SSH Page 4 SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE © 2005 TELEDYNE RELAYS SSH\\042005\\Q1 NEW Series SSH Output to 75A, 510 Vac with Diagnostics High Industrial Performance (HIPpak) Solid-State Relays OPTIONAL CONNECTIONS Directly with wires, with or without ferrules With tips (ring terminals) CONTROL WIRING With double removeable input connector Pluggable spring connector Min AWG28 Max AWG14 POWER WIRING Number of Wires Screwdriver Type Recommended Torque N.m 1 2 Solid (no ferrule) Fine Stranded (with ferrule) Solid (no ferrule) Fine Stranded (with ferrule) AWG16…AWG8 AWG16…AWG10 AWG16…AWG8 AWG16…AWG10 Pozidriv 2 1.2 Power with tips AWG6 16mm2 AWG4 16mm2 W max = 13mm AWG0 50mm2 for high current Options Fastons: Call us Option clip

© 2005 TELEDYNE RELAYS (800) 284-7007 • www.teledynerelays.com SSH Page 5 SSH\\042005\\Q1 NEW Series SSH Output to 75A, 510 Vac with Diagnostics High Industrial Performance (HIPpak) Solid-State Relays Mounting HIPpak SSRs must be mounted on heat sinks. A large range of heat sinks is available. For heat-sink mounting, use thermal grease or a thermal pad with high conductibility specified by Teledyne. 2–2.5°C/W Teledyne P/N FW151 1.1°C/W Teledyne P/N FW108 0.3°C/W Teledyne P/N FW031 Thermal Pad Teledyne P/N –12 Typical Loads SHH relays with zero-cross turn-on are designed for most types of loads. Our data sheet lists the AC-51 current value corresponding to resistive loads. For other loads, check the inrush current at turn ON and possible overvoltages at turn OFF:

  • AC-55b — Incandescent lamps. Inrush current is generally 10 times In during few 10ms.
  • AC-55a — Electric discharge lamp. These loads often have overcurrent at turn ON and overvoltage at turn OFF , so use 400VAC SSR on 230VAC mains.
  • AC-58 — One-pole motors. These loads often have overcurrent at turn ON and overvoltage at turn OFF , so use 400VAC SSR on 230VAC mains and adapt the SSR current to the starting current of the motor.
  • AC-53 — Three-phase motors. 2 or 3 SH zero-cross relays can drive these motors, but generally use E3P/E3PT or other three- phase relays or SH random range.
  • AC-56a — Transformer loads. Very high inrush current up to 100 times In. Use SH random relay or peak control SSR.
  • AC-56b — Capacitor loads with very high current at turn ON and overvoltage at turn OFF . Our high-voltage relays are well adapted for high inrush current. Protection
  • To protect the SSR against a short-circuit of the load, use a fuse with a I2t value = 1/2 I2t value specified. EMC Immunity:
  • Our data sheets list the immunity level of our SSRs according to the main standards for these of products: IEC/EN61000-4-4 and IEC/EN61000-4-5. Y ou can compare the high immunity level with other products on the market. Emission:
  • Teledyne SSRs are designed in compliance with standards for class A equipment (Industry).
  • Use of this product in domestic environments may cause radio interference. In this case the user may be required to employ additional devices to reduce noise. SSRs are complex devices that must be interconnected with other equipment (loads, cables, etc.) to form a system. Because the other equipment or interconnections may not be under Teledyne’s control, it shall be the responsibility of the system integrator to ensure that systems containing SSRs comply with the requirement of any rules and regulations applicable at the system level.
  • The very low zero-cross voltage of SSH relays (<12 volts) improved the conducted emission level in comparison with most SSRs on the market with zero-cross voltage often higher than 50 volts. DIN Rail Adapter Teledyne P/N DL12