Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LMWVR-5-A 2507 XXXXX HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION AND SETTING

  • BEFORE INSTALLATION, ISOLATE THE SUPPLY.
  • Connect the Auxiliary and Monitored Inputs as required. Setting the unit.
  • Set the “Nominal voltage” selector ➑ to the match that of the voltage being monitored on terminals B1 and B2.
  • Set the “Under %” ➎ and “Over %” ➐ trip levels as required. These are scaled as a % of the selected nominal voltage.
  • Set the “Delay” ➏ as required. Applying power.
  • Apply power and the green LED ➊ will illuminate. Both yellow LED’s will remain extinguished and the relay will energise. The red LED ➋ will also illuminate. Under voltage condition:
  • If the monitored voltage falls below the “Under %” trip level the yellow “<Un” LED ➌ will start flashing. The relay will de-energise and red LED extinguish after the delay period “t” has elapsed. The yellow LED will then remain illuminated to indicate an under voltage condition. The relay will re-energise/red LED illuminate (and yellow LED extinguish) when the voltage rises above the trip level plus the hysteresis. Over voltage condition:
  • If the monitored voltage rises above the “Over %” trip level the yellow “>Un” LED ➋ will start flashing. The relay will de-energise and red LED extinguish after the delay period “t” has elapsed. The yellow LED will then remain illuminated to indicate an over voltage condition. The relay will re-energise/red LED illuminate (and yellow LED extinguish) when the voltage falls below the trip level minus the hysteresis. TECHNICAL SPECIFICATION Auxiliary supply voltage U (A1, A2) : 24 – 230V AC/DC Frequency range: 48 - 63Hz (AC supplies) Supply variation: +15%/-10% Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Power consumption (max.): 24V 48V 115V 230V AC: 0.84 VA 0.82 VA 1.1 VA 1.4 VA DC: 0.6 W 0.47 W 0.46 W 0.53 W Monitoring mode: Under and Over voltage (Window) Hysteresis: 2% fixed Selectable nominal voltages (Un): 12, 24, 48, 110, 115, 230, 240V Under trip level adjustment: 70 – 95% of Un Over trip level adjustment: 105 – 130% of Un Time delay (t): 0.1 – 30S (from fault occurring to relay de-energising) Power up delay (Td): 1 second (fixed) Reset time: 100mS Accuracy: ± 1% of maximum full scale Adjustment accuracy: < 5% of maximum full scale Repeat accuracy: ± 0.5% at constant conditions Drift with temperature: ± 0.05% / °C Drift with voltage: ± 0.2% / V Monitoring input (B1, B2) : 0.2 to 350V AC/DC Frequency: DC, 48 – 500Hz Maximum input rating: 500V Overload: 1kV for 1s Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Power on indication: Green LED Under voltage trip indication Red LED Over voltage trip indication Red LED Ambient temp: -20 to +60 °C Relative humidity: +95% Output (15, 16, 18) : SPDT relay Output rating: AC1 250V 10A (2500VA) AC15 250V 5A (no), 3A (nc) DC1 25V 10A (250W) Electrical life: ≥ 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947-1 Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Housing: Grey flame retardant UL94 V0 Weight: 63g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit Terminal conductor size: ≤ 2 x 2.5mm 2 solid or stranded Terminal screw: M3 Tightening torque: 0.4Nm (3.5Lb-In) Max. Approvals: CE, UKCA and RoHS Compliant. EMC: Immunity: EN 61000-6-2 (EN 61000-4-3 10V/m 80MHz - 2.7GHz) Emissions: EN 61000 -6-4 FUNCTION DIAGRAM Under and Over Voltage Monitoring t 15 16 Td UOVM1113 t Supply A1, A2 Monitored Voltage B1, B2 %Hyst. Under % Over % %Hyst. >Un <Un Output Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Installation work must be carried out by qualified personnel.  *NEW* 17.5mm DIN rail housing  Microprocessor based  True R.M.S. monitoring  7 Selectable Nominal voltage ranges (12 – 240V AC/DC)  Window operation Under and Over voltage monitoring  Adjustable Under and Over voltage trip levels  Adjustable time delay  Isolated Auxiliary supply (24 – 230V AC/DC)  1 x SPDT relay output 8A  Green LED indication for supply status  Separate Yellow LED indication for Under or Over voltage condition SETTING DETAILS 1. Power supply status (Green) LED 2. Over voltage trip indication (Yellow) LED 3. Under voltage trip indication (Yellow) LED 4. Relay energised (Red) LED 5. Under voltage trip level adjustment 6. Time delay adjustment 7. Over voltage trip level adjustment 8. Nominal voltage selector CONNECTION DIAGRAM Supply L/+ve N/-ve Monitored Voltage N/-ve L/+ve 16 18 R B2 B1 15 16 18 A1 A2 ➊ ➐ Type: LMWVR Multifunction, Window Voltage Relay