M1020 ENERCON | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 8

Technical content

Page 1 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in M1020 SERIES TVS DIODES PRODUCT HIGHLIGHTS

  • 40 KA, 8/20 TVS DIODES
  • BIDIRECTIONAL DEVICES
  • DESIGNED FOR 320v HIGH ENERGY DC BUS
  • VISUAL LED FAILURE INDICATORS

Page 2 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in

Applications

Military (Airborne, ground-fix, shipboard), Ruggedized, Telecom, Industrial Special Features

  • 40 KA, 8/20µSec TVS diodes
  • Bidirectional devices
  • Designed for 320V high energy DC bus
  • Visual indication in case of a TVS failure
  • DC bus protection
  • Turn on overshoot clamp
  • Lightening protection Electrical characteristics* Paramete r Test Conditions Mi n Type Max Unit Notes ID Vd=380V 1 1.5 10 mA DC leakage V(BR) I(BR)=40mA 40 422 442 V Pulse test Vc Ipulse =50A 460 Pulse test Vc Ipulse 10kA 520 * C F=10kHz, Vd=1vrms 5nF * * Guarantee by design

Page 3 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Absolute Maximum Ratings* Rating Symbol Value Unit Repetitive standoff voltage VWM 380 V Peak energy rating for complete assembly TA=25°C single pulse E(J) 200 Joule Peak current rating per each device 8/20µSec IEC 61000-4-5 Ippm 40 kA Operation temperature T(operation) -40°C to 85°C °C Storage temperature T(storage) -40°C to 85°C °C General information M1020-1 is a protection solution having the parameters described above. The device when mounted on a DIN Rail with 20A serial external circuit breaker provides best in class of bus protection. Please consult factory for details. * Guarantee by design Front Panel LEDs A Green LED, indicates that input power is connected.

Page 4 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Typical test results Connector CH1 yellow trace = TVS voltage during surge test CH2 pink trace = TVS current V clamp = 460V@60A spike

Page 5 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Description of Operation Unit contains TVS diodes. All connected in parallel with external circuit breaker. In case of a failure circuit breaker will be disconnected. The Unit connected with two CB S200MTC-2P-K-20 IAW outline drawing. In case of reverse polarity connection device will not be damage.

Page 6 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Outline Drawing

Page 7 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in

Page 8 of 8 Oct 18, 2021 | Rev c | Doc: DS_M1020 Series M1020 TVS DIODES Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Note: Specifications are subject to change without prior notice by the manufacturer.