AC/DC Industrial Power Supply TBLC 90 Series, 90 Watt

  • High power density in low profile case, module depth < 55 mm
  • Suitable for mounting in domestic installation panels
  • Very high efficiency and low standby power -> compliance to ECO-Standard
  • Low output ripples and spikes
  • Suitable for household appliance and industrial application
  • For distributed power
  • Operating temperature range: –25°C to +70°C
  • UL 508 listed
  • 3-year product warranty IEC 60335-1 IEC 60950-1 UL 60950-1UL 508 This new DIN-Rail mounting power supplies are designed for industrial and res- idential applications. They are lower cost than the existing TBL range, with simi- lar electrical specifications. Additionally, they fully comply to the new standby power and efficiency requirements (ECO Standard). They are intended for con- necting as class II devices, so the safety earth connection is not required. They are mountable in flat racks due to their small dimensions in depth. Their dimen- sions comply to the DIN 43880 standard. Models Order Code Output Power Output Voltage Output Current Efficiency max. nom. (adjustable) max. typ. TBLC 90-112 90 W 12 VDC (12.0 - 16.0 VDC) 7'500 mA 90 % TBLC 90-124 24 VDC (24.0 - 28.0 VDC) 3'750 mA 90 % www.tracopower.com November 30, 2022 Page 1 / 4

Input Voltage Operational Range: 85 - 264 VAC (Full Range) Rated Range: 100 - 240 VAC (Full Range) Input Frequency Operational Range: 47 - 63 Hz Certified: 50/60 Hz Power Consumption - No load & Vin = 230 VAC 500 mW max. (Ready to meet ErP directive) - No load & Vin = 115 VAC 500 mW max. Input Inrush Current - At 230 VAC 50 A max. - At 115 VAC 25 A max. Recommended Input Fuse (The need of an external fuse has to be assessed in the final application.) Input Specifications Output Voltage Adjustment 12 VDC model: 12.0 - 16.0 VDC 24 VDC model: 24.0 - 28.0 VDC (By trim potentiometer) Output power must not exceed rated power! Voltage Set Accuracy ±0.5% max. Regulation - Input Variation (Vmin - Vmax) 0.3% max. - Load Variation (10 - 90%) 0.3% max. Ripple and Noise (20 MHz Bandwidth) 50 mVp-p max. Minimum Load Not required Temperature Coefficient ±0.02 %/K max. Hold-up Time - At 230 VAC 60 ms min. - At 115 VAC 15 ms min. Start-up Time - At 230 VAC 1'000 ms max. - At 115 VAC 1'000 ms max. Short Circuit Protection Continuous, Automatic recovery 70 - 90% of Iout nom. (12 Vout model) 120 - 200% of Iout nom. (24 Vout model) Overload Protection Constant Current Mode Output Current Limitation 105 - 130% of Iout max. Overvoltage Protection 125 - 150% of Vout nom. Transient Response - Peak Variation 400 mV max. (10% to 90% Load Step) - Response Time 1'000 µs typ. (10% to 90% Load Step) Output Specifications Safety Standards - IT / Multimedia Equipment EN 60950-1 IEC 60950-1 UL 60950-1 - Industrial Control Equipment UL 508 - Household EN 60335-1 IEC 60335-1 - Machines Equipment EN 60204 - Power Installation EN 50178 - Measurement, Control & Lab. EN 61010-1 EN 61010-2-201 IEC 61010-1 IEC 61010-2-201 - Power Transformers EN 61558-2-8 EN 61558-2-16 - Converter System EN 62477 IEC 62477 - Certification Documents www.tracopower.com/overview/tblc90 Safety Specifications TBLC 90 Series, 90 Watt All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. www.tracopower.com November 30, 2022 Page 2 / 4

Protection Class Class I & II (Prepared): Reinforced Insulation Class 2 Power Units UL 1310 (24 Vout model only) Pollution Degree PD 2 Over Voltage Category OVC II EMI Emissions EN 61000-6-3 (Generic Residential) EN 61204-3 (Low Voltage Power Supplies) - Conducted Emissions EN 55011 class B (internal filter) EN 55014-1 (internal filter) EN 55032 class B (internal filter) - Radiated Emissions EN 55011 class B (internal filter) EN 55014-1 (internal filter) EN 55032 class B (internal filter) - Harmonic Current Emissions EN 61000-3-2, class A EMS Immunity EN 61000-6-2 (Generic Industrial) EN 61204-3 (Low Voltage Power Supplies) - Electrostatic Discharge Air: EN 61000-4-2, ±8 kV, perf. criteria B Contact: EN 61000-4-2, ±4 kV, perf. criteria B - RF Electromagnetic Field EN 61000-4-3, 10 V/m, perf. criteria A - EFT (Burst) / Surge EN 61000-4-4, ±2 kV, perf. criteria B L to L: EN 61000-4-5, ±1 kV, perf. criteria B L to PE: EN 61000-4-5, ±2 kV, perf. criteria B - Conducted RF Disturbances EN 61000-4-6, 10 Vrms, perf. criteria A - PF Magnetic Field Continuous: EN 61000-4-8, 30 A/m, perf. criteria A - Voltage Dips & Interruptions 230 VAC / 50 Hz: EN 61000-4-11 30%, 25 periods, perf. criteria A 60%, 10 periods, perf. criteria B >95%, 1 period, perf. criteria A

115 VAC / 60 Hz: EN 61000-4-11

30%, 25 periods, perf. criteria B 60%, 10 periods, perf. criteria B >95%, 1 period, perf. criteria B - Voltage Sag Immunity SEMI F47, criteria A EMC Specifications Relative Humidity 95% max. (non condensing) Temperature Ranges - Operating Temperature –25°C to +70°C - Case Temperature +70°C max. - Storage Temperature –40°C to +85°C Power Derating - High Temperature 2.5 %/K above 55°C - Low Input Voltage 2 %/V below 100 VAC Cooling System Natural convection (20 LFM) Altitude During Operation 5'000 m max. (Lower altitude required for IEC61558-1 & 60335 of 3000 m) Switching Frequency 60 - 87 kHz (PWM) Insulation System Reinforced Insulation Isolation Test Voltage - Input to Output, 60 s 3'000 VAC Creepage - Input to Output 4.5 mm min. Clearance - Input to Output 3.7 mm min. Leakage Current - Touch Current 250 µA max. Reliability - Calculated MTBF 1'900'000 h (IEC 61709) Environment - Vibration IEC 60068-2-6 2 g, 3 axis, sine sweep, 3x60 min, 10-150 Hz - Mechanical Shock IEC 60068-2-27 30 g, 3 axis, half sine, 11 ms General Specifications TBLC 90 Series, 90 Watt All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated. www.tracopower.com November 30, 2022 Page 3 / 4

Case Ingress Protection IP 20 (acc. IEC 60529) Housing Material Plastic (UL 94 V-2 rated) Housing Type Plastic Case Mounting Type DIN-Rail Mount (EN 60715 - 35x7.5mm/35x15mm) Connection Type Screw Terminal Weight 280 g Thermal Impedance - Case to Ambient 1.8 K/W typ. Status Indicator Indicated by green LED Environmental Compliance - REACH Declaration www.tracopower.com/info/reach-declaration.pdf REACH SVHC list compliant REACH Annex XVII compliant - RoHS Declaration www.tracopower.com/info/rohs-declaration.pdf Exemptions: 7a, 7c-I (RoHS exemptions refer to the component concentration only, not to the overall concentration in the product (O5A rule). The SCIP number is provided on request.) Supporting Documents Overview Link (for additional Documents) www.tracopower.com/overview/tblc90 Outline Dimensions TBLC 90 Series, 90 Watt Dimensions in mm (inch) Tolerances: ±0.5 (±0.02) 43.5 (1.71) 54.5 (2.15) 90.0 (3.54) 59.5 (2.34) 45.0 (1.77) 89.5 (3.52) Wiring Description Wire size Torque AC Input all models: L, N only (2 pin terminal) AWG 20 - 14 0.5 - 2.5 mm² max. 0.5 Nm DC Output double terminal AWG 20 - 14 0.5 - 2.5 mm² max. 0.5 Nm © Copyright 2022 Traco Electronic AG Specification s can be changed without notice. www.tracopower.com Rev. November 30, 2022 Page 4 / 4