TPI300-M TRACOPOWER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 6

Technical content

AC/DC Power Supply TPI 300-M Series, 300 Watt

  • High power-density: 300 Watt in 4.6”x2.44” package (encased)
  • I/O isolation 3000 VAC rated for 250 VAC working voltage
  • Certification according to IEC/EN/UL 62368-1
  • Peak power operation up to 360 Watt for 5s
  • Operating temperature –40°C to 80°C
  • Active power factor correction >0.9
  • Operating up to 5000m altitude
  • High efficiency up to 93%
  • Protection class II prepared
  • 3-year product warranty IEC 62368-1UL 62368-1 The TPI 300-M series is a set of AC/DC power supplies in an encased package style. They feature a reinforced double I/O isolation (3000 VAC) system accord- ing to latest industrial safety standards. The excellent efficiency of up to 93% allows a high power-density and compact design (4.6” x 2.44”). The operating temperature range is –40°C to +80°C with derating above 50°C. In natural convection operation these power supplies deliver 180 Watt going up to 300 Watt with forced air cooling. Additionally, they can deliver 360 Watt peak power for 5s. The EMC characteristic is dedicated for applications in industrial and medical fields. High reliability is provided by using high quality components and an excellent thermal management making the TPI 300-M an ideal solution for industrial and medical devices and for demanding safety and space critical ap- plications. Models Order Code Output Power Output Voltage Output Current Output Current Efficiency max. nom. (adjustable) max. peak typ. TPI 300-112-M 300 W 12 VDC (10.8 - 13.2 VDC) 25'000 mA 30'000 mA 91 % TPI 300-115-M 15 VDC (13.5 - 16.5 VDC) 20'000 mA 24'000 mA 92 % TPI 300-124-M 24 VDC (21.6 - 26.4 VDC) 12'500 mA 15'000 mA 93 % TPI 300-136-M 36 VDC (32.4 - 39.6 VDC) 8'330 mA 10'000 mA 93 % TPI 300-148-M 48 VDC (43.2 - 52.8 VDC) 6'250 mA 7'500 mA 93 % TPI 300-153-M 53 VDC (47.7 - 58.3 VDC) 5'670 mA 6'790 mA 93 % Options on demand (backorder with MOQ non stocking item) - Optional model with 18 VDC / 16'667 mA - Optional model with 28 VDC / 10'710 mA www.tracopower.com March 16, 2023 Page 1 / 6

Input Voltage - AC Range Operational Range: 85 - 264 VAC (Full Range) Rated Range: 100 - 240 VAC (Full Range) - DC Range Operational Range: 120 - 370 VDC (Designed for, no certification) Polarity: +DC: L / –DC: N Input Frequency Operational Range: 47 - 440 Hz Certified: 50/60 Hz Input Current - Full Load & Vin = 230 VAC 1'600 mA max. - Full Load & Vin = 115 VAC 3'900 mA max. Power Consumption - No load & Vin = 230 VAC 3'000 mW max. - No load & Vin = 115 VAC 3'000 mW max. Input Inrush Current - At 230 VAC 70 A max. - At 115 VAC 40 A max. Power Factor - At 230 VAC 0.9 min. (Active Power Factor Correction) - At 115 VAC 0.9 min. (Active Power Factor Correction) Input Protection T 5 A / 250 VAC (Internal Fuse in L & N) Recommended Input Fuse 5'000 mA (slow blow) (The need of an external fuse has to be assessed in the final application.) Input Specifications Output Voltage Adjustment ±10% (By trim potentiometer) Output power must not exceed rated power! Voltage Set Accuracy ±1% max. Regulation - Input Variation (Vmin - Vmax) 0.2% max. - Load Variation (0 - 100%) 0.5% max. Boost Power Output Current peak: See model table Peak power time: 5 s max. Peak power duty cycle: 20% max. Average operation power: 50% of full load Ripple and Noise (20 MHz Bandwidth) 12 VDC model: 150 mVp-p max. (w/ 1 µF X7R) 15 VDC model: 180 mVp-p max. (w/ 1 µF X7R) 18 VDC model: 210 mVp-p max. (w/ 1 µF X7R) 24 VDC model: 270 mVp-p max. (w/ 1 µF X7R) 28 VDC model: 310 mVp-p max. (w/ 1 µF X7R) 36 VDC model: 390 mVp-p max. (w/ 1 µF X7R) 48 VDC model: 510 mVp-p max. (w/ 1 µF X7R) 53 VDC model: 540 mVp-p max. (w/ 1 µF X7R) Capacitive Load 12 VDC model: 20'000 µF max. 15 VDC model: 12'000 µF max. 18 VDC model: 9'000 µF max. 24 VDC model: 2'400 µF max. 28 VDC model: 2'000 µF max. 36 VDC model: 1'000 µF max. 48 VDC model: 650 µF max. 53 VDC model: 470 µF max. Minimum Load Not required Temperature Coefficient ±0.02 %/K max. Hold-up Time - At 230 VAC 5 ms min. - At 115 VAC 5 ms min. Start-up Time - At 230 VAC 2'000 ms max. - At 115 VAC 2'000 ms max. Short Circuit Protection Continuous, Automatic recovery Output Current Limitation 135 - 165% of Iout max. 150% typ. of Iout max. Output Specifications TPI 300-M Series, 300 Watt All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. www.tracopower.com March 16, 2023 Page 2 / 6

Overvoltage Protection 115 - 135% of Vout nom. (Latch off) Transient Response - Response Deviation 3% typ. / 10% max. (50% to 75% Load Step) - Response Time 600 µs typ. (50% to 75% Load Step) Safety Standards - IT / Multimedia Equipment EN 62368-1 IEC 62368-1 UL 62368-1 - Certification Documents www.tracopower.com/overview/tpi300-m Protection Class Class I & II (Prepared): Reinforced Insulation Pollution Degree PD 2 Over Voltage Category OVC II Safety Specifications EMI Emissions - Conducted Emissions EN 55032 class B (internal filter) FCC Part 15 class B (internal filter) - Radiated Emissions EN 55032 class A (internal filter) FCC Part 15 class A (internal filter) - Harmonic Current Emissions EN 61000-3-2, class A - Voltage Fluctuations & Flicker EN 61000-3-3 EMS Immunity EN 55024 (IT Equipment) EN 55035 (Multimedia) EN 60601-1-2 edition 4 (Medical Devices) - Electrostatic Discharge Air: EN 61000-4-2, ±15 kV, perf. criteria A Contact: EN 61000-4-2, ±8 kV, perf. criteria A - RF Electromagnetic Field EN 61000-4-3, 20 V/m, perf. criteria A - EFT (Burst) / Surge EN 61000-4-4, ±2 kV, perf. criteria A L to L: EN 61000-4-5, ±1 kV, perf. criteria A L to PE: EN 61000-4-5, ±2 kV, perf. criteria A - Conducted RF Disturbances EN 61000-4-6, 20 Vrms, perf. criteria A - PF Magnetic Field Continuous: EN 61000-4-8, 30 A/m, perf. criteria A - Voltage Dips & Interruptions 230 VAC / 50 Hz: EN 61000-4-11 30%, 25 periods, perf. criteria A >95%, 0.5 periods, perf. criteria A >95%, 250 periods, perf. criteria B

115 VAC / 60 Hz: EN 61000-4-11

30%, 25 periods, perf. criteria A >95%, 0.5 periods, perf. criteria A >95%, 250 periods, perf. criteria B EMC Specifications Relative Humidity 95% max. (non condensing) Temperature Ranges - Operating Temperature –40°C to +80°C - Storage Temperature –40°C to +80°C Power Derating - High Temperature Depending on model - Low Input Voltage 2 %/V below 100 VAC See application note: www.tracopower.com/overview/tpi300-m Over Temperature Protection Switch Off - Protection Mode 118°C min. / 125°C typ. / 132°C max. (Automatic recovery at 112°C typ.) - Measurement Point See application note: www.tracopower.com/overview/tpi300-m (Internal Thermistor) Cooling System Forced air cooling (with internal fan) Fan Power Source - Characteristic Variable fan speed (temperature regulated) - Output Voltage 12 VDC - Output Current 500 mA max. General Specifications TPI 300-M Series, 300 Watt All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. www.tracopower.com March 16, 2023 Page 3 / 6

Standby Power Source - Output Voltage 5 VDC - Output Current 1000 mA max. (Fan Power Source and Standby Power Source total power must not exceed 8 W.) Remote Control - Voltage Controlled Remote On: 3.0 to 12 VDC or open circuit Off: 0 to 1.2 VDC or short circuit Refers to '+Remote' and '-Remote' Pin - Off Idle Input Current 16 mA typ. / 25 mA max. (excl. Standby power source and Fan power source) - Remote Pin Input Current -0.5 to 1.0 mA (Standby power source and Fan power source are always present) Altitude During Operation 5'000 m max. Switching Frequency 100 - 180 kHz (PWM) 140 kHz typ. (PWM) Insulation System Reinforced Insulation Working Voltage (rated) 250 VAC Isolation Test Voltage - Input to Output, 60 s 3'000 VAC - Input to Case or PE, 60 s 2'000 VAC - Output to Case or PE, 60 s 2'000 VAC Creepage - Input to Output 13.6 mm min. - Input to Case or PE 5 mm min. - Output to Case or PE 4.2 mm min. Clearance - Input to Output 9.7 mm min. - Input to Case or PE 5 mm min. - Output to Case or PE 4.2 mm min. Isolation Resistance - Input to Output, 500 VDC 100 MΩ min. Isolation Capacitance - Input to Output, 100 kHz, 1 V 1'250 pF typ. / 1'500 pF max. Leakage Current (264 VAC / 63 Hz) - Earth Leakage Current 300 µA max. Distance Through Isolation 0.4 mm Reliability - Calculated MTBF 1'056'000 h (MIL-HDBK-217F, ground benign) Environment - Vibration IEC 60068-2-6 5 g, 3 axis, sine sweep, 3x30 min, 5-500 Hz - Mechanical Shock IEC 60068-2-27 50 g, 3 axis, half sine, 11 ms - Thermal Shock MIL-STD-810F Housing Material Aluminum Housing Type Metal Case Mounting Type Chassis Mount Connection Type Pin Connector Weight 318 g Power OK Signal Open collector output - Trigger Threshold 12 VDC model: 10 - 10.8 VDC 15 VDC model: 12.5 - 13.5 VDC 18 VDC model: 15.3 - 16.2 VDC 24 VDC model: 20 - 21.6 VDC 28 VDC model: 24 - 25.2 VDC 36 VDC model: 31 - 32.4 VDC 48 VDC model: 41.5 - 43.2 VDC 53 VDC model: 46 - 47.7 VDC - Power OK Low level - Power Off High resistance (Refers to 'PG' and '-Vout' Pin) - Pin Specifications 50 VDC / 50 mA max. TPI 300-M Series, 300 Watt All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. www.tracopower.com March 16, 2023 Page 4 / 6

Sense Function 10% max. of Vout nom. (If sense function is not used, sense pins should be connected to output pins.) Environmental Compliance - REACH Declaration www.tracopower.com/info/reach-declaration.pdf REACH SVHC list compliant REACH Annex XVII compliant - RoHS Declaration www.tracopower.com/info/rohs-declaration.pdf Exemptions: 7a, 7c-I (RoHS exemptions refer to the component concentration only, not to the overall concentration in the product (O5A rule). The SCIP number is provided on request.) Supporting Documents Overview Link (for additional Documents) www.tracopower.com/overview/tpi300-m TPI 300-M Series, 300 Watt All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. www.tracopower.com March 16, 2023 Page 5 / 6

TPI 300-M Series, 300 Watt Voltage Adj. 101.6 (4.00) 85.0 (3.346) 15.9 (0.63) 10.8 (0.43) 15.8 (0.62) 8.8 (0.35) 30.5 (1.201) 44.45 (1.75) 95.2 (3.748) All dimensions in mm (inch) Tolerance: X.X ±0.5 (±X.XX 0.02) X.XX ±0.25 (±0.01) Max. screw penetration depth: 3.3 (0.130) Setup screw locked torque: max. 2.5 kgfcm / 0.25 Nm CON2 screw locked torque: max. 16.8 kgfcm / 1.65 Nm wires 24 - 14 AWG BOTTOM VIEW TOP VIEW 109.22 (4.30) 116.8 (4.60) 40.82 (1.607) 62.0 (2.44) 44.5 (1.75) 1.6 (0.06) 59.0 (2.32) 4-M3X0.5 CON3 CON4 CON2 1 2 3 4 CON1 4-M3X0.5 (corner screw holes) 4-M3X0.5 (center screw holes) Inpu utput CON1 CON2 Pin Function Pin Function

1 AC (L) / DC (+) 1 + Vout

3 AC (N) / DC (–) 2 – Vout

2 – Fan 2 – Standby 3 + Sense 3 PG 4 – Sense 4 – Remote 5 + Remote CON1: Molex Housing 09-50-8031 Molex Crimp Terminals 08500106 (2478), 08520112 (6838), 45570 CON2: KST Ring Terminal RVS2-3.7 CON3: Molex Housing 90143-0004 Molex Crimp Terminals 90119 CON4: Molex Housing 51021-0500 Molex Crimp Terminals 50058, 50078 © Copyright 2023 Traco Electronic AG Specification s can be changed without notice. www.tracopower.com Rev. March 16, 2023 Page 6 / 6