Page 1 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in M1012 SERIES DOUBLE-CONVERSION ONLINE UPS 19" RACKMOUNT, 1U HIGH, MILITARY GRADE, UNIVERSAL INPUT RANGE, PURE SINE-WAVE OUTPUT, UP TO 1.25kW/1.5kVA. STACKABLE TO 7.5kW SINGLE-PHASE or 3.75kW 3-PHASE

Page 2 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Highlights

  • Input / Output isolation
  • Pure sine-wave output
  • Remote control and telemetry
  • Internal EMI filters
  • Battery Management System
  • Battery hot-swappable
  • Safe LiFePO4 battery chemistry
  • Stackable for future proofing o 1-phase: up to 7.5kW o 3-phase: up to 3.75kW
  • High efficiency design
  • Protected against: o Short-circuit / Overload o Output over-voltage o Over temperature Electrical Specifications Input Voltage range1: 85 to 265 VRMS Frequency: 47-63 Hz / 400 Hz High Power Factor2: > 0.98 Operates through transients IAW MIL-STD-704A-F Output (Preset in factory) Voltage: Up to 230VAC /400VDC Frequency: Up to 800 Hz Real Power: Up to 1250 W Apparent power: Up to 1500 VA Reactive power: Up to 830VAr Isolation Input to Output: 1000 VDC Input to Case: 1000 VDC Output to Case: 1000 VDC Output Voltage Regulation Less than ±3% (no load to full load, –20C to +50C). Output Waveform Pure sinewave synthesized from a crystal oscillator, with THDV <1.5% into a linear load. EMC Designed to meet3 MIL-STD- 461F CE101, CE102, CS101, CS114, CS115, CS116, RE102, RS103 Backup Backup (full load, 0C to +50°C): > 10 minutes Charge time from depleted to full capacity (0C to +40°C): < 6 hours Battery life expectancy: at least 1000 cycles. Cooling Self-cooled by two internal fans. Thermally controlled fan speed, to reduce noise & increase reliability. Can operate with reduced performance in case of fan failure. Fan assemblies are user replaceable. 1 Power capability is derated to 1000W below 102VRMS. DC input optional with special variant. consult factory.

2 Measured at 115V/60Hz with full resistive load

3 Compliance achieved with shielded cables

Page 3 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Protections 4 Input

  • Under Voltage Lock-Out Input stage shuts down when input voltage falls below

80 VRMS

  • Surge Suppressor Protection against fast transients
  • Catastrophic Failure Protection 20A circuit breaker on input line, to protect the user's system in case of internal failure. Output
  • Overvoltage Protection Output shuts down if output voltage exceeds a preset value due to internal failure.
  • Current Limiting Current waveform is clamped (~21Apk@115VRMS), and the output current shape will be a sinewave with a “flat top”, approaching a square wave at short circuit.
  • Short Circuit Protection At high overload/short- circuit, the output hiccups several times. If the high loading/short persists, the output will be shut down. General
  • Over Temperature Protection o UPS shuts down individual modules if their internal temperature exceeds a preset threshold. UPS resumes operation automatically upon cooldown. o Charger/discharger disconnects the battery if its temperature exceeds a preset threshold. In this case, the UPS continues operation without backup. Charger/discharger resumes normal operation automatically upon battery cool down.
  • Battery Management System o Overcharge: Electronically disconnects the battery if overcharge state is detected. o LVD: Electronic Low Voltage Disconnect if battery voltage drops below preset threshold. o Over Temperature: Electronically disconnects the battery if the internal temperature exceeds a preset threshold. 4 Thresholds and protections can be modified / removed – please consult factory.

Page 4 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Environmental Conditions Designed to meet MIL-STD-810G Temperature Methods 501.5 & 502.5 Operating: -20 C to +50 C (ambient) Charging: 0 C to +40 C (ambient) Storage: –30 C to +60 C (ambient) Altitude Method 500.5 Procedures I – up to 40,000 ft. (non- operational) Procedure II – up to 30,000 ft. (operational) Humidity Method 507.5 Up to 95% RH Salt Fog Method 509.5 Vibration Method 514.6 Category 24 (IAW Figure 514.6E-1) General minimum integrity exposure 1 hour per axis. Fungus Method 508.6 Shock Method 516.6 20g, 11ms terminal peak saw-tooth Sand & Dust Method 510.5 Procedures I & II Acceptance Test Procedure (ATP) & Environmental Stress Screening (ESS) All units go through standard ATP and 24 hours burn-in. In addition, ESS (random vibration and thermal cycling) tests can be performed on each unit – please contact factory for further details. Simplified Block Diagram CIRCUIT BREAKER INPUT EMI FILTER ISOLATED LID HPFC AC/DC DC/AC INVERTER OUTPUT EMI FILTER CHARGER / DISCHARGER LiFePO4 BATTERY CONTROL MONITOR AC INPUT AC OUTPUT

Page 5 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Front Panel Layout Switches Name Description PWR (Toggle switch) Turns UPS ON or OFF Multifunction (Momentary push button)

  • Silences active audible alarm
  • Turns output voltage OFF (Charge-only mode)
  • Prepares the UPS for battery hot-swap (disconnects battery pack) Indications Name Description INPUT OK Input voltage in range OUTPUT OK Output voltage in range of nominal value BATT IN USE Battery discharging (UPS provides backup) LOW BATT Battery discharged to below 20% of full capacity. OVER TEMP Internal temperature exceeds a preset threshold. Indication resets when internal temperature drops back to normal FAN A/B FAIL FAN A / FAN B does not operate normally. FAIL General failure.

Page 6 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Back Panel Layout Switches Name Description AC INPUT ON/OFF 250V / 20A circuit breaker. Connects the UPS to the input voltage line and provides overload and short circuit protection against internal failures. Connectors Designation Name Description J1 INPUT Input voltage connection. Single-phase, 85-265Vrms, 47-63Hz / 400Hz J2 RS-232 Remote communication, telemetry and control over RS-232 protocol. Remote controlled standby mode (via dry contact). J3 CSC/3PC The UPS can be configured to operate in parallel with other UPSs in current share mode, or in a 3-phase connection, by connecting an appropriate cable to this connector. J4 OUTPUT Output voltage connection. Single-phase, 115/230Vrms, 50/60/400Hz/Other (depending on model) J5 ETHERNET Remote communication, telemetry and control, over Ethernet protocol.

Page 7 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Pin Assignment J1 – INPUT connector Connector type: D38999/20WD5PN or eq. Mates with: D38999/26WD5SN or eq. Pin No. Function A GND B Neutral C Neutral D Line E Line J2 – RS-232 connector Connector type: M24308/23-39F or eq. Mates with: M24308/4-3F or eq. Pin No. Function Pin No. Function

1 N/C (for future use) 9 N/C (for future use)

2 N/C (for future use) 10 N/C (for future use)

3 N/C (for future use) 11 Tx

4 RMT_OUT_SHDN 12 5V_SIG

5 RMT_SHDN 13 SIGNAL RTN

6 Rx 14 N/C (for future use)

7 N/C (for future use) 15 RMT_SHDN_RTN

8 N/C (for future use)

Page 8 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in J3 – CSC/3PC connector Connector type: DD15M3000C-15 or eq. Mates with: DD15S1000C-15 or eq. Pin No. Function Pin No. Function

1 AC_OFF_OUT 9 SET_PH0

2 SET_SLV 10 SET_PH1

3 PH_SLV_CFG 11 SYNC_OUT

4 CRNT_SHR_OUT 12 CRNT_SHR_IN_REF

5 CRNT_SHR_OUT_REF 13 SIGNAL_RTN

6 AC_OFF_IN 14 SLV_D_P

7 SYNC_IN 15 SLV_D_N

8 CRNT_SHR_IN

J4 – OUTPUT connector Connector type: D38999/20WD5SN or eq. Mates with: D38999/26WD5PN or eq. Pin No. Function A GND B Neutral C Neutral D Line E Line

Page 9 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Functions Pure Sine-Wave Output Voltage The UPS employs a double-conversion online topology. In this topology, the output voltage is ALWAYS generated inside the UPS, whether the input power is available or not. This means that the load does not suffer from common problems of grid or generator connected loads, such as surges, sags, brown-outs, spikes, frequency transients and high harmonic content. This also means that the transfer from grid to battery backup, and vice versa, is seamless. Backup The UPS contains a plug-in, hot-swappable, LiFePO4 Battery Pack (MPS P/N M1012-3801), that provides, when fully charged, at least ten minutes of backup operation at full load when ambient temperature is between 0C to +50°C, in case of input power loss. Operation at lower temperature down to -20°C is possible with reduced load. Current Share This connector is used to connect a stack of up to six (6) UPS devices in parallel, in order to enable load current sharing. (Modification can be made to enable stacking of more than six UPSs. Please contact the factory for more details). See parallel connection scheme in the M1012 User Manual. 3-Phase Configuration This connector is used to connect three units, in order to enable 3-phase connection, to support 3- phase loads of up to 1.25kW/1.5kVA per phase. See 3-phase connection scheme in the M1012 user manual. Load Gauge The UPS provides a ten-level load gauge, visible on the front panel and through the telemetry communication channels. Battery Fuel Gauge The UPS provides a ten-level battery fuel gauge, visible on the front panel and through the telemetry communication channels. Alarm The UPS provides alarms for various events, that can be viewed on the front panel and audibly heard. The alarms can also be viewed through the telemetry communication channels.

Page 10 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Cooling The UPS uses two internal fans to cool itself during operation. The fans speed is determined by the internal temperature. A fan failure is a rare event. The fan's expected life is 40,000 hours @ 60°C ambient, or 70,000 hours @ 40°C ambient. However, if this failure occurs, please replace the fan as soon as possible. A spare part can be purchased from us for this purpose (MPS P/N M1012-3901). Please refer to M1012 User Manual for maintenance instructions. In case of a fan failure, the appropriate FAN FAIL LED will light up on the front panel, and an indication will appear through the remote communication channel. The UPS will not shut down due to the fan failure itself, but it may shut down due to internal over temperature, that can occur at high power levels and within the normal ambient temperature range.

Page 11 of 11 Feb 23, 2022 | Rev (-) | Doc: DS_M1012 Series M1012 Series– UPS Switzerland sales@enercon-europe.com Israel sales@enercon.co.il India sales@mpsindia.in Outline Drawing Note: Specifications are subject to change without prior notice by the manufacturer Notes 1. Dimensions are in inches 2. Tolerance is: .XX  0.01 in .XXX  0.005 in 3. Weight: Approx. 36 lbs.