Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LMMT-6-A 2506 HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION AND SETTING

  • BEFORE INSTALLATION, ISOLATE THE SUPPLY.
  • Connect the unit as required. Setting the unit.
  • Set the “Function” selector ➎ to the required position 1.
  • Set the “Range” ➍ to the required position (depending on whether seconds, minutes or hours are required), then set the “Set %” adjustment ➌ as required. The “Set %” is a % of the selected range, so 60% of the 1 – 10 hour range will give 6 hours. Applying power.
  • Apply power and the green LED ➊ will illuminate or start flashing depending on Function selected. If a Switch initiated function is selected, the LED will begin flashing upon closing of the external input.
  • The red relay LED ➋ will illuminate to indicate the relay is in the energised state. Note: 1 If the “Function” selector is changed whilst the power is applied, the relay will remain in its current state and the green LED will flash at a faster rate. Power must be removed and re-applied for the new Function to operate. 2 In accordance with IEC 61812, the green LED is permitted to extinguish during a voltage dip or momentary interruption of the power supply providing the state of the output relay does not change. The dip / interruption duration and levels are defined in the product standard. TECHNICAL SPECIFICATION Supply voltage U (A1, A2) : 24 – 230V AC/12 – 230V DC Frequency range: 48 - 63Hz (AC supplies) Supply variation: AC: +15/-20%, DC: +/-15% Overvoltage category: III (IEC 60664) Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Power consumption (max.): 12V 24V 110V 230V AC: 0.3VA 0.4VA 1.3VA 3.4VA DC: 0.26W 0.24W 0.47W 0.95W Timing functions (7): Supply initiated: Delay On (DO) , Interval (IN) , Symmetrical Recycling Off/On (RF) Switch initiated: Delay On (DOb) , Delay Off (DN) , Interval (Trailing) (INa) , Interval (Leading) (INb) Timing ranges (7): Seconds: Minutes: Hours: 1 – 10 1 – 10 1 – 10 10 - 100 Reset time: 100ms Accuracy: ± 1% of maximum full scale Adjustment accuracy: < 5% of maximum full scale Repeat accuracy: ± 0.5% at constant conditions (IEC 61812) Drift with temperature: ± 0.05% / °C Drift with voltage: ± 0.2% / V External trigger input (A1 > B1) : Volt Free Contact, Open Collector External loading: Yes, between B1 and A2 (i.e. LED, Relay, Lamp) Trigger threshold: >75% of voltage present between A1 and A2 (auto-set) Minimum trigger time: AC: 60ms DC: 40ms (B1 terminal unloaded) Maximum input frequency: 10 Hz (with 50:50 duty cyc le) Maximum cable length: 10m (between Timer and external switching device) Power on indication / Timing 2: Green LED Relay status Red LED Ambient temp: -20 to +60 °C Relative humidity: +95% Output (15, 16, 18) : SPDT relay Output rating: AC1 250V 8A (2000VA) AC15 250V 5A (no), 3A (nc) DC1 25V 8A (200W) Electrical life: ≥ 150,000 ops at rated load Dielectric voltage: 2kV AC (rms) IEC 60947-1 Rated impulse withstand voltage: 4kV (1.2/50 µ S) IEC 60664 Housing: Grey flame retardant UL94 Weight: ≈ 60g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit. Terminal conductor size: ≤ 2 x 2.5mm 2 solid or stranded Terminal screw: M3 (Designed for use with PZ1 “pozi-driver”) Tightening torque: 0.6Nm Max. Approvals: Conforms to IEC 61812. CE, UKCA, C-tick and RoHS Compliant. EMC: Immunity: EN 61000-6-2 (EN 61000-4-3 10V/m 80MHz - 2.7GHz) . Emissions: EN 61000 -6-4 FUNCTION DIAGRAMS t Supply A1, A2 Output 15 16 DOSU0813 Output 15 16 Supply A1, A2 INSU0813 t t t t t t Supply A1, A2 Output 15 16 RFN0813 Output 15 16 Supply t V.F.C. A1, B1 t A1, A2 DOSWL0813 Output 15 16 Supply t V.F.C. A1, B1 A1, A2 DFSW0518 t<t Output 15 16 A1, A2 Supply t V.F.C. A1, B1 t INSWT0813 Output 15 16 Supply t V.F.C. A1, B1 t A1, A2 INSWL0813 Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Installation work must be carried out by qualified personnel. Type: LMMT Multifunction, Multi-voltage Timer  *NEW* 17.5mm DIN rail housing  7 Selectable functions (3 Supply Initiated, 4 Switch Initiated)  3 Switch initiated functions are re-triggerable (DOb, DN and INb)  7 Selectable time ranges (0.1 seconds – 100 hours)  Fine adjustment of selected time range  LED warning indication if function is changed whilst powered  Switch initiated functions ideal for use in Watchdog circuits  Multi-voltage input (24 – 230V AC/12 – 230V DC)  1 x SPDT relay output 8A  Green LED indication for supply / timing status  Red LED indication for relay status  Conforms to IEC 61812 SETTING DETAILS 1. Power supply status / Timing (Green) LED 2. Relay output status (Red) LED 3. “Set %” adjustment 4. Time delay “Range” selector 5. Timing “Function” selector CONNECTION DIAGRAM External N.O. contact Example of external loads that can be connected to the trigger input simultaneously. Relay Lamp Supply L/+ve N/-ve 16 18 R 16 18 LED operation: “Function” Symbol explanation: Symbol Function 1 Triggered from: DO Delay On Operate Supply (A1/A2) IN Interval Supply (A1/A2) RF Symmetrical Recycling (Off/On) Supply (A1/A2) DOb Delay On Switch (A1/B1) DN Delay Off Switch (A1/B1) INa Interval* Switch (A1/B1) INb Interval Switch (A1/B1) * This function is non -retriggerable LED Off LED Flashing LED On Wiring Information and Product Demonstration Videos can also be found on our YouTube channel https://www.youtube.com/user/BroyceControlLtd