Features

◆ Universal battery controller module for uninterruptable 24 VDC and 48 VDC bus voltage ◆ Redundant inputs for two indepedant sources ◆ Battery protection for over voltage, deep discharge, short circuit and reverse connection ◆ Alarm outputs for input, output and battery condition ◆ Remote On/Off for battery ◆ Controlled end of charge voltage by temperature sensor ◆ International safety approval package ◆ 3-year product warranty * Maximum current at nominal Vout IEC 60950-1 EMC This module provides a professional battery management system to charge and monitor an external 12V lead-acid battery. Together with a power supply of the TSP series or any other stabilized 24 VDC or 48 VDC power supply a perfect DC- UPS system can be configured. The connected battery will be charged and held in charged mode by the power supply. In the event of a mains power failure the battery will supply the output power until the battery is discharged. A step up con- verter is used to maintain the selected output voltage level, Vnom - 6% (typical). To avoid overcharging the battery, an external temperature sensor adjusts the battery voltage automatically to the required end of charge voltage. This can extend the battery life. The battery is protected against deep discharge. Mains power and bat- tery status are monitored regularly and failures indicated by corresponding LED’s and alarm outputs. The module also provides an external On/Off input to switch-off both, power supply and battery. TSP-TS battery temperature sensor (10 kOhm NTC with 2m cable) optional Order code Inputs Input voltag range Output Current max.* Output Power max. Back up battery TSP-BCMU360 2 x 360 W, for any single or two identical 24 VDC or

48 VDC sources

24–28 or 48–56 VDC (range selection with jumper)

24 VDC / 15 A

48 VDC / 7.5A 360 W 12V lead acid battery (to purchase on local market) Models UL 60950-1 External Batteries: For external batteries we recommend: Datasheet: www.tracopower.com/products/tsp-panas_072.pdf

http://www.tracopower.com Page 2 of 8 All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. Battery Controller Module TSP-BCMU360 Series 360 Watt Output Specifications Output voltage / current – Normal Mode 24 VDC mode: Vin – (0.4 - 0.8V); 15 A max. 48 VDC mode: Vin – (0.4 - 0.7V); 7 .5 A max. – Buffer Mode 24 VDC mode: 22.2 – 22.9 VDC; 10 A (15 A in boost mode for 10min) 48 VDC mode: 44.6 – 45.3 VDC; 5 A (7 .5 A in boost mode for 3min) Efficiency – Normal mode 94 – 98 % (battery charged) (load >50 % of Iout max.) – Buffer mode 87 – 92 % General Specifications Operating temperature – Normal Mode –25°C to +70°C max. (without derating) – Buffer Mode nominal 24 VDC mode: derating above +50°C : 2.0 %/K 48 VDC mode: derating above +40°C : 2.0 %/K – Buffer Mode boost 24 VDC mode: up to +40°C for 10 minutes max. 48 VDC mode: up to +40°C for 3 minutes max. Storage temperature –25°C to +85°C max. Temperature coefficient 0.02 %/K Humidity (non condensing) 95 % rel. H max. Reliability, calculated MTBF at +25°C acc. to IEC 61709 > 1.5 Mio. h Battery protection against over voltage, deep discharge, overcharge, short circuit and reverse connection (built-in fuse) Signals – Status DC OK input, DC OK output, BAT OK all relay contact closed and LED on at status OK – Contact rating 30 VDC, 1.0 A max. / 60 VDC, 0.5 A max. Battery charging current 0.8 – 1.2 A Nominal battery voltage (at 25ºC) 13.6 VDC (factory setting) Battery voltage adjustment range 13.2 – 14.4 VDC Battery restistance test 100mOhm min. (normal mode at 25ºC) Battery test current 2.5A / 60ms typ. (normal mode at 25ºC) Battery test interval (acc. to jumper setting) 15s or 10min Battery warning 10.4 – 1 1.4 VDC (buffer mode only) Battery disconnection 9.1 – 9.7 VDC (buffer mode only) Battery remote Off disconnects battery in buffer mode (see page 6 - connector) Automatic battery temperature compensation range –15ºC – 50ºC Degree of protection IP 20 (IEC/EN 60529) Altitude during operation 2000 m Safety standard IEC/EN 60950-1, UL 60950-1 (2nd) + Am1:201 1 UL508 – requirements IEC/EN 61010-1, IEC/EN 61010-2-201 Safety approvals – CSA UL60950, UL508 – CB test certificate IEC 60950-1 (SIQ for EN) IEC/EN 61010-1, IEC/EN 61010-2-201 – Certification documents www.tracopower.com/overview/tsp-bcmu Electromagnetic compatibility in correspondence to connected unit (no internal switching device) Environment – Vibration acc. IEC 60068-2-6; 3 axis, sine sweep, 10 – 55 Hz, 1 g, 1 oct/min – Shock acc. IEC 60068-2-27 3 axis, 15 g half sine, 1 1 ms Enclosure material aluminium (chassis) / stainless steel (cover) Mounting – DIN-rail mounting for DIN-rails as per EN 50022-35x15/7 .5 (snap-on with self-locking spring) – Wall mounting (option) with wall mounting bracket - see page 7 Connection – Input Output battery screw terminal (plug included) – Signal & control detachable screw terminals (plugs included)

http://www.tracopower.com Page 3 of 8 Function Specification Function Diagram: 1. General Description The TSP-BCMU360 module extends any 24VDC or 48VDC power supply to a DC-USV (uninterruptable DC Power supply). This module is a standalone unit and is designed to function with the Traco TSP series; however it can be used in conjunction with any fully stabi- lized 24V or 48V DC power supply output. The set voltage is configured through the means of a jumper on the unit with two selecta- ble DC voltage levels, 24V or 48V. No other signals are required between the TSP-BCMU360 and the connected power supplies for correct operation of the module. In the event of power fail from the connected power supply, the energy required by the load will be supplied continuously and without interruption from an external 12V lead acid battery. The module also offers the unique feature of redundant inputs as well as the battery backup. Redundancy is achieved by two internal decoupling diodes which allow operation with two independent voltage sources in order to increase the reliability of the output even further. 2. Operation 2.1. Battery Backup for USV Operation The TSP-BCMU360 module extends any 24VDC or 48VDC power supply to a DC-USV (uninterruptable DC Power supply), this is achie- ved by the connecting a 12V lead-acid battery to the BATT_IN connector of the unit. During normal operation, the connected power supply provides energy to load with a voltage level of Vin –0.5V (typical, 0.5V loss due to internal decoupling diodes) as well as char- ging the connected battery. If the connected supply fails, the battery is then connected to the load (buffer mode), a step up converter is used to maintain the selected output voltage level, Vnom - 6% (typical). 2.2. Dual Inputs for Redundancy The module provides two inputs to connect two power supplies to facilitate a redundant system. If one of the two connected sources fails then the second supply will provide energy to load maintaining the desired operation of the unit. The unit is designed to function with the TRACO POWER TSP series, but due to its standalone nature it can be used with any type of fully stabilized 24V or 48V power supply. 2.3. Output Voltage Level and Efficiency The TSP-BCMU360 module functions with both 24VDC (15A) and 48VDC (7 .5A) supplies. The desired voltage is selectable by means of a jumper located on the side of the unit. It also offers very high efficiencies with up to 96% and 98% efficiency in normal mode for 24V and 48V modes respectively. In the buffer mode efficiencies are as high as 92% and 89% for 24V and 48V modes respectively. Battery Controller Module TSP-BCMU360 Series 360 Watt

Figure 1. The user can adjust the set end of battery charge voltage level by means of the “Battery Voltage Adjust” potentiometer. ler, therefore batteries with a capacity of 2.5Ah or less should not be used with this module.

3.1 Battery Protection

http://www.tracopower.com Page 6 of 8 All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. 5. Battery Remote On/Off The TSP-BCMU360 module provides a Battery Remote on/off input (2 pins on signal connector); if this input is short circuited (switch closed in Figure 5) the battery will be disconnected from the unit by means of an internal relay. A voltage of 1V or less across the Bat- tery Remote on/off terminals will disconnect the battery from the unit. If the Battery Remote On/Off signal is set to off (short between pins) this will not affect the output of the unit in normal mode, however the battery will be disconnected, hence it will not charge. If the unit enters buffer mode while the Battery Remote On/Off signal is off, the battery will remain disconnected, hence no energy will be supplied to the load. An overview of the Battery Remote on/off input is given in the table below. Battery State Battery Remote On/Off Pins Voltage Connected Open Circuit 5V Disconnected Short Circuit <1V 6. Signals The TSP-BCMU360 module provides three signals to the user as an indication of the status of the unit; these signals are made available as LED indicators and corresponding isolated relay contacts and are as follows. Note: All Signal Relay contacts are rated for 30VDC/1A, 60VDC/0.5A  DC-IN-OK: The DC-IN-OK LED will illuminate and relay will close if at least one of the inputs is present and has a voltage within +20 / –3% tolerance.  BATT-OK: The BATT-OK LED will illuminate and relay will close if the battery is charged and has a low internal resistance. During battery discharge operation this signal monitors the output voltage and will switch off the LED and open the relay when the battery approaches the disconnection voltage.  DC-OUT-OK: The DC-OUT-OK LED will illuminate and relay will close if the output voltage of the unit is higher than 85–90% of the nominal output voltage. Figure 5 – Simplified Battery Remote On/Off Circuitry Function Specification (continued) Battery Controller Module TSP-BCMU360 Series 360 Watt

http://www.tracopower.com Page 7 of 8 Battery Controller Module TSP-BCMU360 Series 360 Watt Outline Dimensions Connector Position A: Battery test period 10 min (not fitted, default); 15 sec (fitted) B: Output voltage settings 48 V (not fitted); 24 V (fitted, default) C: Not in use (spare jumper fitted) Remote On/Off Recommended switch specifications for operation with a switch: 5V / 5mA For direct pulldown operation, the voltage level has to be <1.0V DC IN OK Bat. OK DC OUT OK Temp. Sensor (TS) Remote On/Off BATTERY VOLTAGE ADJUST DC-OUT-OK BATT-OK DC-IN-OK FUSE 10.2 11.6 10.2 11.7 61.8 69.9 75.5 81.1 110 ± 1 110 ± 1 113 ± 1* 54 ± 1 8.5 8.5 DIN-Rail Hook * Measurment from front panel to DIN Rail 6.4 Signal Connector 3.6 11.9 19.3 11.7 M2 Combi Head (QTY: 10) Combi Head (QTY: 8) IN-2IN-2 IN-1IN-1 OUTPUTBATT-IN DC-IN-OK 24 V/15 A

48 V/7,5 A

24 V/15 A

13,8V/30A F40A Battery Voltage Adjust MODEL 10.7 10.9 8.1 36.4 Jumper: Battery Test Period/ Output Voltage Select Detail A 13.5 3.8 DC-IN OK Bat OK DC OK Battery Remote ON/OFF Temp. Sensor Weight: 730 g

Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com www .tracopower.com Rev. November 23, 2021 Ordercode of Kit For Models Content of Kit TSP-WMK03 TSP-BCMU360 1 bracket TSP–WMK Wall Mounting Bracket 15.0 (0.59) 7.0 (0.28) 15.0 (0.59) Material: 2 mm Mild Steel Tolerance: ±0.1mm (± 0.004) 55.0 (2.16) Dimensions: [mm] ( ) = Inch 46.0 (1.81) 33.0 (1.30) 25 (0.98) 50.0 (1.97) 2x ø4.3 (0.17) 4 x positioning holes 2.0 (0.08) Material: 2 mm Mild Steel Tolerance: ±0.1mm (± 0.004) 62.5 (2.46) 96.0 (3.78) 62.5 (2.46) 173.0 (6.81) TSP 360 TSP 600 2.0 (0.08) 30.0 (1.18) 15.0 (0.59) ø 4.3 (0.17) 7.0 (0.28) ø 4.25 (0.17) 2.0 (0.08) 2.0 (0.08) R 2.12 (0.083) R 2.12 (0.083) 85.0 (3.35) 42.5 (1.67) 74.0 (2.91) 37.0 (1.45) 4 x positioning holes TSP-WMK03 Battery Controller Module TSP-BCMU360 Series 360 Watt