TG-F976-0E APR. 2002 TG-F976-6E SEP . 2013K CDT1000 Series Multi-Digital Flowmeter OUTLINE CDT1000 is a new series of flowmeter which combines a multi- digital indicator with a pitot tube. CDT1000 detects the differential pressure exerted by flow velocity in the pitot tube inserted in the pipe and outputs flow rate with digital indication. Applicable sizes range from 20mm to 450mm dia. The principal applications are for hot and cooling water lines for air conditioning in apartment and office buildings and other facilities.

FEATURES

❏ Easy installation ❏ Installation simply by making a 35mm dia. hole and welding 20mm (3/4") socket at measuring point of existing pipes. This is most convenient for renewal use when additional flow sensor is required on the line. ❏ Low pressure drop ❏ Wide measuring range Measuring range selectable depending on application ❏ Applicable for both horizontal and vertical pipes. ❏ Various indicator functions selectable from the following: Battery type, Current Output type (2-wire 4 to 20mA) and Alarm Output type ❏ Indicator parts are interchangeable. ❏ Easy to see because of large LCD display ❏ Compact size and lightweight ❏ Quick delivery STANDARD SPECIFICATION

  • Measuring Fluid : Water, Cold water, Hot water
  • Max. Pressure : 2MPa
  • Max. Allowable Differential Pressure : 700kPa (Bias pressure) Not applicable for vacuum service
  • Temperature and Relative Humidity Fluid temperature : -10 to 70 oC Use PVC lining and resin tubes within respective allowable temperature ranges. Ambient Temp. : -10 to 50 oC < 85%RH Storage Temp. : -20 to 60 oC < 85%RH (Without icing, without condensation)
  • Process pipe size : 20mm(3/4") to 450mm(18")
  • Adaptation pipe : Carbon steel pipe for piping (JIS G 3452) [1MPa class] Carbon steel pipe for pressure piping (JIS G 3454 Sch40) [2MPa class] Note : If pipe other than above is required, special calibration may be necessary. Consult factory for details. less than 30%)
  • Measuring range : Flow rate from 10 to 100% of full scale
  • Low cutoff : Less than 7%
  • Protection class : IP65 (JIS C 0920) (Except for the air introduction port at the bottom of housing.)
  • Mass : Approx. 2kg
  • Indicator type function (All types with indicator) Type Function Battery type Battery drive, Indication only Current output type 4-20mA DC (2-wire) 2 points + 4-20mA DC Alarm output type Alarm 1-point +totalized pulse + 4 to 20 mA
  • Indication function Flow rate indication 3-1/2 digits LCD (Height 18mm) : 0 to 1999 (FFF appears in case of out of range) 11 segment bar graph Totalizer indication 7-1/2 digits LCD (Height 5mm): 0 to 19999999 Indication interval : 1s (Sampling 0.5 sec) Filter : 0,2,4,8,16,32s (Moving average) LCD back light : Continue 10s after operation (Except current output type)
  • Material of Pitot tube parts : Refer to [OUTLINE DIMENSION] and [MATERIAL]
  • Material of wetted parts of indicator Diaphragm : 316L SS Body : 316SS O-ring : Fluorine rubber (JIS Class4-D) Drain hole sealing : Alumina ceramics
  • Material of indicator body: Aluminium alloy
  • Painting : Melamine resin painting (Indicator housing)
  • Painting color Front : Wine red (Munsell 10RP3/8) Rear : Light gray (Munsell N7.5)
  • Process connection : R3/4" (M)
  • Installation posture : Front vertical installation

CDT1000 QUICK FLOW for Air Conditioning Application Digital Flowmeter TG-F976-6E2 TOKYO KEISO CO., LTD.

  • Standard full scale range [SGP,STPG(40~450mm)pipe] mm inch 05 10 20 20 3/4 50 70 100 (26) 25 1 70 100 150 (34) 32 1- 1/4 120 160 250 (43) 40 1- 1/2 130 200 300 41.6 41.2 50 2 200 300 450 52.9 52.7 65 2- 1/2 400 500 700 67.9 65.9 80 3 500 700 1000 80.7 78.1 100 4 900 1300 1800 105.3 102.3 125 5 1300 2000 2800 130.8 126.6 150 6 2000 3000 4000 155.2 151.0 200 8 3500 5000 7000 204.7 199.9 250 10 5000 7 000 10000 254.2 248.8 300 12 8000 1 0000 16000 304.7 297.9 350 14 10000 13000 20000 339.8 333.4 400 16 13000 18000 25000 390.6 381.0 450 18 16000 20000 30000 441.4 428.6 Process pipe size Full scale range [L/min] Inside dia. (mm) Code 1MPa 2MPa Refer to following table mm inch 10 20 50 (mm) 20 3/4 50 70 100 21.4 25 1 70 100 150 27.2 32 1- 1/4 120 160 250 35.5 Inside dia. Code Full scale range [L/min]Process pipe size 2) Current output type Power supply :24V DC /H1100610% Output :4-20mA DC (2-wire) Max. load :600 Ω Output accuracy : /H110060.5% F.S. at 23oC Response :Less than 2 s (At filter setting 0) 3) Alarm output type Power Supply : 24V DC /H1100610% Power Consumption : Less than 25mA Alarm Output : Open Collector x 2 (Independent) (When the totalized pulse output option is added, the alarm output can be set only at either a high or low limit.) Totalized pulse output: Pulse width : 200 to 300ms Frequency : Less than 1Hz Load : Less than 30V DC / 80mA Response : Less than 2 s (At Filter setting 0) Alarm setting : Selectable (high / Low), Reset Span: Adjustable / Min. 1digit Output : 4-20mA DC Max. load : 600 Ω Output Accuracy : /H110060.5%F.S.at 23oC
  • Cable entry
  • Standard full scale range [PVC lined pipe]
  • Standard full scale range [2MPa version = 20~32mm] Note 1) The inside diameter of pipe size 20 to 32mm in 1MPa is based on three-way socket (JIS B 2301). (It is possible to attach three-way socket as option.) 2) The inside diameter of pipe size 20 to 32mm in 2MPa is based on three-way socket (Sch.40). (Supplied by customer.) 3) 40mm or more, the inside diameter of in 1MPa specification is based on Carbon steel tube for ordinary piping SGP (JIS G3452), and the inside diameter of in 2MPa specification is based on Carbon steel pipes for pressure piping STPG (JIS G 3454 Sch40). 4) Full-scale flow rates for the PVC lining pipe are calculated based on the inner diameter of ESLON ESLOCOAT LX tee fittings (Sekisui Chemical Co., Ltd). If you use other fittings, additional calibration is needed. Please determine the values of “D” and “L” in the figure at the end of this document and the kind of pipe and then contact us. mm inch 05 10 20 32 1- 1/4 75 100 150 29.5 40 1- 1/2 100 130 200 34.7 50 2 170 250 350 46.2 65 2- 1/2 300 400 600 59.7 80 3 450 650 900 70.9 100 4 800 1000 1600 95.2 125 5 1200 1800 2500 119.7 150 6 1700 2500 3500 142 (mm) Inside dia. Code Full scale range [L/min]Process pipe size Type Cable entry Battery type Current output type Alarm output type Acceptable cable outside diameter 3∼8mm : Yes : No OPTION (Factory set)
  • Totalizing indication Selection of totalizer function CODE : /TLZ
  • Totalized indication + Pulse output CODE : /PUL OPTION (Others)
  • Refer to “MODEL CODE”
  • Specification and function of each type 1) Battery type Battery :Alkali battery (LR6) x 2 pcs. Battery life :Approx. 2 years at 23 oC Auto power off mode selectable Low Battery monitor as standard

CDT1000 QUICK FLOW for Air Conditioning Digital Flowmeter TG-F976-6E TOKYO KEISO CO., LTD. 3 WIRING DIAGRAM MATERIAL and OUTLINE DIMENSION dA B 20mm Rc3/4 33 33 25mm Rc1 35 36 32mm Rc11/4 36 4 1 Rc3/4 B 2-d AA 34.5 No. Part Description Material /L54706 Indicator body Aluminum alloy Isolation valve SCS 14 /L54707 Valve Shaft SUS 316 O-ring NBR /L54708 Vent valve SUS 316 /L54709 Cap nut SCS13 /L54710 Fittings SCS 14 /L54711 Pitot tube SUS 316 /L54712 Socket SS 400

8 Three-way socket FCMB*1,2

Dimension of three-way socket *1 It is possible to attach standard material for socket (SS400 or FCMB) if requested, but material besides these materials shall be provided by customer when needed. *1,2 For the 2 MPa rating, the parts made of proper material such as S25C be selected and provided by customers considering pipe sch40. Cable entry Drain hole /L54712 Socket (CFSW) (Refer to approval drawing for the dimension I.)

8 SGP three-way socket

(JIS B 2301/CFTW) [OPTION] $%5˘˘ $%5˘˘ 6/*5 .0%& "PGG "%+ 6/*5 .0%& "PGG "%+ -NJO -NJO M ʢʣ ʢʣ ʢʣ M ʢʣ ʢʣ "JSWFOUTDSFX OUT2 OUT1 ANA OUT DC24V 4-20mA Alarm output (1) Alarm output (2) Receiver [Current output type] DC24V 4-20mA + Receiver+ - [Alarm output type] Alarm output (1)/(2) : Open collector Load: Less than 30V DC/80mA (each) - + - (OUT1 is used for the pulse output when the totalized pulse output option is added.)

CDT1000 QUICK FLOW for Air Conditioning Application Digital Flowmeter TG-F976-6E4 TOKYO KEISO CO., LTD. Piping Socket Fittings Fixing by screw Blind plug Isolation valve Hexagon socket head cap screws Equalizing pressure valve with O-ring (P4) Vent plug (2pcs) Vent valve (2pcs) O-ring (P38) O-ring (P8) O-ring (S4) Pitot tube O-ring (S31.5) Cap nut o C LRZ OUT1 100 Aoff SETADJ. kPa OUT2 cm3/h m3/h UNIT MODE CDT14 ■■ Indicator M4 x 14(4pcs) M4 x 14(4pcs) M5 x 20(4pcs) Fixing by screwFixing by screw Screwing Welding Piping Fixin g by screw Fixin g by screw Weldin g Screwin g Socket FittingsFixing by screw Bolt, Washer Blind plug Isolation valve Hexagon socket head cap screws Equalizing pressure valve with O-ring (P4) Vent plug (4pcs) Vent valve (4pcs) O-ring (P38) O-ring (P8) O-ring (S4) Indicator Pitot tube O-ring (S31.5) Cap nutSCS14 o C LRZ OUT1 100 Aoff SETADJ. kPa OUT2 cm3/h m3/h UNIT MODE CDT12 ■■ [Option]

  • Protection cover (For indicator protection) CODE : /HGC CAUTIONS ON INSTALLATION
  • Avoid direct rays and equip with a protection cover or install in the place which a direct rainstorm does not splash. (If protection cover is used, it may be difficult to read the display.) Protection cover M5 x 20(4pcs) Bolt, Washer o C OUT1 100 Aoff SETADJ. OUT2 cm3/h m3/h UNIT MODE CONSTURUCTION

CDT1000 QUICK FLOW for Air Conditioning Digital Flowmeter TG-F976-6E TOKYO KEISO CO., LTD. 5 MODEL CODE Installation type Pressure rating Main pipe size Full scale range Indicator type Application Version Option* Additional function Description Note Horizontal type Perpendicular type Nominal diameter for installation pipe Flow rate range Select for the code of Standard full scale range Battery type Current output type Alarm output type For liquid Version code Totalization indicator Battery drive 4-20mA DC (2-wire) 2 points + 4-20mA DC Provided Not provided Blank PVC lined pipe specification /TLZ /HGC /CFT /CFS /PL With protection cover at display part Three-way socket for piping (CFTW) Attachment is possible in case of the quality of the material FCMB and 1MPa specification (20 to 32 mm) Welding sockt (CFSW) Available only for SS400 (More than 40 mm) Not necessary if above-mentioned code is available. Inform us L and D dimension of figure in page 6. Consult about the details of the pipe material or Pitot-tube length. 10 1MPa class 20 2MPa class -0 2 0 20mm -0 2 5 25mm -0 3 2 32mm -0 4 0 40mm -0 5 0 50mm -0 6 5 65mm -0 8 0 80mm -1 0 0 100mm -1 2 5 125mm -1 5 0 150mm -2 0 0 200mm -2 5 0 250mm -3 0 0 300mm -3 5 0 350mm -4 0 0 400mm -4 5 0 450mm -0 5 -1 0 -2 0 -5 0 L Standard type Vertical type Carbon steel pipe for piping (JIS G 3452) Carbon steel pipe for pressure piping (JIS G 3454 Sch40) /PUL Totalized indication + Pulse output Applicable for alarm output type only. *Note) Insert “/ ” between each code when the plural codes are selected. Code example 1: [In case optional code is not selected] Horizontal installation, Connection size 50mm, 1MPa class, Full scale flow rate code[10], Battery drive type Model code: CDT1210-050-104L-A Code example 2: [In case all of the possible optional codes are selected] Vertical installation, Connection size 100mm, 1MPa class, Full scale flow rate code[05], Current output type, Totalization indicator, indication, With protection cover at display part, With welding socket Model code: CDT1410-100-055L-A/TLZ/HGC/CFS Code example 3: [In case piping type specification] Horizontal installation, Connection size 80mm, Pipe material SUS304TPD, 1MPa class, Full scale flow rate code[20], Current output type, Totalization indicator, With welding socket Model code: CDT1210-080-205L-A /TLZ/CFS/Z When the piping type is specified as seen in the above Code example 3, it will be additional function. Moreover, in case socket and three-way socket are prepared by customer, Pitot tube length may be changed by installation dimension. This will be an additional function. Accordingly the last letter of model code will be “ /Z” in case of such special specification as not mentioned in the above model code.

CDT1000 QUICK FLOW for Air Conditioning Application Digtal Flowmeter TG-F976-6E6 INSTALLATION 1) Keep the upstream and downstream straight runs as required. 2) To install the flowmeters, Drill a hole of 35mm diameter into the pipe having more than or equal to 40mm diameter. Use the three-way socket for the pipe having less than or equal to 32 mm diameter. 3) Select and drill the hole at right place so that the final fixed pos- ture of indicator should be horizontal. 4) Weld the socket to the drilled hole. The centerline of the socket must be in line with the one of the pipe. 5) Screw the CDT1000 into the welded socket to complete the installation. Three-way socket Rc3/4 Rc3/4 Three-way socket Ø35 Ø35 Piping CDT12 ■■ CDT14■■ Three-way socket (20 to 32mm)Straight piping (/H1108440mm) SUGGESTIONS

  • The model CDT 12(4) 10 flowmeter is calibrated based on the inside diameter of JIS G3452 SGP . For the model CDT 12(4) 20, calibrated JIS G3454 Sch.40. Consult TOKYO KEISO if pipes are different from above. Specific calibration is required.
  • Straight length for upstream and downstream is required for accurate measurement as shown in the following table, Size Upstream Downstream /H1101732mm /H1108410D /H110845D /H1108440mm /H110845D /H110843D Note) D : Inside diameter of main pipe.
  • Run the fluid fully in the pipe. Otherwise it could not be measured.
  • Vent the air before measurement. See CDT1000 Instruction Manual for further details. LINING AND OTHER PIPING
  • The full scale flow rates are based on when the flow runs through the inside diameter of the pipe lined with PVC which consists of a tee joint of the Eslo coat LX made by Sekisui Chemical Co.’s Eslon®. If you use the tee joints with the different inside diameter from above, the extra calibration is required. For further consultation inform us of the dimension “D” in the following drawing.
  • When the main pipe size is between 32 mm and 150 mm, provide either one of the following tee joint and bushing assembly to make the connection size 20 mm: — tee joint with 25 mm in branch line + A bushing with 25 mm x 20 mm — tee joint with larger than 25 mm in branch line + One or more bushings in series to make the final connection size 20 mm For further consultation inform us of the dimension “L” in the following drawing.
  • Piping can be customized.
  • Please determine the values of “D” and “L” in the figure below and the kind of pipe and then contact us. Head Office : Shiba Toho Building, 1 – 7 – 24 Shibakoen, Minato-ku, Tokyo 105 – 8558 Tel : +81-3 – 3431 – 1625 (KEY) ; Fax : +81-3 – 3433 – 4922 * Specification is subject to change without notice. Bushing (R1 x Rc3/4) 32mm L Ø D Lining piping (PVC) Other piping

ORDERING INFORMATION

  1. Model code 2. Quantity Rc3/4 Ø D L