EE210 EPLUSE | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 13

Technical content

Humidity and Temperature Sensor for Demanding Climate Control EE210

v2.12 / Modification rights reserved | 2 EE210 The EE210 humidity (RH) and temperature (T) sensor is designed to meet the highest requirements in demanding climate control applications. Besides the accurate measurement of RH and T EE210 calculates various RH related parameters such as dew point temperature, absolute humidity and mixing ratio. Outstanding Measurement Performance Excellent performance of EE210 in polluted or aggressive environment is ensured by the encapsulated measurement electronics inside the sensing probe and the long-term stable E+E sensing element with proprietary coating. Analogue, Digital Outputs and Display All measured and calculated values are available on the BACnet MS/TP or Modbus RTU interface, two of them on the analogue voltage or current outputs, while up to three values can be shown simultaneously on the optional display. Versatility EE210 is available for wall or duct mount, with remote probe, as well as an outdoor version. The IP65 / NEMA 4X enclosure minimizes installation costs and provides outstanding protection against contamination and condensation. Easy Configuration and Adjustment With an optional USB configuration adapter, the user can set the RS485 interface parameters, the output scaling and perform one or two point adjustment for RH and T. Humidity and Temperature Sensor for Demanding Climate Control EE210 duct mount (type T2) EE210 with remote probe (type T3) EE210 outdoor with radiation shield (type T13) EE210 wall mount (type T1)

v2.12 / Modification rights reserved | 3

Features

according DIN EN 10204-3.1 Enclosure ▪ Protection rating IP65 / NEMA 4X ▪ Type T13 compatible with radiation shield H010501 Display ▪ Selectable display layout ▪ Measurands freely selectable ▪ Backlight optional External mounting holes ▪ Mounting with closed cover ▪ Electronics protected against construction site pollution ▪ Easy and fast mounting Bayonet screws ▪ Open / close with a ¼ rotation Cast electronics ▪ Mechanical protection ▪ Condensation-resistant E+E RH and T Sensing Element ▪ Outstanding long-term stability ▪ Protected solder pads ▪ Tested according to automotive standard AEC-Q200 Watertight cable outlet Electronics on the underside of the PCB ▪ Optimum protection against mechanical damage during installation Smooth cover surface ▪ No accumulation of dust in protruding edges Knockout for ½" conduit fitting (US)

v2.12 / Modification rights reserved | 4 Values in mm (inch) Dimensions The E+E proprietary sensor coating is a protective layer applied to the active surface of the sensing element. The coating substantially extends sensor lifetime and ensures optimal measurement performance in corrosive environment (salts, off- shore applications). Additionally, it improves the sensors’ long term stability in dusty, dirty or oily applications by preventing stray impedance caused by deposits on the active sensor surface. Protective Sensor Coating Type T1 (wall mount) Type T2 (duct mount) FOR CONDUIT INSTALLATION CABLE GLAND M16x1.5 ~55 ~2.16 Ø 12 Ø 0.47 ±0.3 3.54 ±0.11 1.81 0.2 80.6 3.17 ±0.3 3.54 ±0.11 Ø > 13 Ø > 0.51 101 3.98 0.75 GASKET Length according to ordering guide L = filter cap length mm (inch) Membrane 34 (1.4) Stainless steel 33 (1.3) Metal grid 33 (1.3)

v2.12 / Modification rights reserved | 5 Type T3 (remote probe) PE210 ±0,3 FOR CONDUIT INSTALLATION 80.6 CABLE GLANDS M16x1.5 (3.54 ±0.11) (1.81) (3.17) (0.2) 106 4.17 Type T13 (outdoor) Mounting flange in the scope of supply for type T2 and T3 Radiation shield HA010501 for type T13 (outdoor) needs to be ordered separately 37.2 1.5 3.5 3.5 2.2 1.3 0.5 Ø > 16 Ø > 0.63 0.24 ±0.3 2.36 ±0.11 44 (1.73) Ø5 (Ø0.2) 20 (0.79) 20 (0.79) 1.5 (0.06) 122 (4.8) 44 (1.73) Ø105 (Ø4.13) 174 (6.85) 94 (3.7) Values in mm / inch Dimensions

v2.12 / Modification rights reserved | 6 Technical Data Measurands Relative humidity (RH) Measuring range 0...100 % RH Accuracy1) incl. hysteresis, non-linearity and repeatability Type T1, T2 Type T3 @ 20 °C (68 °F) Type T13 ±(1.3 + 0.003*measured value) %RH ±2.3 %RH ±(1.5 + 0.015*measured value) %RH ±2.5 %RH ±(1.6 + 0.005*measured value) %RH ±3 %RH ±(2.3 + 0.008*measured value) %RH 1) Traceable to international standards, administrated by NIST, PTB, BEV,... The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement). For Type T13: @ 24 V DC and RL=250 Ω for A6 Versions. Temperature (T) Measuring range Type T1, T2, T13 Type T3 (probe) Type T3 (enclosure) Accuracy Type T1,T2 Type T3 Type T13 ± ∆T [°C] T [°C] ± ∆T [°C] T [°C] ± ∆T [°C] T [°C]

v2.12 / Modification rights reserved | 7 Calculated measurands from up to unit Dew point temperature Td -40 (-40) 60 (140) °C (°F) Frost point temperature Tf -40 (-40) 0 (32) °C (°F) Wet bulb temperature Tw 0 (32) 60 (140) °C (°F) Water vapour partial pressure e 0 (0) 200 (3) mbar (psi) Mixing ratio r 0 (0) 160 (1200) g/kg (gr/lb) Absolute humidity dv 0 (0) 150 (60) g/m3 (gr/ft3) Specific enthalpy h -40 (-10) 500 (200) kJ/kg (BTU/lb) Technical Data Measurands Outputs Analogue Two freely selectable and scalable outputs 0 - 5 V / 0 - 10 V -1 mA < IL < 1 mA IL = load current 4 - 20 mA (2-wire) RL ≤ 500 Ω RL = load resistance 250 ≤ RL ≤ 500 Ω recommended for type T13 0 - 20 mA (3-wire) RL ≤ 500 Ω Digital Digital interface RS485 (EE210 = 1 unit load) Protocol Factory settings Supported Baud rates Data types for measured values Modbus RTU Baud rate according to ordering guide, parity even, 1 stop bit, Modbus address 242 9 600, 19 200 and 38 400 FLOAT32 and INT16 Protocol Factory settings Supported Baud rates BACnet MS/TP Baud rate according to ordering guide, parity none, 1 stop bit, BACnet address 1 9 600, 19 200, 38 400, 57 600, 76 800 and 115 200

v2.12 / Modification rights reserved | 8 Technical Data Power supply class III USA & Canada: Class 2 supply necessary, max. voltage 30 V DC 4 - 20 mA (2-wire) (10 V + RL * 20 mA) < V+ < 30 V DC for type T13: 24 V DC ±10 % recommended 0 - 5 V / 0 - 10 V 0 - 20 mA (3-wire) RS485 15 - 35 V DC or 24 V AC ±20% Current consumption at 24 V Voltage output DC supply max. 12 mA AC supply max. 34 mA rms with display max. 23 mA with display max. 49 mA rms Current output 2-wire DC supply max. 40 mA with display max. 40 mA Current output 3-wire DC supply typ. 33 mA AC supply typ. 65 mA rms with display max. 44 mA with display max. 84 mA rms Digital interface DC supply typ. 5 mA AC supply typ. 15 mA rms with display max. 20 mA with display max. 35 mA rms Electrical connection Screw terminals, max. 1,5 mm 2 Cable gland M16x1,5 Display1) Available for type T1 / T2 / T3 1, 2 or 3 lines, user configurable Optional with backlight Temperature ranges Without display With display for probe PE210 for probe PE210 Enclosure Material Protection rating PC (Polycarbonate), UL94 V-0 (with display UL94 HB) approved IP65 / NEMA 4X Electromagnetic compatibility EN 61326-1 EN 61326-2-3 Industrial environment FCC Part15 Class A ICES-003 Class A Conformity 1) For display operation with EE210-M1xA6 (4 - 20 mA, 2-wire) both outputs must be connected. General

v2.12 / Modification rights reserved | 9 Ordering Guide Feature Description Code Hardware Configuration EE210- Model RH + T M1 Type Wall mount T1 Duct mount T2 Remote probe 1) T3 Outdoor T13 Probe length 50 mm (1.97”) L50 200 mm (7.84ʺ) L200 Output 0 - 5 V A2 0- 10 V A3 A3 0 - 20 mA (3-wire) A5 4 - 20 mA (2-wire) A6 A6 RS485 J3 Filter Membrane F2 Metal grid F3 F3 Stainless steel sintered F4 Display2) Without display No code Without backlight 3) D1 With backlight 4) D2 Setup Analogue Outputs Output 1 measurand Relative humidity RH [%] No code Temperature T [°C] MA1 Temperature T [°F] MA2 Other measurands (xx see measurand code) MAxx Output 1 scaling low 0 No code Value SALValue Output 1 scaling high 100 No code Value SAHValue Output 2 measurand Temperature T [°C] No code Temperature T [°F] MB2 Other measurands (xx see measurand code) MBxx Output 2 scaling low Value SBLValue Output 2 scaling high Value SBHValue Setup RS485 Protocol Modbus RTU5) P1 BACnet MS/TP 6) P3 Baud rate 9 600 BD5 19 200 BD6 38 400 BD7 57 6007) BD8 76 8007) BD9 115 2007) BD10 Units Metric (SI) No code Non metric (US/GB) U2 1) The PE210 probe has to be ordered as seperate position. 2) Factory setup: For analogue output versions the display shows the measurands selected for output 1 and output 2. For digital output versions the display shows RH and T. 3) Not with output A5. 4) Not with output A6. 5) Modbus Map and setup instructions: See User Guide and Modbus Application Note at www.epluse.com/ee21 0. 6) Product Implementation Conformance Statement (PICS) available at www.epluse.com/ee21 0. 7) Only for BACnet MS/TP. Feature Description Code HW-Configuration PE210- Model RH + T M1 Filter Membrane F2 Metal grid F3 Stainless steel sintered F4 Connection cable length 1.5 m (4.9 ft) KL150 3 m (9.8 ft) KL300

v2.12 / Modification rights reserved | 10 Measurand Code For Output 1 and 2 in the Ordering Guide Measurand Unit Code MAxx / MBxx Relative humidity % 10 Temperature °C Dew point Td °C Frost point Tf °C Mixing ratio r g/kg gr/lb Absolute humidity dv g/m³ gr/ft³ Wet bulb temperature Tw °C Water vapour partial pressure e mbar psi Specific enthalpy h kJ/kg BTU/lb Order Examples EE210-M1T1A3F2D2SBL-40SBH60 Feature Code Description Model M1 RH + T Type T1 Wall mount Output A3 0 - 10 V Filter F2 Membrane Display D2 With backlight Output 1 measurand No code Relative humidity RH [%] Output 1 scaling low No code 0 %RH Output 1 scaling high No code 100 %RH Output 2 measurand No code Temperature T [°C] Output 2 scaling low SBL-40 -40 °C Output 2 scaling high SBH60 60 °C Type T1 and T2 PLEASE NOTE No mix of SI/US units allowed.

v2.12 / Modification rights reserved | 11 Order Examples EE210-M1T3A6MB52SBL-10SBH50 Feature Code Description Model M1 RH + T Type T3 Remote probe Output A6 4-20 mA (2-wire) Display No code Without display Output 1 measurand No code Relative humidity RH [%] Output 1 scaling low No code 0 %RH Output 1 scaling high No code 100 %RH Output 2 measurand MB52 Dew Point Temperature Td [°C] Output 2 scaling low SBL-10 -10 °C Output 2 scaling high SBH50 50 °C Type T3 Position 1: Basic Device Position 2: Remote Probe PE210-M1F3KL150 Feature Code Description Model M1 RH + T Filter F3 Metal grid Connection cable length KL150 1,5 m (4.9 ft) EE210-M1T13A6F3SBL-40SBH60 Type T13 Position 1: Feature Code Description Model M1 RH + T Type T13 Outdoor Output A6 4 - 20 mA (2-wire) Filter F3 Metal grid Display No code Without display Output 1 measurand No code Relative humidity RH [%] Output 1 scaling low No code 0 %RH Output 1 scaling high No code 100 %RH Output 2 measurand No code Temperature T [°C] Output 2 scaling low SBL-40 -40 °C Output 2 scaling high SBH60 60 °C HA010501 Position 2: Radiation shield for EE210 Outdoor.

v2.12 / Modification rights reserved | 12 Accessories For further information see datasheet “Accessories” . Accessories Code USB configuration adapter HA011066 Product configuration software (Free download: www.epluse.com/configurator ) EE-PCS Radiation shield for EE210 Outdoor (Type T13) HA010501 Power supply adapter V03 Protection cap for Ø12 mm probe HA010783

Company Headquarters & Production Site E+E Elektronik Ges.m.b.H. Langwiesen 7

4209 Engerwitzdorf | Austria

info@epluse.com www.epluse.com Subsidiaries E+E Sensor Technology (Shanghai) Co., Ltd. T +86 21 6117 6129 info@epluse.cn E+E Elektronik France SARL T +33 4 74 72 35 82 info.fr@epluse.com E+E Elektronik Deutschland GmbH T +49 6171 69411-0 info.de@epluse.com E+E Elektronik India Private Limited T +91 990 440 5400 info.in@epluse.com E+E Elektronik Italia S.R.L. T +39 02 2707 86 36 info.it@epluse.com E+E Elektronik Korea Ltd. T +82 31 732 6050 info.kr@epluse.com E+E Elektronik Corporation T +1 847 490 0520 info.us@epluse.com Version v2.12 | 10-2023 Modification rights reserved