interruption of supply “Delay on operate” functionality provides an adjustable delay period before the relay energises Fixed Under voltage trip level (80% of Un) Adjustable time delay (2 – 60s) Fixed reset time (100ms) SPDT relay output 8A Green LED indication for supply status Red LED indication for timing and relay status Compact 17.5mm DIN rail housing Ideal for water authorities where remote pumping stations and unmanned control systems are in use SETTING DETAILS 1. Supply status (Green) LED 2. Relay output/timing status (Red) LED 3. “Delay (t)” adjustment CONNECTION DIAGRAM 16 18 R Contactor Local Fuse Board N To Load Supply / Monitored Voltage 18 16 Type: LDRT Mains Restoration “Brown Out” Auto Restart Timer (Delay On Operate) ^ Please state supply voltage when ordering