Features

◆ Ultra-wide input voltage range ◆ Output voltage adjustable ◆ Overload and short circuit protection ◆ Low ripple and noise ◆ I/O isolation 1500 VDC ◆ Compact, slim plastic case ◆ Reliable snap-on mount on DIN-rail ◆ Bracket for wall mount included ◆ 3-year product warranty In the TCL range of DIN-rail power supplies are 6 models for DC input voltage avail- able. The wide input ranges of 9.5–18 VDC resp. 18–75 VDC means these models can be operated from all popular DC supply voltage systems. With tightly regulated output voltage these DC/DC converters provide a reliable power source for sensitive loads in industrial process controls, factory automation and other equipment exposed to a critical industrial environment. Further applica - tions for these converters are isolation of a specific load or refreshing the 24 V bus voltage. Easy installation is provided with snap-on mounting on DIN-rails and detachable screw terminal block. Order Code Input Voltage Range Output Voltage Output Current max. TCL 012-124 DC 9.5 – 18.0 VDC 24 VDC 1.0 A TCL 024-105 DC 5 VDC 5.0 A TCL 024-112 DC 18 – 75 VDC 12 VDC 2.0 A TCL 024-124 DC 24 VDC 1.0 A TCL 060-112 DC TCL 060-124 DC 18 – 75 VDC 12 VDC

24 VDC

5.0 A 2.5 A Models Page 1 of 3 UL 508 CB Scheme

http://www.tracopower.com Industrial DC/DC-Converter TCL-DC Series 24 to 60 Watt Input Specifications Input power at no load 1.0 Watt max. Start-up voltage/under voltage shut down TCL 012 model: 8.4 VDC / 7 .6 VDC TCL 024 & TCL 060 models: 17 .2 VDC / 15.7 VDC Reverse polarity protection by internal fuse Efficiency 86 % typ. Output Specifications Output voltage adj. range 5 VDC model: 5.0 – 5.25 VDC 12 VDC models: 12.0 – 15.0 VDC 24 VDC models: 24.0 – 28.0 VDC Regulation – Input variation Vin min. to Vin max. 0.5 % max – Load variation 0...100% 0.5 % max Ripple and noise (20 MHz bandwidth) <50 mV pk-pk Electronic short circuit protection current limitation at 1 10 % typ. (constant current, automatic recovery) Overvoltage protection, trigger point 5 VDC model: <6.5 V

12 VDC models: <24 V

24 VDC models: <42 V

Temperature ranges – Operating –25°C to +70°C max. – Storage (non operating) –25°C to +85°C Temperature derating TCL 012 & TCL 024 models: 1.5 %/K above +50°C TCL 060 models: 2.0 %/K above +40°C Humidity (non condensing) 95 % rel. H max. Temperature coefficient 0.02 %/K Switching frequency 55 – 180 kHz depending on load (frequency modulation) Isolation voltage (60 sec.) – Input/Output 1500 VDC Reliability, calculated MTBF at +25°C (according to IEC 61709) >2.5 Mio h Safety standards – Information technology equipment IEC 60950-1, EN 60950-1 (output SELV), UL Std. 60950-1 (2nd Edition) +Am1:201 1, CAN/CSA-C22.2 No. 60950-1-07 +Am1:201 1 – Industrial control equipment UL 508 – Electronic equipment for power installation EN 50178 – Electrical equipment for machines EN 60204 – Measurement, Control & Laboratory IEC 61010-1, EN 61010-1 IEC 61010-2-201, EN 61010-2-201 Safety approvals – UL approval www.ul.com -> certifications UL 508C listed, CSA C22.2 No.14 File e210002 Electromagnetic compatibility (EMC), emissions EN 61000-6-3 – Conducted RI suppression on input EN 55022 class B – Radiated RI suppression EN 55022 class B Electromagnetic compatibility (EMC), immunity EN 61000-6-2 – Electrostatic discharge (ESD) EN 61000-4-2 4 kV / 8 kV – Radiated RF field immunity EN 61000-4-3 10 V/m – Electrical fast transient / burst immunity EN 61000-4-4 Level 3 – Surge immunity EN 61000-4-5 Level 3 – Immunity to conducted RF disturbances EN 61000-4-6 10 Vrms Environmental compliance – Reach www.tracopower.com/info/reach-declaration.pdf – RoHS RoHS directive 2011/65/EU Case protection IP 20 (IEC 60529) Enclosure material plastic UL 94V-0 rated Mounting DIN-rails as per EN 50022-35x15/7 .5 (snap-on with self-locking spring) bracket for wall/chassis mount included Installation instructions www.tracopower.com/overview/tcl-dc All specifications valid at nominal input voltage, full load and +25 °C after warm-up time unless otherwise stated. Page 2 of 3

Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com www .tracopower.com Industrial DC/DC-Converter TCL-DC Series 24 to 60 Watt Rev. November 25, 2020 Page 3 of 3 27 (1.06) 2.2 (0.09) 100.0 (3.94) 75.0 (2.95) DC-ON LED Output voltage adjust INPUT 1 2 3 OUTPUT 1 2 Output Input 1 + Vout 1 Functional Ground 2 – Vout 2 –Vin 3 +Vin Weight: 140g (4.9 oz) Dimensions in [mm], () = Inch Tolerances: ±0.5 (±0.02) Case Dimensions Wall Mounting Bracket Instead on a DIN-rail, the modules can be also mounted on a chassis or wall with help of a mounting bracket which is supplied as standard with each Converter 75.0 (2.95) 100.0 (3.94) 3.2 (0.13) 45 (1.77) DC-ON LED Output voltage adjust OUTPUT 1 1 2 2 INPUT 1 2 3 TCL 012 and TCL 024 models TCL 060 model Weight: 265 g (9.4 oz) Output Input 1 + Vout 1 Functional Ground 2 – Vout 2 –Vin 3 +Vin