METAL TUBE VARIABLE AREA FLOWMETER AM7000 Series GENERAL The metal tube variable area flowmeter AM7000 Series has been developed from AM-1000 Series which were based on the long time experience of TOKYO KEISO in the field of flow measurement. In addition to highly reliable local indicators, a variety of outputs are equipped to meet the requirements. Standard metallic materials and full line-up of lined materials cover almost all fluids even they are very corrosive. AM7000 covers liquids, gases and steam measurement applications in various industrial fields.
FEATURES
❑ FULL LINE-UP TO MEET ALL POSSIBLE REQUIREMENTS !! All the necessary functions required for variable area flowmeter, i.e. local indication, electric transmitters, local flow integration HART communication, integrator with scaled pulse output and alarm are now available from one line. ❑ COMPACT DESIGN Smaller and lighter…To suit modern needs. ❑ WIDE PRESSURE RANGE 150 lbs and 300 lbs rating are available as standard and higher pressure versions are also available as option. ❑ WIDE RANGE OF MATERIAL SELECTION All possible metallic materials and a wide variety of lining materi- als are available even for corrosive fluids. ❑ HART COMMUNICATION PROTOCOL CAN BE CONNECTED. ❑ CORRESPONDING TO EXPLOSION-PROOF CONSTRUCTION Certification: TIIS, KOSHA, NEPSI, ATEX & IECEx ❑ DUST TIGHT AND WATER IMMERSION PROOF IP67 TG-F2026-E21 22th edition Nov 2025 K 1st edition Oct 2009 K
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 2 TOKYO KEISO CO., LTD. - - / / L E H T R N M W Dust tight, water immersion proof, non-explosionproof E Flameproof version S Intrinsic safety version Not applicable to local integrator with scaled pulse output - 01 Material of main body :C.S./SUS304 Material of float :SUS304 - 0 2 SUS304 SUS304 - 0 3 SUS316 SUS316 - 0 4 SUS316L SUS316L - R1 Rubber lining PVC or ETFE lining - R2 Rubber lining Fluorocarbon resin lining or ETFE lining - F1 Fluorocarbon resin lining Fluorocarbon resin lining or ETFE lining - P1 PVC lining PVC or ETFE lining - G1 Glass lining Fluorocarbon resin lining or ETFE lining - G2 Glass lining MA276 - ZZ Others Others J1 JIS 10K Other standards J4 JIS 20K J6 : JIS40K J5 JIS 30K J7 : JIS63K A2 ANSI CLASS 150 A7 : ANSI CLASS 600 A5 ANSI CLASS 300 A8 : ANSI CLASS 900 A6 ANSI CLASS 400 A9 : ANSI CLASS 1500 P2 JPI CLASS 150 P7 : JPI CLASS 600 P5 JPI CLASS 300 P8 : JPI CLASS 900 P6 JPI CLASS 400 P9 : JPI CLASS 1500 ID IDF Clamp Applicable for sanitary ZZ R F C J Clamp-on type Ring joint Applicable for sanitary Z - 1 - 2 - 3 - 4 - 5 - 6 - 8 - A - B - C - D - Z /L B /F B /J S /J F /J U /J V /D L /D U /S R /S L Slurry /E 1 /E 2 /H 1 /H 2 /T 1 H / R Reed switch / N M Proximity switch / Microswitch /J E E E E E I I I I TIIS Flameproof version /K KOSHA Flameproof version /C NEPSI Flameproof version /E ATEX Flameproof version /E IECEx Flameproof version (Specify separately.) /J TIIS Intrinsical safety version /K KOSHA Intrinsical safety version /C NEPSI Intrinsical safety version /E ATEX Intrinsical safety version Explosionproof type Not applicable to reed switch and proximity switch. See page 12 for details. Not applicable to local integrator with scaled pulse output. See page 12 for details. Output function Electric transmitter Electric transmitter (intrinsically safe) Electric transmitter with HART communication Electric transmitter with HART communication (intrinsically safe) Local iintegrator+Electric transmittert+integrator with scaled pulse (or alarm) Local indication+Analog current output with HARTcommunication+Integrated pulse (or alarm) Vacuum jaket Liquid damper Gas damper Sanitary (#320 to #400) 150 mm (6") 200 mm (8") Others Additional function Long body Radiating fin Semi-jacket Full-jacket Upper jacket Connection size 15 mm (1/2") 20 mm (3/4") 25 mm (1") 40 mm (1-1/2") 50 mm (2") 65 mm (2-1/2") 80 mm (3") 100 mm (4") 125 mm (5") Connection R.F. F.F. Others Explosionproof Wetted material Rating Others Function of indicator Local indication Electric transmitter Electric transmitter with HART communication Local integration Reed switch Proximity switch Microswitch Flow direction Bottom→Top Bottom→Top side Bottom side→Top side Left→Right Right→Left, Front→Rear, Rear→Front Function 2 code etc. Basic model and Function 1 code may be indicated in the quotation. AM7 Specifications Basic model Material/Connection code Function 1 code Additional function 1Additional function 2 □ shows conditions of switch action. A : High alarm CLOSE(ON), B : High alarm OPEN(OFF), C : Low alarm CLOSE(ON), D : Low alarm OPEN(OFF) Ex. Reed switch/2-point alarm (High alarm CLOSE×1, OPEN×1): /RAB /M 2 M20×1.5(F) Not applicable to local integrator with scaled pulse output /G 1 G1/2(F) Not applicable to local integrator with scaled pulse output /G 2 G3/4(F) Applicable to local integrator with scaled pulse output /N 1 NPT1/2(F) Not applicable to local integrator with scaled pulse output /N 2 NPT3/4(F) Applicable to local integrator with scaled pulse output /O L /W L /A P /E P Electrolytic polishing /L T /P C Waterproof connector Not applicable to flameproof version /F G Flameproof cable gland /A C /W S Double scale, output for main scale Not applicable to alarm output /W E Double scale, output for main and sub scalels Not applicable to alarm output and local integration Accessory Other accessories Double scale Cleaning Oil-free treatment Water-free treatment Test Airtight test Cable entry Pickling treatment Finish OptionSpecial spec. MODEL CODE
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 3 STANDARD SPECIFICATION
- PRESSURE RATING 150lbs (10K) class, 300lbs (20K) class On request Consult factory for higher pressure. ✽ Only 150lbs (10K) class is available for full jacketed flow meters (AM7□□□/JF) and lining material flow meters.
- MATERIAL Carbon steel, SUS304, SUS316, SUS316L, Rubber lining, Fluorocarbon resin lining, PVC lining and Glass lining On request Other metallic material General purpose 150lbs (10K) class Medium purpose 300lbs (20K) class Fluid Temp. (°C) Max. /f_luid press. (MPa) up to 120 1.4 up to 220 1.2 up to 300 1.0 up to 120 3.4 up to 220 3.1 up to 300 2.9 up to 350 2.6 up to 400 2.3 Lining type Refer to Page 4 1.0
- FLUID PRESSURE Consult factory for the specifications of higher pressure model. General purpose Medium purpose Higher purpose JIS 10K FF JIS 20K RF Consult factory ANSI, JPI, DIN Other type are available
- CONNECTION Flange connection [On request Screw connection (Consult factory)] Only RF (Raised faced) flange is available for glass, PVC and fluorocarbon resin lined flow meters. Only FF (Flat faced) flange is available for rubber lined flow meters.
- METER SIZE 15 to 150 (Please refer to M Series for more than 200) Local indication Local indication Electric transmitter Local indication Electric transmitter HART communication Local indication Electric transmitter Local integration Pulse output Alarm output Local indication Alarm output AM7/uni25A1/uni25A1/uni25A1/E/uni25A1AM7/uni25A1/uni25A1/uni25A1/H/uni25A1AM7/uni25A1/uni25A1/uni25A1/T/uni25A1AM7/uni25A1/uni25A1/uni25A1 /R/uni25A1, /N/uni25A1, /M/uni25A1AM7/uni25A1/uni25A1/uni25A1
- FUNCTIONS
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 4 TOKYO KEISO CO., LTD. AM7□□□ (LOCAL INDICATION)
- AMBIENT TEMPERATURE –30 to 80°C
- Dimension of indicator 12 12150 174 230 65 165 Approx. mass: 2.5kg Type Operating temperature range of /f_luid AM7/uni25A1/uni25A1/uni25A1/DU 0 to 149°C AM71/uni25A1/uni25A1 –20 to 200°C *1 *2 AM72/uni25A1/uni25A1 AM73/uni25A1/uni25A1 0 to 149°C *3 AM72/uni25A1/uni25A1/FB AM73/uni25A1/uni25A1/FB (Fluid : Gases) to 0°C 150 to 400°C *4 AM72/uni25A1/uni25A1/FB AM73/uni25A1/uni25A1/FB (Fluid : Liquids) 150 to 400°C *2 *4 Rubber lining –10 to 80°C Fluorocarbon resin lining –10 to 80°C PVC lining 0 to 60°C Glass lining –10 to 110°C * Notes : The flowmeters out of the above temperature range may be available on your request. Consult TOKYO KEISO Co., Ltd. for details. *1 Available up to 250°C as an option. *2 A very low temperature version is also available as an option. *3 Select AM72□□/FB or AM73□□/FB when temperature of gas service is lower than 0°C , or 150°C or higher. Select AM72□□ /FB or AM73□□/FB when temperature of liquid service is 150°C or higher. Available as low as –50°C as an option for lower than 0°C liquid service. *4 The Max. fluid temperature of ordinary type 150 lbs class is 300°C.
- FLUID TEMPERATURE (a) Metallic material (b) Lining material * Max. 80°C for fluorocarbon resin float ✽ ±2% F .S. for resin material float version
- STANDARD SCALE LENGTH 70mm
- RANGEABILITY 10:1 (10:2 for the slurry type)
- INDICATOR CONSTRUCTION Dust tight and water immersion proof IP67
- PAINTING COLOR PAINTING Measuring tube (Carbon steel), Indicator body Indicator cover · Transmitter Cooling /f_in COLOR Jade green Light gray Metallic silver (Munsell 7.5BG4/1.5) (Munsell N7.5)
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 5 AM7□□□ /E□ (LOCAL INDICATOR WITH ELECTRIC TRANSMITTER) AM7□□□ /E□ indicates flow rate by pointer and scale plate, and outputs electric (4 to 20mA DC) signal which is proportional to flow rate. In addition to the dust tight and water immersion proof type, the intrinsically safe (dust explosion-proof) and flame proof versions are available.
- SPECIFICATION OF TRANSMITTER Power supply voltage : 10 to 30V DC ❲Voltage between transmitter terminals❳ (For Intrinsically safe version : 10 to 28V DC/For TIIS Flameproof version: 12 to 30 VDC) Current output : 4 to 20mA DC ❲Effective output range : 4.0 to 21.6mA At abnormal condition, however, 22.8mA or 3.75mA as an option can be output.❳ Allowable load resistance : Less than 830Ω (580Ω or less / 24V DC) Determine the allowable load resistance for each supply voltage using following formula. Allowable load resistance ≦(Power supply voltage [V] –10 ) / 0.024 [Ω] The allowable load resistance includes the one of circuit wiring. Output accuracy : ±1.0%F .S. (Against flow calibration) Low cut off : 0 to 20%F .S. (default 7%F .S.) Damping : 0 to 20s (default 1s) Cable entry : Weather proof 2–M20×1.5, 2–G1/2, 2–NPT1/2, Weather proof connector : Intrinsically safe & Flame proof 2–M20×1.5, 2-G1/2, 2–NPT1/2, Packing type cable gland Note : The packing type cable gland model SXC -16BY made by Shimada Electric Co. shall be used for the TIIS flame proof construction. The cable entry for the indicator is G1/2 only. Construction : Dust tight and water immersion proof IP67 : Intrinsically safe Ex ia IIC T1 to T6 AM7□□□/E2/□I (dust explosion-proof) The temperature class of TIIS certified products is T6. II 2 D Ex ia IIIC T135°C Db (For ATEX certified products) : Flame proof Ex d IIC T1 to T6 AM7□□□/E1/□E The temperature class of TIIS certified products is T4. Ambient temp. : Dust tight and water immersion proof –20 to 70°C : Intrinsically safe –20 to 60°C : Flame proof –20 to 55°C (For TIIS certified products) –20 to 60°C (For other certified products) Insulation resistance : 20 MΩ or more / 500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 500V AC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR / TRANSMITTER
- TERMINAL AND WIRING 12 150 12 174 110 Cable entry 41 69 φ74 155 75 30 50.5 310.5 Approx. mass: 3.7kg A E Power supply Load resistance
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 6 TOKYO KEISO CO., LTD. AM7□□□/H□ (LOCAL INDICATOR WITH ELECTRIC TRANSMITTER & HART COMMUNICATION) AM7□□□/H□ indicates flow rate by pointer and scale plate, and outputs electric (4 to 20mA DC) signal equipped with HART Communication complying with Multi-drop. In addition to the dust tight and water immersion proof type, the intrinsically safe (dust explosion-proof) and flame proof versions are available.
- SPECIFICATION OF TRANSMITTER Power supply voltage : 10 to 30V DC ❲Voltage between transmitter terminals❳ (For Intrinsically safe version: 10 to 28V DC/For TIIS Flameproof version: 12 to 30 VDC) Current output : 4 to 20mA DC ❲Effective output range : 4.0 to 21.6mA At abnormal condition, however, 22.8mA or 3.75mA as an option can be output.❳ Allowable load resistance : 230 to 830Ω (Not less than 230Ω load resistance is needed for “with HART communication.”) Determine the allowable load resistance for each supply voltage using following formula. Allowable load resistance ≦ (Power supply voltage [V] –10) / 0.024 [Ω] The allowable load resistance includes the one of circuit wiring. Output accuracy : ±1.0%F .S. (Against flow calibration) Low cut off : 0 to 20%F .S. (default 7% F .S.) Damping : 0 to 20s (default 1s) Cable entry : Weather proof 2–M20×1.5, 2–G1/2, 2–NPT1/2, Weather proof connector : Intrinsically safe & Flame proof 2–M20×1.5, 2–G1/2, 2–NPT1/2, Packing type cable gland Note : The packing type cable gland model SXC -16BY made by Shimada Electric Co. shall be used for the TIIS flame proof construction. The cable entry for the indicator is G1/2 only. Construction : Dust tight and water immersion proof IP67 : Intrinsically safe Ex ia IIC T1 to T6 AM7□□□/H2/□I (dust explosion-proof) The temperature class of TIIS certified products is T6. II 2 D Ex ia IIIC T135°C Db (For ATEX certified products) : Flame proof Ex d IIT1 to T6 AM7□□□/H1/□E The temperature class of TIIS certified products is T4. Ambient temp. : Dust tight and water immersion proof –20 to 70°C : Intrinsically safe –20 to 60°C : Flame proof –20 to 55°C (For TIIS certified products) –20 to 60°C (For other certified products) Insulation resistance : 20 MΩ or more/500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 500V AC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR / TRANSMITTER
- TERMINAL AND WIRING 12 150 12 174 110 Cable entry 41 69 φ74 155 75 30 50.5 310.5 Approx. mass: 3.7kg A ELoad resistance Power supply
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 7 AM7□□□/T□ (LOCAL INDICATOR WITH LOCAL INTEGRATION, INTEGRATION PULSE, ELECTRIC TRANSMISSION AND HART COMMUNICATION) With local flow rate indication, AM7□□□/T□ has the functions of local flow integration, integration pulse output, 4 to 20mA electric output and Hart communication. This series serves the custody of flow. The additional magnetic sensing switches to conventional push buttons are available for cus- tomers' convenience. In addition to the dust tight and water immersion proof type, the flame proof version is available.
- SPECIFICATION OF TRANSMITTER Integration : 6 digit red LCD (With 8 digit scaling and reset function) Count rate : Less than 10Hz (Less than 36000 c/h) Pulse or Alarm output : NPN Open collector 2 point select output (Pulse width : 30ms, 50ms, 100ms, 200ms, 500ms) : 1 point alarm + pulse output, or 2 points alarm output (Alarms are selectable from the flow rate or the integrated flow alarm.) : Max. voltage 30V DC, max. current 50mA (The power supply circuit and the output circuit are insulated.) Reverse-connected protection, Residual voltage when turning it on more less 1.2V (10mA) Integration accuracy : ±1.0%F .S. (Against flow calibration) Power supply : 16 to 30V DC ❲Voltage between transmitter terminals❳ Current consumption : Less than 60mA Current output : 4 to 20mA DC ❲Effective output range : 4.0 to 21.6mA At abnormal condition, however, 22.8mA or 3.75mA as an option can be output.❳ Allowable load resistance : Less than 830Ω (In case of HART communication version : 230 to 830Ω) Determine the allowable load resistance for each supply voltage using following formula. Allowable load resistance ≦ (Power supply voltage [V] – 10) / 0.024 [Ω] The allowable load resistance includes the one of circuit wiring. Output accuracy : ±1.0%F .S.(Against flow calibration) Low cut off : 0 to 20%F .S. (default 7%F .S.) Damping : 0 to 20s (default 1s) Cable entry : 2–G3/4, 2–NPT3/4, Packing type cable gland Note : The packing type cable gland model SXC -22BY made by Shimada Electric Co. shall be used for the TIIS flame proof construction. The cable entry for the indicator is G3/4 only. Construction : Dust tight and water immersion proof IP67 : Flame proof Ex d IIC T1 to T6 AM7□□□/T□/□E The temperature class of TIIS certified products is T4. Ambient temp. : Dust tight and water immersion proof –20 to 70°C : Flame proof –20 to 55°C (For TIIS Certified products) –20 to 60°C (For other Certified products) Insulation resistance : 20 MΩ or more/500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 500V AC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR/TRANSMITTER
- TERMINAL AND WIRING 12 150 12 174 41 79.5 157.5 230 57 64.5Cable entry φ90 53.5 101.5 105.5 Approx. mass: 3.8kg 1 2 3 4 5 6 7 8 9 10 Terminal No. Terminal wiring DO1+ DO1– DO2+ DO2– 5 6 PS+ PS– FG (Attention) DO: Contact output terminals, R: 4–20mA analog output terminals, PS: Power supply, FG: Grounding
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 8 TOKYO KEISO CO., LTD. AM7□□□/R□ (LOCAL INDICATOR WITH REED SWITCH TYPE ALARM) AM7□□□/R□ indicates flow rate by pointer and outputs SPST contact at set point for flow alarm. In addition to the dust tight and water immersion proof type, the intrinsically safe (dust explosion-proof) version is available.
- SPECIFICATION OF TRANSMITTER Alarm point : 2 points (1 point high alarm, 1 point low alarm or 2 points high and low alarm) Switch : Self-holding reed switch (a or b contact) Rating : Reed switch (SPST) 10VA AC, 10W DC as resistance load Max. 125V AC/0.5A, Max. 100V DC/0.5A Setting accuracy : ±1.5% F .S. (Against flow calibration) Note: While switch is on, and if any other flow rate than the alarm setting value is indicated, it may result in causing wrong accuracy. Reset span : Less than 10% F .S. (Against flow calibration) Cable entry : G1/2 or NPT1/2 or others Enclosure : Dust tight and water immersion proof IP67 : Intrinsically safe Ex ia IIC T1...T6 (dust explosion-proof) (TIIS certified products are subject to the safety barrier. See Page 12 for details.) II 2 D Ex ia IIIC T135°C Db (For ATEX certified products) Ambient temp. : –10 to 60°C Insulation resistance : 100 MΩ or more/500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 1500V AC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR / TRANSMITTER
- TERMINAL AND WIRING Terminal No. High alarm Terminal No. Low alarm Wiring of high alarm Wiring of low alarm Note : Terminal No.4 and 5 are not used for 1 point high alarm. Likewise, terminal No. 1 and 2 are not used for 1 point low alarm. High alarm Low alarm 12 150 12 174 61.5 291.5 36.5 Cable entry (47) (37)43 230 Approx. mass: 2.8kg
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 9 AM7□□□/N□ (LOCAL INDICATOR WITH PROXIMITY SWITCH TYPE ALARM) With local flow rate indication, AM7□□□/N□ has a proximity switch which outputs alarm signals complying with NAMUR standard. In addition to the dust tight and water immersion proof type, the intrinsically safe (dust explosion-proof) version is available.
- SPECIFICATION OF TRANSMITTER Alarm point : 2 points (1 point high alarm, 1 point low alarm or 2 points high and low alarm) Switch : Proximity switch Power supply voltage : 8V DC Operating current : Proximity switch complying with NAMUR, ON :1mA or less, OFF : 3mA or more Setting accuracy : ±1.5% F .S. (Against flow calibration) Reset span : Less than 1.5% F .S. (Against flow calibration) Cable entry : G1/2 or NPT1/2 or others Enclosure : Dust tight and water immersion proof IP67 : Intrinsically safe Ex ia IIC T1...T6 (dust explosion-proof) (The temperature class of TIIS certified products is T5. See Page 12 for details.) II 2 D Ex ia IIIC T135°C Db (For ATEX certified products) Ambient temp. : Dust tight and water immersion proof –25 to 80°C : Intrinsically safe –20 to 60°C TIIS certified transmitter –20 to 50°C Other certified transmitters (Ambient temperatures above are subject to the safety barrier.) Insulation resistance : 100 MΩ or more/500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 500V DC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR / TRANSMITTER 12 150 12 174 61.5 291.5 36.5 Cable entry (47) (37)43 230 Approx. mass: 2.8kg
- TERMINAL AND WIRING High alarm Low alarm Terminal No. High alarm Terminal No. Low alarm Note : Terminal No.4 and 5 are not used for 1 point high alarm. Likewise, terminal No. 1 and 2 are not used for 1 point low alarm.
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 10 TOKYO KEISO CO., LTD. AM7□□□/M□ (LOCAL INDICATOR WITH MICRO SWITCH TYPE ALARM) With local flow rate indication, AM7□□□/M□ has a micro switch which outputs SPDT alarm signals. In addition to the dust tight and water immersion proof type, the intrinsically safe (dust explosion-proof) version is available.
- SPECIFICATION OF TRANSMITTER Alarm point : 2 points (1 point high alarm, 1 point low alarm or 2 points high and low alarm) Switch : Micro switch (c contact) Rating : 250V AC/5A as resistance load Setting accuracy : ±1.5% F .S. (Against flow calibration) Note: While switch is on, and if any other flow rate than the alarm setting value is indicated, it may result in causing wrong accuracy. Cable entry : G1/2 or NPT1/2 or others Enclosure : Dust tight and water immersion proof IP67 : Intrinsically safe Ex ia IIC T1...T6 (dust explosion-proof) (TIIS certified products are subject to the safety barrier. See Page 12 for details.) II 2 D Ex ia IIIC T135°C Db (For ATEX certified products) Ambient temp. : Dust tight and water immersion proof –25 to 80°C : Intrinsically safe –20 to 60°C Insulation resistance : 100 MΩ or more/500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 1500V AC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR / TRANSMITTER 12 150 12 174 61.5 291.5 36.5 Cable entry (47) (37)43 230 Approx. mass: 2.8kg Terminal No. High alarm Terminal No. Low alarm COM. COM. NC. NC. NO. NO. Note : Terminal No.4, 5 ,6 are not used for 1 point high alarm. Likewise, terminal No. 1,2,3 are not used for 1 point low alarm. NC. NO. COM NC. NO. COM High alarm Low alarm
- TERMINAL AND WIRING
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 11 AM7□□□/M□/□E (FLAME PROOF) AM7□□□/M□/□E outputs an alarm signal by SPDT contacts by adding a micro switch to the local flow rate indicator.
- SPECIFICATION OF TRANSMITTER Alarm point : 2 points (1 point high alarm, 1 point low alarm or 2 points high and low alarm) Switch : Micro switch (c contact) Rating : 125V AC/1A or 30V DC/1A Setting accuracy : ±1.5% F .S. (Against flow calibration) Note: While switch is on, and if any other flow rate than the alarm setting value is indicated, it may result in causing wrong accuracy. Cable entry : M20×1.5 or NPT1/2 Enclosure : Dust tight and water immersion proof IP67 : Flameproof Ex d IIC T1 to T6 (The temperature class of TIIS certified products is T4. See Page 12 for details.) Ambient temp. : Dust tight and water immersion proof –25 to 80°C : Flameproof –20 to 55°C TIIS-certified transmitter –20 to 60°C Other certified transmitters Insulation resistance : 100 MΩ or more/500V DC (between batch of power supply terminal and indicator case) Withstand voltage : 1500V AC/1min (between batch of power supply terminal and indicator case)
- DIMENSION OF INDICATOR / TRANSMITTER Terminal No. High alarm Terminal No. Low alarm COM. COM. NC. NC. NO. NO. Note : Terminal No.4, 5 ,6 are not used for 1 point high alarm. Likewise, terminal No. 1,2,3 are not used for 1 point low alarm. NC. NO. COM NC. NO. COM High alarm Low alarm
- TERMINAL AND WIRING 12 150 12 174 110 Cable entry 41 69 φ74 155 75 30 50.5 310.5 Approx. mass : 3.7kg
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 12 TOKYO KEISO CO., LTD. AM7□□□/□□/□E (FLAMEPROOF VERSION) The flameproof model with electric or alarm output (microswitch) as an additionally specified feature,is available complying with the stan- dard.
- INTRINSICALLY SAFE SPECIFICATION OF CURRENT TRANSMISSION
- INTRINSICALLY SAFE SPECIFICATION OF ALARM OUTPUT AM7□□□/□□/□I [INTRINSICALLY SAFE VERSION (dust explosion-proof)] Intrinsically safe modes complying with the standard are available depending on additionally specified features of the current transmission, or alarm output. G1/2 G1/2 or NPT1/2 For the current transmission ,current transmission HART communication. For the site integration ※8mm to 12mm (standard:10 mm to 12mm) ※12mm to 16mm (standard: 14mm to 16mm) SXC-16BY By Simada Electric Co. G3/4 SXC-22 By Simada Electric Co. G3/4 or NPT3/4 For the alarm output ※6mm to 12mm (standard: 10mm to 12mm) M20×1.5 EXPC-16B by Simada Electric Co. M20×1.5 G1/2 or NPT1/2 NOTE) Be sure to use the cable gland shown in the figure below for the TIIS flameproof version (current transmission,current transmission HART communication, or local integration or alarm output). ※Cable diameters applicable to cable glands included in the prodect. TIIS KOSHA NEPSI ATEX IECEx Ex d IIC T4 Ex d IIC T6 to T1 Ex d IIC T1 to T6 Gb II2G Ex d IIC T6... T1 Gb Ex d IIC T6... T1 Gb EX type Class Functions Current transmission Current Transmission HART communication Local integration Alarm output microswitch TIIS KOSHA NEPSI ATEX Ex ia IIC T6 Ex ia IIC T5 Ex ia IIC T1 to T6 Ex ia IIC T1 to T6 Gb II 2 G Ex ia IIIC T1... T6 Gb II 2 D Ex ia IIIC T135° C Db EX type Class Functions Current transmission Current Transmission HART communication Local integration Alarm output (Note1) (Note1) Note 1: The read switch type (AM7□□□/R□) and the micro switch type (AM7□□□/M□) are available only when the intrinsically safe relay barrier is used. The temprature class of the TIIS intrinsically safe proximity switch type (AM7□□□/N□) is T5. Consult us for details. ○ ○ - ○ Max.voltage for intrinsically safe circuit Max.current for intrinsically safe circuit Max.power consumption for intrinsically safe circuit Capacitance inside intrinsically safe circuit Inductance inside intrinsically safe circuit Current transmission 28V DC 93mA 650mW 5nF 0.2mH Max.voltage for intrinsically safe circuit Max.current for intrinsically safe circuit Max.power consumption for intrinsically safe circuit Capacitance inside intrinsically safe circuit Inductance inside intrinsically safe circuit Recommended relay barrier Read switch Proximity switch AM7□□□/N□/□I Micro switch 30V DC 500mA EB3C (IDEC)KFD2-SR2-Ex1.W (P&F) (Note 2) 30V DC 500mA EB3C (IDEC) 10.5V DC 13mA 34mW 150nF 150 μ H 16V DC 25mA 64mW 150nF 150 μ H Note: 2 The TIIS intrinsically safe proximity switch has been certified in combination with barriers made by PEPPERL+FUCHS. Be sure to use intrinsically safe proximity switches with the barriers shown below. For other proximity switches, use the explosion-proof barriers conforming to the rated valuesabove. TIIS intrinsically safe barrier For 1ch : KFD2-SR2-Ex1.W For 2ch : KFD2-SR2-Ex2.W TIIS intrinsically safe product Other products
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 13 ADDITIONAL FUNCTION
- Cooling fin (Model AM7□□□/FB) A cooling fin is to be provided between tube part and indicator hous- ing to release fluid heat in case fluid temperature is more than 150°C. Cooling fin is available for models AM72□□ (Bottom-Top side), AM73 □□ (Bottom side-Top side), AM76 □□ (Left- Right) and AM77□□ (Right-Left).
- Jacket (Model AM7□□□/JS, Semi-jacket, AM7□□□/JF, Full-jacket) Heating jacket is available for the application of high viscosity and/or sticky fluids. Semi-jacket covers tube part only and full-jacket covers flanges as well. Steam inlet/outlet is screw connection (Rc or NPT). Heating jacket is available for AM71□□ (Bottom-Top) and AM72□□ (Bottom-Top side). Only 150 lbs rating is available for full-jacketed flowmeters (AM□□□/JF).
- Liquid damper (Model AM7□□□/DL) A damper is to be provided for steam and gas applications to prevent vibration of float. A damper pot is provided at the bottom of tube part in which damper liquid (silicon or diflon oil) is contained. The friction between damper liquid and damper makes the float movement smooth for stable indication and durability of moving part. Damper is also recommended for liquid application with heavy pulsation. Available types are AM73□□ (Bottom side-Top side), AM76□□ (Left- Right) and AM77□□ (Right-Left).
- Gas damper (Model AM7□□□/DU) Gas damper is available for gas measurement application which does not require damper liquids. (Gas dampers are available for metallic flowmeters only.) Mechanical damper is integrated at the part of float guide which con- sists of piston and cylinder. As it is not required to install liquid damp- er at the bottom of flowmeters, it contributes to increase the flexibility of piping design. Also it is not required to fill damper liquid that saves maintenance labour works. Gas damper is applicable for gas measurement applications and not suitable for liquids and steam. Also chlorine gas (easy to form chemi- cal compound) and gas containing rust, trash and oil may hinder the function of piston part. Consult factory for details. Available size is 20mm to 100mm (Not available for 15mm) and only for metallic mate- rial (Not for lined material). Flow Float guide Body Fin Indicator 2-Rc1/4 Lead pipe jackets Lead pipe Jackets pipe Body 2-Rc1/4 2-Rc1/4 Lead pipe jackets Lead pipe Jackets pipe Body 2-Rc3/8 Semi-jacket Full-jacket Flow Damper pot Damper Damper liquid Float rod Cylinder Piston Float rod Tapered tube Float
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 14 TOKYO KEISO CO., LTD.
- Slurry (Model AM7□□□/SL) The structure of the float and float part allows solids to pass easily. Accordingly, this model is suitable for measuring liquids containing fibers, granules, etc. In addition to the standard stainless steel, PVC lining is available, which is suitable for plating drainage and other highly corrosive liquids. Guide Float rod Float
- Sanitary (Model AM71□□/SR) This model is designed and manufactured for sanitary processes. It can be fitted onto process lines through IDF clamps (ISO standard). All wetted parts are buff polished (#320 to #400). It can be easily disassembled and assembled for cleaning. The electrolytic polish - ing is also available as an option. See the Technical Guidance TG- F1152 of AM7000/SR series. Meter size Size φ 0.01 0.15 0.2 0.3 0.5 0.8 1.0 100 1.0 125 1.0 150 1.0 Allowable size of solid matter in measuring fluid (mm)
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 15 Q water (m3/h) Pressure loss (kPa) Mass (approx.) Mass (approx.) Note: The mass shown in the table is for the local indicator, and it is also same for the mass in the subsequent tables. In case of "with transmission function," refer to the outside dimension for each model. Figures in ( ) are those of 20K class. 100 100(Large flow type) 125 125(Large flow type) 150 150(Large flow type) 6.5 6.0 7.3 9.0 6.3 7.8 9.1 12.0 20.0 14.0 22.0 18.0 28.0 104 110 118 125 137 150 163 350 350 350 400 400 450 450 450 500 500 104 110 118 125 137 350 400 400 400 450 500 500 500 ( 1.5) ( 3.8) ( 7.15) (15.1) (26.5) (39.5) (67.5) (100) ( ̶ ) ( ̶ ) ( ̶ ) ( ̶ ) 1.5 4.06 7.15 15.1 27.5 40.5 71.9 100 110 150 150 200 0.1~0.75 (0.7) Meter size (B) (mm) L (mm) (B) (mm) L (mm) 10K, Class 150 20K, Class 300 /uni25A0 Table 1 No Tapered tube Float ass'y Lower body Flange Float guide Indicator Other special metallic material available on request. SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 SUS316 SUS316 SUS316 SUS316 SUS316 ADC12 SUS316L SUS316L SUS316L SUS316L SUS316L ADC12 Description Class 1 Class 2 Class 3 Class 4 /uni25A0 Table 2 Meter size Pressure loss (kPa) L JIS10K(B) Size (mm) Mass (approx.)Q air [m3/h(nor)] 100 10.0 10.0 12.0 10.0 16.5 23.0 24.0 500 500 500 500 600 600 600 104 110 118 125 137 16~50 120 210 420 820 1200 2050 /uni25A0 Table 5 No Tapered tube Float ass'y Lower body Flange Float guide Indicator Other special metallic material available on request. SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 SUS316 SUS316 SUS316 SUS316 SUS316 ADC12 SUS316L SUS316L SUS316L SUS316L SUS316L ADC12 Description Class 1 Class 2 Class 3 Class 4 /uni25A0 Table 6 DIMENSIONS, MATERIAL, PRESSURE LOSS, FLOW RATE TABLE
- AM71□□ (Flow direction : Bottom—Top) AM71 □□ (Flow direction : Bottom—Top, Large flow type) AM71□□/LB (Flow direction : Bottom—Top, Long body design) For liquid [METALLIC MATERIAL] *1 Float rod comes out 70mm during operation in meter size 20mm to 150mm. The straight length of downstream pipe with the same size as the flowmeter must be more than 70 mm for a free movement of the float rod. For AM71□□ (Flow direc- tion: Bottom- Top, Large flow type), the float rod does not come out. The material of the tapered tube is SCS16. In case of AM71 □□/LB (Bottom-Top, Long body design) this coming out is avoided by extending the tube length. The extension length of body (L dimension) is 130mm for 10K (150lbs) version. Consult factory for length of 20K (300lbs) version.
- AM71□□/DU (Flow direction : Bottom—Top, with gas damper) For gas (70)L (B) L (B) 100 125 150 6.5 6.0 7.3 9.0 6.3 7.8 9.1 12.0 14.0 18.0 104 110 118 125 137 150 163 350 350 350 400 400 450 450 450 500 500 104 110 118 125 137 350 400 400 400 450 500 500 500 ( 1.5) ( 3.6) ( 6.8) (13.5) (26.5) (37.5) (65) ( ̶ ) ( ̶ ) 1.5 3.9 7.5 15.1 27.5 40.5 110 150 0.1~0.7(0.7) Meter size Q water (m3/h) Rangeability 10:2 Pressure loss (kPa) (B) (mm) L (mm) Mass (approx.) (B) (mm) L (mm) Mass (approx.) 10K, Class 150 20K, Class 300 Note: Rangeability for models with the SL code is 10:2. Note: The mass shown in the table is for the local indicator, and it is also same for the mass in the subse- quent tables. In case of "with transmission function," refer to the outside dimension for each model. /uni25A0 Table 3 Figures in ( ) are those of 20K class. subse- quent No Tapered tube Float ass'y Lower body Flange Float guide Indicator Other special metallic material available on request. SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 SUS316 SUS316 SUS316 SUS316 SUS316 ADC12 SUS316L SUS316L SUS316L SUS316L SUS316L ADC12 Description Class 1 Class 2 Class 3 Class 4 /uni25A0 Table 4
- AM71□□/SL (Flow direction : Bottom—Top) AM71□□/LB/SL (Flow direction : Bottom—Top, Long body design) For liquid and slurry Rangeability 10:2 *1 Float rod comes out 70mm during operation in meter size 20mm ~ 150mm. The straight length of downstream pipe with the same size as the flowmeter must be more than 70 mm for a free movement of the float rod. In case of AM71□□/LB/SL (Bottom-Top, Long body design) this coming out is avoided by extending the tube length. The extension length of body (L dimension) is 130mm for 10K (150lbs) version. Consult factory for length of 20K (300lbs) version. (70)L (B)
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 16 TOKYO KEISO CO., LTD. 100 125 150 8.5 9.1 6.0 5.0 8.0 6.5 12.7 13.6 16.0 21.0 650 650 650 670 680 780 820 840 860 970 250 250 250 250 250 350 350 350 370 480 100 100 100 100 100 150 150 150 250 250 650 660 670 680 720 810 840 880 250 250 250 250 250 350 350 350 100 100 100 100 100 150 180 180 ( 1.6) ( 3.6) ( 5.9) (12.4) (25.0) (34.3) (55.0) ( — ) ( — ) 1.6 4.19 7.73 15.1 29.3 40.8 70.8 110 150 0.1~0.69 (0.69) Meter size Q water (m3/h) Pressure loss (kPa) (H) (mm) L (mm) A (mm) Mass (approx.) (H) (mm) L (mm) A (mm) Mass (approx.) 10K, Class 150 20K, Class 300 "H" dimension will be extended by 130mm if a cooling /f_in is provided. /uni25A0 Table 7 Figures in ( ) are those of 20K class. No
Description
Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 8
- AM72□□ (Flow direction : Bottom—Top side) For liquid A L (H)
- AM72□□/SL (Flow direction : Bottom—Top side) For liquid and slurry Meter size 0.1~0.75 1.7 4.2 7.5 29.5 110 150 250 250 250 250 250 350 350 350 370 480 100 100 100 100 100 150 150 150 250 250 100 125 150 (m3/h) L (mm) A (mm) 770 790 790 840 860 940 990 1010 1030 1140 (H) (mm) Mass (approx.) Figure Flow rate Size /uni25A0 Table 9 No Tapered tube Float ass'y Body Flange Chamber Lead pipe Case Bolt & nuts Gasket Description Class 1 SUS304 SUS304 SGP STPG370 SS400 SS400/SGP SUS304 ADC12 SS400 SUS304 Non-asbestos PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 SS400 SUS304 Non-asbestos PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SUS316 SUS316 ADC12 SS400 SUS304 Non-asbestos PTFE /uni25A0 Table 10 Meter size 2.92~23.1 53.3 123.7 187.8 447.1 787.4 1088 1769 14.0 11.0 14.0 9.0 12.0 12.0 12.0 11.0 690 690 690 690 700 800 820 860 250 250 250 250 250 350 350 350 100 [m3/h (nor)] (H) L 100 100 100 100 100 150 150 150 A JIS 10K Q air Pressure loss (kPa) Size (mm) Mass (approx.) /uni25A0 Table 11 No
Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 12
- AM72□□DU (Flow direction : Bottom—Top side, with gas damper) For gas A L (H)
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 17 Meter size 0.1~0.69 (0.69) 1.6 (1.6) 4.19 (3.6) 7.73 (5.9) 15.1 (12.4) 29.3 (25.0) 40.8 (34.3) 70.8 (55.0) 110 ( — ) 150 ( — ) 8.5 9.1 6.0 5.0 8.0 6.5 12.7 13.6 16.0 21.0 690 690 690 720 740 860 910 940 980 1110 250 250 250 250 250 350 350 350 370 480 100 100 100 100 100 150 150 150 250 250 100 125 150 (H) (mm) (mm) 100 120 140 (mm) A (mm) Mass (approx.) 690 700 720 740 790 900 950 1000 250 250 250 250 250 350 350 350 100 100 100 100 100 150 180 180 (H) (mm) (mm) 110 120 (mm) A (mm) Mass (approx.) Q water (m3/h) Pressure loss (kPa) 10K, Class 150 20K, Class 300 /uni25A0 Table 15 Figures in ( ) are those of 20K class. "H" dimension will be extended by 130mm if a cooling /f_in is provided. No Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 16 Meter size 2.92~23.1 53.3 123.7 187.8 447.1 787.4 1088 1769 17.0 14.0 18.0 12.0 17.0 17.0 17.0 16.0 730 730 730 730 760 880 910 960 250 250 250 250 250 350 350 350 100 (H) L1 100 (L2) 100 100 100 100 100 150 150 150 A JIS 10K Q air [m3/h(nor)] Pressure loss (kPa) Size (mm) Mass (approx.) /uni25A0 Table 17 No Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 18
- AM73□□ (Flow direction : Bottom side—Top side) For liquid 2 A L1(L2) (H) 2 A L1(L2) (H)
- AM73□□/DU (Flow direction : Bottom side—Top side, with gas damper) For gas Meter size 2.92~17.1 39.3 77.7 129.9 254.7 440.8 630.6 1233.8 2.8 4.0 2.7 2.9 3.4 2.6 4.0 5.5 690 690 690 690 700 800 820 860 250 250 250 250 250 350 350 350 100 [m3/h (nor)] (H) L 100 100 100 100 100 150 150 150 A JIS 10K Q air Pressure loss (kPa) Size (mm) Mass (approx.) /uni25A0 Table 13 No
Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 14
- AM72□□DU (Flow direction : Bottom—Top side, with low pressure loss gas damper) For gas A L (H)
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 18 TOKYO KEISO CO., LTD. (H1)(H2) L Meter size 0.1~0.6 1.4 3.1 6.1 155 11.0 12.0 10.0 15.0 11.5 10.0 16.0 18.0 20.0 25.0 440 470 480 510 540 570 610 650 670 720 110 130 110 100 125 150 (H1) (mm) (H2) (mm) 160 160 180 240 260 340 360 360 440 440 L (mm) Mass (approx.) 440 500 500 520 550 580 620 660 100 120 120 120 100 100 110 130 (H1) (mm) (H2) (mm) 160 160 180 240 260 340 360 360 L (mm) Mass (approx.) Q water (m3/h) Pressure loss (kPa) 10K, Class 150 20K, Class 300 /uni25A0 Table 23 "H1" dimension will be extended by 130mm if a cooling /f_in is provided. No Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 24 (Flow direction : Left—Right, Right—Left) For liquid Meter size Q water (m3/h) Q air [m3/h(nor)] 0.1~0.69 (0.69) 1.6 (1.6) 4.19 (3.6) 7.73 (5.9) 15.1 (12.4) 29.3 (25.0) 40.8 (34.3) 70.8 (55.0) 110 (— ) 150 (— ) 3.1~21.3 (21.3) 53 (53) 129.4 (124) 238 (206) 466 (431) 904 (831) 1260 (1160) 2186 (1934) 3300 (—) 4500 (—) 10.0 12.2 17.7 11.0 15.8 19.5 18.0 19.5 22.0 27.0 800 810 830 860 960 1080 1130 1160 1220 1330 220 220 220 220 220 350 350 350 370 480 100 100 100 100 100 150 150 150 250 250 100 125 150 (H) (mm) (mm) 190 190 210 220 310 300 310 320 360 360 (mm) A (mm) Mass (approx.) 830 850 880 930 1050 1180 1220 1280 220 220 220 220 220 350 350 350 100 100 100 100 100 150 180 180 (H) (mm) (mm) 210 220 240 280 370 370 380 400 (mm) A (mm) Mass (approx.) Pressure loss (kPa) 10K, Class 150 20K, Class 300 /uni25A0 Table 21 Figures in ( ) are those of 20K class. "H" dimension will be extended by 130mm if a cooling /f_in is provided. No Tapered tube Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Damper Description Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE SUS304 Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE SUS304 Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE SUS316 Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE SUS316L /uni25A0 Table 22 /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request.
- AM73□□/DL (Flow direction : Bottom side—Top side, with liquid damper) For gas and steam A L1(L2) (H)
- AM73□□/DU (Flow direction : Bottom side—Top side, with low pressure loss gas damper) For gas A L1(L2) (H) Meter size 2.92~17.1 39.3 77.7 129.9 254.7 440.8 630.6 1233.8 2.8 4.0 2.7 2.9 3.4 2.6 4.0 5.5 100 [m3/h (nor)] Q air Pressure loss (kPa) /uni25A0 Table 19 730 730 730 730 760 880 910 960 250 250 250 250 250 350 350 350 (H) L1 100 (L2) 100 100 100 100 100 150 150 150 A JIS 10K Size (mm) Mass (approx.) No
Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 20
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 19 (Flow direction : Bottom—Top, with jacket) For liquid Meter size 0.1~0.7 1.5 3.8 7.15 15.1 26.5 39.5 67.5 110 150 6.5 6.0 7.3 9.0 6.3 7.8 9.1 12.0 14.0 18.0 350 400 400 400 450 500 500 500 500 500 101 108 118 125 131 150 163 176 350 400 400 400 450 500 500 500 101 108 118 125 131 150 100 125 150 L (mm) (B) (mm) Mass (approx.) L (mm) (B) (mm) Mass (approx.) Q water (m3/h) Pressure loss (kPa) 10K. Class 150 20K. Class 300 /uni25A0 Table 27 *1 Float rod comes out by 70mm during operation in meter sizes 20mm ~ 150mm. The straight length of downstream pipe with the same size as the flowmeter must be more than 70 mm for a free movement of the float rod. L (70) L (70)6 (B) (B) No Tapered tube Float ass'y Body Jacket pipe Flange Float guide Indicator Description Class 1 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 Class 2 SUS304 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 Class 3 SUS316 SUS316 SUS316 SUS304 SUS316 SUS316 ADC12 Class 4 SUS316L SUS316L SUS316L SUS304 SUS316L SUS316L ADC12 /uni25A0 Table 28
- AM71□□/JS/SL, AM71□□/JF/SL (Flow direction : Bottom—Top, with jacket) For liquid and slurry Meter size 0.1~0.7 1.5 3.6 6.8 13.5 26.5 37.5 100 140 6.5 6.0 7.3 9.0 6.3 7.8 9.1 12.0 14.0 18.0 350 400 400 400 450 500 500 500 500 500 101 108 118 125 131 150 163 176 350 400 400 400 450 500 500 500 101 108 118 125 131 150 100 125 150 L (mm) (B) (mm) Mass (approx.) L (mm) (B) (mm) Mass (approx.) Q water (m3/h) Pressure loss (kPa) 10K. Class 150 20K. Class 300 /uni25A0 Table 29 *1 Float rod comes out by 70mm during operation in meter sizes 20mm ~ 150mm. The straight length of downstream pipe with the same size as the /f_lowmeter must be more than 70 mm for a free movement of the /f_loat rod. L (70) L (70)6 (B) (B) No Tapered tube Float ass'y Body Jacket pipe Flange Float guide Indicator Description Class 1 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 Class 2 SUS304 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 Class 3 SUS316 SUS316 SUS316 SUS304 SUS316 SUS316 ADC12 Class 4 SUS316L SUS316L SUS316L SUS304 SUS316L SUS316L ADC12 /uni25A0 Table 30 0.1~0.7 1.6 3.5 6.5 155 3.1~18 100 200 400 750 1100 1800 2800 4800 Q water (m3/h) Q air [m3/h(nor)]Meter size 12.0 14.8 21.0 15.5 19.0 22.1 21.0 24.0 26.0 31.5 440 470 480 510 540 570 610 650 670 720 200 200 210 200 270 280 290 300 320 340 105 125 100 125 150 (H1) (mm) (H2) (mm) 160 160 180 240 260 340 360 360 440 440 L (mm) Mass (approx.) 440 500 500 520 550 580 620 660 210 210 230 240 290 320 330 340 (H1) (mm) (H2) (mm) 160 160 180 240 260 340 360 360 L (mm) Mass (approx.) Pressure loss (kPa) 10K, Class 150 20K, Class 300 /uni25A0 Table 25 "H1" dimension will be extended by 130mm if a cooling /f_in is provided. No
Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Damper Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE SUS304 Class 2 SUS304 SUS304 SUS304 SUS304 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE SUS304 Class 3 SUS316 SUS316 SUS316 SUS316 SS400 SUS316 ADC12 SS400 Non-asbestos /PTFE SUS316 Class 4 SUS316L SUS316L SUS316L SUS316L SS400 SUS316L ADC12 SS400 Non-asbestos /PTFE SUS316L /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. /uni25A0 Table 26 (Flow direction : Left—Right, Right—Left, with liquid damper) For gas and steam L (H1)(H2)
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 20 TOKYO KEISO CO., LTD. L (H) A A 3 3 L (H) (Flow direction : Bottom—Top side, with jacket) For liquid L (B) [RUBBER AND ETFE LINED MATERIAL]
- AM71□□ (Flow direction : Bottom—Top) For liquid Meter size 0.1~0.69 1.6 3.6 5.9 12.4 25.0 34.3 55.0 110.0 150.0 8.5 9.1 6.0 5.0 8.0 6.5 12.7 13.6 16.0 21.0 660 680 670 680 710 820 850 900 940 1050 250 250 250 250 250 350 350 350 370 480 100 125 150 (H) (mm) L (mm) 100 100 100 130 130 150 180 180 250 250 A (mm) Mass (approx.) 660 680 670 690 750 850 870 940 250 250 250 250 250 350 350 350 (H) (mm) L (mm) 100 100 100 130 130 150 180 180 A (mm) Mass (approx.) Q water (m3/h) Pressure loss (kPa) 10K. Class 150 20K. Class 300 /uni25A0 Table 31 Only General purpose 150 lbs (10K) class is available for full jacketed version. (AM7/uni25A1/uni25A1/uni25A1/JF) No Tapered tube Float ass'y Body Flange Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Upper jacket pipe Jacket pipe Description Class 1 SUS304 SUS304 SGP /uni273D SS400 SS400 SUS304 ADC12 SS400 Non-asbestos /PTFE SUS304 Class 2 SUS304 SUS304 SUS304 SUS304 SUS304 SUS304 ADC12 SS400 Non-asbestos /PTFE SUS304 SGP or STPG370 (Depending on jacket medium press.) Class 3 SUS316 SUS316 SUS316 SUS316 SUS316 SUS316 ADC12 SS400 Non-asbestos /PTFE SUS304 Class 4 SUS316L SUS316L SUS316L SUS316L SUS316L SUS316L ADC12 SS400 Non-asbestos /PTFE SUS304 /uni25A0 Table 32 /uni273DSTPG370 for Medium press. 300 lbs (20K) class. Other special metallic material available on request. Meter size 0.1~0.65 1.2 2.8 6.5 11.5 17.0 34.0 60.0 90.0 140.0 5.0 6.0 6.0 9.0 6.0 8.0 9.0 11.0 13.0 17.0 550 550 550 600 650 700 750 750 750 800 104 110 118 125 137 150 163 100 125 150 L (B) Mass (approx.) JIS10K Q water (m3/h) Pressure loss (kPa) /uni25A0 Table 33 Size (mm) Tapered tube Float ass'y Upper body Lower body Float guide (L) Float guide (U) Bolts & nuts Gasket Indicator /uni273D1 Float rod material is ETFE lined SUS304 for meter size 15 and 20mm. /uni273D2 Float rod material is ETFE lined SUS304 for meter size 15, 20, 25 and 40mm. F .C.R. means Fluorocarbon Resin.Other metallic material on request No Description Class 1 Rubber lined PVC /uni273D1 Rubber lined Rubber lined PVC PVC SS400 EPDM ADC12 Class 2 Rubber lined F .C.R. /uni273D2 Rubber lined Rubber lined PVDF PVDF SS400 EPDM ADC12 /uni25A0 Table 34 Other metallic material on request No Tapered tube Float ass'y Upper body Lower body Float guide (L) Float guide (U) Bolts & nuts Gasket Indicator
/uni25A0 Table 35 Class 3 F .C.R. lined F .C.R. lined /uni273D2 F .C.R. lined F .C.R. lined PVDF PVDF SS400 PTFE ADC12
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 21 A (H) L L (B) A (H) L
- AM72□□ (Flow direction : Bottom—Top side) For liquid [PVC LINED MATERIAL] (Flow direction : Bottom—Top) For liquid
- AM72□□ (Flow direction : Bottom—Top side) For liquid A slurry type is available. For details, contact us. Meter size 0.8~2.7 4.8 11.4 20.2 33.0 54.0 88.0 88.0 140.0 5.5 4.3 7.0 5.4 10.0 10.0 14.0 14.0 20.0 Not available Not available 700 730 780 810 870 1000 1020 1140 1150 320 350 380 400 440 500 500 550 600 125 135 100 125 125 150 (H) L 120 130 130 150 150 200 200 220 220 A Mass (approx.)Q water (m3/h) Pressure loss (kPa) /uni25A0 Table 36 /uni273D1 Class 1, 2 /uni273D2 Class 3 /uni273D1 /uni273D2 Size (mm) JIS10K Tapered tube Float ass'y Upper body Lower body Float guide Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket /uni273D Float rod material is ETFE lined SUS304 for meter size 15, 20 and 25mm. F .C.R. means Fluorocarbon Resin.Other metallic material on request No Description Class 1 Rubber lined PVC /uni273D Rubber lined Rubber lined PVC SS400 PVC ADC12 SS400 EPDM Class 2 Rubber lined F .C.R. /uni273D Rubber lined Rubber lined PVDF SS400 PFA tubed SUS304 ADC12 SS400 EPDM /uni25A0 Table 37 Other metallic material on request No Tapered tube Float ass'y Upper body Lower body Float guide Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket
/uni25A0 Table 38 Class 3 F .C.R. lined F .C.R. lined /uni273D F .C.R. lined F .C.R. lined PVDF SS400 PFA tubed SUS304 ADC12 SS400 PTFE Meter size 0.1~0.65 1.1 2.1 2.7 6.5 5.0 5.0 5.5 8.0 5.5 7.0 8.0 10.0 12.0 16.0 101 104 110 118 131 137 150 163 130 100 125 150 (B) 550 700 750 800 850 900 900 950 950 1000 L Mass (approx.)Q water (m3/h) Pressure loss (kPa) /uni25A0 Table 39 Size (mm) JIS10K No Tapered tube Float ass'y Upper body Lower body Float receiver Float guide Bolts & nuts Gasket Indicator Description Material PVC lined PVC /uni273D PVC lined PVC lined PVC PVC SS400 EPDM ADC12 /uni25A0 Table 40 /uni273D Float rod material is ETFE lined SUS304 for meter size 15 and 20mm. Meter size 0.6~1.9 2.6 5.8 29.5 5.0 3.8 6.0 4.8 8.5 8.5 12.0 17.0 850 830 830 850 850 850 930 930 930 980 980 980 1010 1010 1010 1050 1050 1050 1100 1100 1100 1140 1150 1150 420 400 400 420 420 420 480 480 480 520 520 520 530 530 530 553 553 553 600 600 600 641 650 650 100 125 150 (H) Not available Not available 100 100 125 100 125 150 125 150 200 Conn size L 103 110 128 135 141 135 141 190 167 210 220 A Mass (approx.)Q water (m3/h) Pressure loss (kPa) /uni25A0 Table 41 Size (mm) JIS10K No Tapered tube Float ass'y Upper body Lower body Float guide Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Description Material PVC lined PVC PVC lined PVC lined PVC SS400 PVC ADC12 SS400 EPDM /uni25A0 Table 42
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 22 TOKYO KEISO CO., LTD.
- AM72□□ (Flow direction : Bottom—Top side) For liquid [GLASS LINED MATERIAL]
- AM71□□ (Flow direction : Bottom—Top) For liquid L (B) A (H) L Meter size Not available Not available Not available Not available 0.1~0.4 0.8 1.3 1.7 3.2 6.5 6.0 8.0 6.0 6.0 6.0 6.0 9.0 9.0 100 125 150 100 100 150 570 552 768 710 806 781 688 840 875 803 867 750 903 790 943 835 987 870 1024 L Conn size 104 104 110 125 137 (B) Mass (approx.)Q water (m3/h) F .C.R. Float Pressure loss (kPa) 0.1~0.6 1.0 1.6 2.5 4.5 10.0 10.0 8.0 8.0 8.0 8.0 10.5 11.5 Q water (m3/h) UNS10276 Float Pressure loss (kPa) /uni25A0 Table 43 Size (mm) JIS10K No Tapered tube Float ass'y Upper body Lower body Float receiver Float guide Bolts & nuts Gasket Indicator Description Class 1 Glass lined F .C.R. /uni273D Glass lined Glass lined PVDF PVDF SS400 PTFE ADC12 Class 2 Glass lined UNS10276 Glass lined Glass lined UNS10276 UNS10276 SS400 PTFE ADC12 /uni25A0 Table 44 /uni273DFloat rod material is ETFE lined SUS304 for meter size 15, 20, 25 and 40mm. F .C.R. means Fluorocarbon Resin. Meter size Not available Not available Not available Not available Not available 0.3~0.79 1.3 2.1 2.8 7.8 8.0 6.0 7.0 6.0 7.0 9.0 9.0 190 203 102 126 143 173 100 125 150 100 100 150 740 850 760 780 890 800 830 920 820 840 920 820 900 980 910 980 1050 980 1210 1280 1220 (H) Conn size 362 470 380 378 486 398 422 512 418 418 508 414 450 544 474 526 596 526 580 650 590 L A Mass (approx.)Q water (m3/h) F .C.R. Float Pressure loss (kPa) 0.4~1.0 1.6 2.7 3.6 10.0 8.0 9.0 8.0 8.5 10.5 11.5 Q water (m3/h) UNS10276 Float Pressure loss (kPa) /uni25A0 Table 45 Size (mm) JIS10K No Tapered tube Float ass'y Upper body Lower body Float buide Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Description Class 1 Glass lined F .C.R. /uni273D Glass lined Glass lined PVDF SS400 ADC12 SS400 PTFE Class 2 Glass lined UNS10276 Glass lined Glass lined UNS10276 SS400 ADC12 SS400 PTFE /uni25A0 Table 46 /uni273DFloat rod material is ETFE lined SUS304 for meter size 15, 20 and 25mm. F .C.R. means Fluorocarbon Resin. PFA tubed SUS304
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 23
- AM73□□/DL (Flow direction : Bottom side—Top side, with liquid damper) For gas (L2) (H) Meter size Not available Not available Not available Not available Not available 10~26 240 510 1140 9.0 7.0 7.5 6.5 8.0 10.0 12.0 190 203 102 126 143 173 100 125 150 100 100 150 1010 1050 1110 1120 1190 1300 1560 (H) Conn size 280 280 300 300 310 330 350 (L2) 348 365 406 404 446 521 592 L1 A1 190 190 203 203 102 234 126 259 143 285 100 Mass (approx.)Q air [m3/h(nor)] Q air [m3/h(nor)] F .C.R. Float Pressure loss (kPa) Pressure loss (kPa) 12~33 115 300 650 1460 11.0 9.5 10.0 9.0 9.0 11.5 14.0 UNS10276 Float /uni25A0 Table 47 Size (mm) JIS10K No Tapered tube Float ass'y Body Float buide Upper /f_lange Lead pipe Indicator Bolts & nuts Gasket Damper Blind /f_lange Description Class 1 Glass lined F .C.R. /uni273D Glass lined PVDF SS400 ADC12 SS400 PTFE Glass lined SS400/PTFE Class 2 Glass lined UNS10276 Glass lined UNS10276 SS400 ADC12 SS400 PTFE Glass lined SS400/PTFE /uni25A0 Table 48 /uni273DFloat rod material is ETFE lined SUS304 for meter size 15, 20 and 25mm. F .C.R. means Fluorocarbon Resin. PFA tubed SUS304
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 24 TOKYO KEISO CO., LTD. b. Viscosity limit In case the Viscosity of fluid is more than 1mPa·s, confirm the suitability shown in the fiigure below. Trace viscosity and flow rate and confirm the crossing point is below the curve. If the crossing point is above the curve, consult factory for detailed calculation by com puter.
- Viscosity curve Flow rate [L/h] Viscosity [mPa·s] c. Slurry application Consult factory if contaminations, sand, dirt and other solid particles are expected in fluid. AM7□□□/SL series slurry flowmeter is avail- able. 2. Gas application Generally, flowmeters with damper (Model AM71 □□/DU, AM72□□/DU, AM73□□/DU, AM73□□DL, AM76□□/DL, AM77□□/DL) are rec- ommended for gas application to prevent float vibration. Selection of meter size Maximum possible flow rate for each meter size is shown in dimension tables of AM71□□/DU, AM72□□/DU, AM73□□/DU, AM73□□/ DL, AM76□□/DL, and AM77□□/DL flowmeters. If actual fluid condition is different from such figures, a conversion calculation is to be performed by the following formula: QA : Converted /f_low rate in air 0°C, 1atm [m 3/h(nor)] : Density of gas to be measured [kg/m 3(nor)] p : Pressure of gas to be measured (MPa) t : Operating temperature (°C) Example Gas to be measured : Nitrogen (N2) Speci/f_ic weight ( ρ ) : 1.251kgf/m3(nor) Operating pressure ( p ) : 0.6MPa Operating temperature ( t ) : 20° C Flowmeter to be used : AM73/uni25A1/uni25A1/DU = 300×0.0169×22.86 ρ ρ SELECTION OF FLOWMETER 1. Liquid application a. Selection of meter size Maximum possible flow rate each meter size is shown in dimension tables from Page 15 to 22. These figures are based on water flow (Den- sity 1.0g/cm 3 and Viscosity 1.0MPa·s). If actual fluid condition is different from such figures, a conversion calculation is required as follow- ing formula: Qw : Water converted /f_low rate (m 3/h) Q : Flow rate of actual /f_luid (m 3/h) : Density of actual /f_luid (g/cm 3) Example Fluid: Alcohol Density: 0.8g/cm 3 Flow rate: 50m 3/h Flowmeter to be used: AM71/uni25A1/uni25A1 ρ ρ = 50×0.882 = 44.1(m 3/h) Referring to table 1 on Page 15, the required meter size is 100. For possible connection flange sizes, refer to Table 45. Referring to table 15 on Page 17, the suitable meter size is 25. For possible connection flange sizes, refer to Table 45.
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 TOKYO KEISO CO., LTD. 25 3. Steam application Flowmeters with liquid damper (type AM73 □□/DL, AM76□□/DL, AM77□□/DL) are recommended for steam application to prevent float vibration. Also a cooling fin is normally needed because of high temperature. Selection of meter size Steam flow rate is to be converted into water flow rate by the following formula for size determination. Qw = Qs×0.03× Qw : Water converted /f_low rate (m3/h) Qs : Steam /f_low rate (m 3/h) : Density of steam (kg/m 3) ρ ρ Example Fluid Saturated : Steam Pressure : 0.9MPa Flow rate : 1t/h Flowmeter to be used : AM76□□/DL First, density of the steam is to be obtained from “Steam graph” etc. In this application, density(ρ ) of 0.9MPa steam is 5.1kg/ m3. Saturated steam curve (by temperature) is shown in the fiigure below and saturated steam curve (by pressure) is shown in the fiigure below for reference. Normally, flow rate of steam is described in weight unit, which is to be converted to volume unit (Qs) as follows: 1t/h = 1000 kg/h Qs = 1000 kg/h / 5.1 kg/m 3 = 196 m 3/h Then, all these figures are to be put into the formula: Qw = 196×0.03× 5.1 = 196×0.0677 = 13.3 (m 3/h) Referring to Table 21 on Page 18, the suitable meter size is 65. For possible connection flange sizes, refer to Table 45.
- Density of saturated Steam(by temperature) ● Density of saturated Steam (by pressure) Steam temp. [°C] [kg/m3] Density Steam press. [MPa] [kg/m3] 5.1 Density 0.5 1.00.9 1.5 2
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 26 TOKYO KEISO CO., LTD. 5. Scale graduation Customer can select any one of the following 16 standard scale graduations if meter size and connection flange meet the specification. Range ability is 10 : 1 Example If required scale range is 150–1500 m3/h (nor), the graduation on the flowmeter will be 15–150×10 m3/h (nor) 1.2 1.6 2.5 3.5 4.5 7.5 1.5 4. Connection flanges Table 45 shows possible connection flange sizes against selected meter sizes. The table is applicable for flowmeters with Metallic materi - als, Rubber lining, ETFE lining. Only listed connection sizes in dimension tables are available for flowmeters with PVC lining and Glass lining. AM71/uni25A1/uni25A1 AM71/uni25A1/uni25A1/JS, JF AM72/uni25A1/uni25A1 AM72/uni25A1/uni25A1/JS, JF AM73/uni25A1/uni25A1 AM76/uni25A1/uni25A1 AM77/uni25A1/uni25A1 Bottom – Top Bottom – Top Bottom – Top side Bottom – Top side Bottom side – Top side Left – Right Right – Left Model Flow direction Against meter size –1 size ±0 size +1 size /uni25A0 Table 45 6. Special orders a. Low pressure drop version If standard pressure drop does not meet the requirement, “Low pressure drop version” is available on request. Consult factory for further details. b. Low temperature application If the fluid temperature is very low (i.e. liquefied gas etc.), Special arrangement to prevent frost is available. Consult factory for further detail. c. High pressure application Up to 196 MPa possible with experience. Consult factory for further details.
- Standard scale graduation
AM7000 Series METAL TUBE VARIABLE AREA FLOWMETER TG-F2026-E21 At least 20 cm At least 20 cm Local indication and alarm output type Electric transmitter and alarm output (Flameproof) type Local integration type For a meter size of 50 or less: at least 35 cm For a meter size of 65 or more: at least 45 cm For a meter size of 50 or less: at least 35 cm For a meter size of 65 or more: at least 45 cm For a meter size of 50 or less: at least 40 cm For a meter size of 65 or more: at least 50 cm At least 20 cm CAUTIONS
- This flowmeter transmits the displacement caused by the magnet coupling. A surrounding magnetic field might affect its performance.
- Avoid installation near magnetic fields. Magnetic materials including insulation covers may also affect its performance; do not bring them within 20 cm from the flowmeter.
- When installing two or more flowmeters, place them at least the distances shown in the figures below apart from each other to avoid mutual interference. For maintenance, ensure a clearance of at least 20 cm between the indicator of one flowmeter and the body of other flowmeters. Head Of/f_ice :Shiba Toho Building, 1 – 7 – 24 Shibakoen, Minato-ku, Tokyo 105 – 8558 Tel : +81-3 – 3431 – 1625 (KEY) ; Fax : +81-3 – 3433 – 4922 * Speci/f_ication is subject to change without notice.