v1.3 / Modification rights reserved | 2 EE046 The EE046 condensation monitor helps to prevent condensation on critical cold spots. With the help of its relative humidity (RH) sensing element, it reliably detects the danger of condensation just before it occurs. Mounting Options The EE046 is available in two variants. The wall / pipe mount type is appropriate for installation on flat surfaces and on pipes with a maximum diameter of 50 mm (2”). It is mounted on cooling ceilings, on cooling or cold water piping, cooled surfaces and chilled beams. The snap-on type can be mounted on plastic and aluminium composite pipes with 16 mm or 20 mm diameter. It’s typical applications are cooling and heating by concrete core activation. Reliable Anti-Condensation Safe Guard Condensation on a surface occurs when the relative humidity of the air close to the surface reaches 100 %RH. Because of the very good thermal coupling with the surface, the EE046 measures the RH of the air directly at surface temperature. Its properties make it the ideal choice for applications where control guards are required to prevent dripping or mould. Early Detection of Condensation Risk The relay output provides an early warning before condensation actually happens. It also indicates a power supply failure or a broken cable. A status LED indicates normal operation, alarm or power supply failure.The E+E proprietary coating protects the humidity sensor against dust and dirt. EE046 wall / pipe mount EE046 snap-on mount Condensation Monitor
v1.3 / Modification rights reserved | 3 Mounting ▪ Compact design and easy mounting ▪ Versatile mounting options
Features
▪ For pipe diameter N16 and N20 Wall / pipe mount Enclosure ▪ IP40 protection rating ▪ Polycarbonate, UL94 V-2 approved Performance ▪ Wide RH / T working range ▪ Fast response time ▪ Sensing element protection ▪ Protected electronics board Output and connection ▪ Relay output for early warning ▪ Indication for power supply / cable failure ▪ 5 poles push-in spring terminal LED status indication
v1.3 / Modification rights reserved | 4 The E+E proprietary sensor coating is a protective layer applied to the active surface of the sensing element. The coating substantially extends sensor lifetime and ensures optimal measurement performance in corrosive environment (salts, off- shore applications). Additionally, it improves the sensors’ long term stability in dusty, dirty or oily applications by preventing stray impedance caused by deposits on the active sensor surface. Protective Sensor Coating Dimensions Values in mm (inch) Wall / Pipe mount Front view 33.5 (1.32) Status LED 43 (1.69) 53 (2.09) 23 (0.9) Ø4.5 (0.18) 63.5 (2.5) Wall mount Pipe mount Thermal conductive film 22 (0.87) Thermal conductive film max. Ø50 (2)
v1.3 / Modification rights reserved | 5 Dimensions Values in mm (inch) Snap-on mount Front view Side view Status LED 33.5 (1.32) 63.5 (2.5) 39.5 (1.56) N16: Ø16 (0.63) N20: Ø20 (0.79) N16: 9.5 (0.37) N20: 11.5 (0.45) Snap-on mount On Pipe Pipe N16: Ø 16 (0.63) N20: Ø 20 (0.79) Technical Data Measurands Relative Humidity (RH) Working range 10...100 %RH, non condensing Threshold @ 24 V AC/DC, 20 °C (68 °F) 90 ±3 %RH Hysteresis Hysteresis 5 %RH 85 ±3 %RH 90 ±3 %RH Response time t90, change of the relative humidity (RH) change of the surface temperature <25 s <3 min
v1.3 / Modification rights reserved | 6 Output Relay Changeover contact, potential free Switching capacity, max. 24 V AC/DC, 1 A Contact functions WET DRY Contact for RH > threshold, Power off (NC) Contact for RH < threshold, Power on (NO) Power supply class III USA & Canada: Class 2 supply necessary
24 V AC/DC ±20 %
Current consumption @ 24 V DC @ 24 V AC <6 mA <10 mArms Electrical connection 5 pole push-in terminal, max. 1.5 mm 2 (AWG 16) Protection Sensing Element Electronics E+E proprietary coating Varnish Relay status indication LED, red Temperature range Operation Storage Weight, typ. Wall / pipe mount version Snap-on mount version 60 g 80 g Enclosure Material Protection rating PC (Polycarbonate), UL94 V-2 approved IP40 Electromagnetic compatibility EN 61326-1 EN 61326-2-3 Industrial environment FCC Part15 Class A ICES-003 Class A Conformity General Technical Data Ordering Guide Feature Description Code Hardware EE046- Type Wall / pipe mount T11 Snap-on mount T25 Pipe diameter 16 mm (0.63”) N16 20 mm (0.79”) N20 Order Example EE046-T25N16 Feature Code Description Type T25 Snap-on mount Pipe diameter N16 16 mm (0.63")
Company Headquarters & Production Site E+E Elektronik Ges.m.b.H. Langwiesen 7
4209 Engerwitzdorf | Austria
info@epluse.com www.epluse.com Subsidiaries E+E Sensor Technology (Shanghai) Co., Ltd. T +86 21 6117 6129 info@epluse.cn E+E Elektronik France SARL T +33 4 74 72 35 82 info.fr@epluse.com E+E Elektronik Deutschland GmbH T +49 6171 69411-0 info.de@epluse.com E+E Elektronik India Private Limited T +91 990 440 5400 info.in@epluse.com E+E Elektronik Italia S.R.L. T +39 02 2707 86 36 info.it@epluse.com E+E Elektronik Korea Ltd. T +82 31 732 6050 info.kr@epluse.com E+E Elektronik Corporation T +1 847 490 0520 info.us@epluse.com datasheet_EE046 |Version v1.3 | 01-2024 Modification rights reserved