Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Email: sales@broycecontrol.com Web: www.broycecontrol.com The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk. LDB-3-2-A 2511 XXXXX HS Code: 85364900 Country of Origin: UK Dims: to DIN 43880 W. 17.5mm INSTALLATION

  • BEFORE INSTALLATION, ISOLATE ALL SUPPLIES
  • Connect the unit as per the diagram below.
  • Note this unit is designed for 24VAC operation only . Applying power/operation
  • Apply power to the timer. The red LED ➊ will illuminate.
  • The external load will energise and green LED ➋ illuminate confirming the output is active.
  • When power is removed, the load will de-energise. B oth LEDs will extinguish. The time delay period “t” will now commence.
  • Even if power is re-applied, the time delay period must have finished before the load will energise again. Troubleshooting
  • Check all connections are good to the timer and ext ernal devices.
  • If the external load fails to operate, ensure the voltage is within the operating limits as specified in the technical specification on the right.
  • Ensure that the time delay period has completed. TECHNICAL SPECIFICATION Voltage rating Un: 24VAC Frequency range: 48 – 63Hz Supply variation: 75 – 125% Un Brownout threshold: <19VAC Return voltage: >20VAC Power consumption: 1.5W Time delay (t): 3 minutes (fixed) Time delay tolerance: ± 10% Repeat accuracy: ± 5% at constant conditions Reset time: 60ms Power on indication: Red LED Output status/timing: Green LED Ambient temp: -20 to +60 °C Relative humidity: +95% Output: Solid state Load current rating: Min. Max. 40mA 1A Load type: Inductive or Resistive Housing: Grey flame retardant UL94 Weight: ≈ 46g Mounting option: On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit. Terminal conductor size: Max. 2.5mm 2 solid or stranded Terminal screw: M2.5, Combi-screw Tightening torque: 0.4Nm Max. Approvals: Conforms to: IEC 60664-1, IEC 60947-1, UL508 CE, UKCA and RoHS Compliant. FUNCTION DIAGRAM Terminal Protection to IP20 DIMENSIONS Withdraw clips fully when surface mounting 92 (+/- 1mm) 67.5 49.5 66.5 89 (exc. clips) Insert screwdriver to release clips all dimensions in mm. Installation work must be carried out by qualified personnel.  Protects compressor in refrigeration, air conditioning and heat pumps against premature cycling  Prevents re-starting of compressor until time delay “lockout” period has completed  Works with anticipator thermostats  Fixed time delay of 3 minutes  Red LED indication for supply status  Green LED indication for output/timing status  Solid state control with 1A max. switching capacity  Designed for 24VAC low voltage control  Easy to install  Compact dimensions  DIN Rail or Surface mounting CONNECTION DIAGRAM Type: L DB -3 Delay On Break Timer FRONT PANEL LAYOUT 1. Power supply status LED (Red) 2. Output/timing status LED (Green) LED STATUS TABLE STATUS RED ➊ GREEN ➋ ON DEVICE ON OUTPUT ON FLASHING SUPPLY BELOW THRESHOLD 1 TIMING OFF DEVICE OFF OUTPUT OFF

1 Threshold voltage is <19VAC