AFE2000 ARTESYN | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
[ 2 YEAR WARRANTY ]
- Approved to EN61000, IEC-1000, UL1950, CSA 22.2 No. 950-95
- Operating ambient temperature of 0°C to +50°C
- Complies with ETS300 132-1 and EN61000-3-2
- Hot-swap capability
- 11.5 x 6.75 x 4.9 inch size
- N+1 redundancy capability
- Extensive features available
- Compatible with AFS standard shelves for configuring rack-mounted power systems The AFE2000 power module is a rack mountable single phase AC to DC power supply, designed to be a cost-competitive front-end power supply for distributed power systems. It is particularly suitable for use in data processing, datacom and telecom applications. The outputs are floating so the end user can ground the plus, minus or neither depending on the end use application. The AFE2000 power modules are designed for hot-swap operation and can be mounted into AFS4000/6000 power shelves for redundant-mode operation. SPECIFICATION All specifications are typical at nominal input, full load at 25 °C unless otherwise stated PAGE 1 OUTPUT SPECIFICATIONS Output voltage Main: 48/54.5/56.2VDC ±1.0% Auxiliary: 12VDC ±1.0% Output power Main 2000W Auxiliary 12W Regulation Line, load, IT, ageing ±3.0% Turn-on Output rise time 100 to 400ms Turn-on (AC applied) 4s max. Turn-on (inhibit removed) 1.5s max. Ripple and noise 480mV pk-pk (<50MHz) Transmission noise 100 to 3kHz 35dBrnC Overvoltage protection 60VDC max. Undervoltage protection >44.5VDC Delivers full power <42VDC for >5s Latch-off Short circuit protection <30s Automatic recovery >30s Latch-off Current sharing Active current share ±10% (50% to 100% loading) Remote sense 1.0V max. distribution line loss INPUT SPECIFICATIONS Input voltage range 200/240VAC nom. 170 to 264VAC Input frequency range 50/60Hz nom. 47Hz to 63Hz Input surge current 25°C cold start 22A Safety ground 254VAC @ 60Hz 1.5mA max. leakage current 0.5mA typ. Input current 220VAC, 2000W 10.5A rms Power factor 0.99 min. EMC CHARACTERISTICS Conducted emissions FCC-CFR, part 15, subpart B Class B CISPR 22 Class B Radiated emissions FCC-CFR, part 15, subpart B (Note 7) CISPR 22 (Note 7) Immunity - conducted IEC1000-6 Level 2 Immunity - radiated IEC1000-3 Level 3 Immunity - ESD IEC1000-2 Level 3 Line harmonics per EN61000-3-2 Compliant GENERAL SPECIFICATIONS Hold-up time 150 to 170VAC 500ms (See Note 1) 0 to 150VAC 20ms Efficiency 86% Isolation voltage Input/output 3000VAC Input/chassis 1500VAC Output/chassis 100VAC Switching frequency 200kHz Approvals and EN60950, IEC950, UL1950 standards CSA C22.2 No. 950 Case material Electrolytic zinc coated CRS, ASTM A591, light beige paint Weight 5.0kg (11Ibs) MTBF MIL-HDBK-217E 150,000 hours Demonstrated 300,000 hours ENVIRONMENTAL SPECIFICATIONS Thermal performance Operating ambient 0°C to +50°C Non-operating -40°C to +100°C Cooling Forced air Relative humidity Operating 5% to 95% RH Altitude Operating 13,000 feet max. Vibration 5Hz to 500Hz 0.75G rms peak Shock 15G, 1/2 Sine, 11ms
RIPPLE TOTAL REMOTE PARALLEL MODEL NUMBER VOLTAGE MIN MAX REGULATION ENABLE/INHIBIT INTERFACES 48VDC 0A 41.7A 480mV ±3.0% Inhibit All AFE2000-26S48NA 54.5VDC 0A 36.7A 545mV ±3.0% Inhibit All AFE2000-26S54NA 56.2VDC 0A 35.6A 562mV ±3.0% Inhibit All AFE2000-26S56NA Parallel interface specifications. All signals are referenced to ISO_GND unless otherwise indicated. Isolated signal ground (ISO_GND) May be connected to any voltage in the range from +Vout+5VDC to -Vout- 5VDC. Overtemperature (OTW) Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Signal precedes OT shutdown by 5ms. Logic 1 : Normal operation. Remote Inhibit (INHIBIT) Input bi-level signals. Bi-level input signals shall be no greater than 5VDC. Logic 0 : Normal operation. Logic 1 : Output inhibit. Voltage margin down (DOWN) Input bi-level signals. Bi-level input signals shall be no greater than 5VDC. Logic 0 : Nominal output voltage. Logic 1 : 44.5 to 45.5VDC output. Power good signal (PWR_GOOD) Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Output undervoltage. Logic 1 : Output voltage normal. Fault fail signal (F/F ±) Differential relay contact, isolated from all outputs and returns within the power module. Relay closed : Power supply failure Relay open : Normal operation. Power fail warning signal (PFW) Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Signal precedes loss of output power by 5ms. Logic 1 : Normal operation. Module Missing Pin (MM) Provision for detection of unseated or removed module. MM pins are common internal to the power supply. Internal pull-up resistor to +5VDC logic bias, referenced to RS-. Auxiliary Output (AUX ±) 12VDC auxiliary output. Isolated from both the main output and the isolated signal ground. May be utilized for external housekeeping supply and connected to either main output or isolated signal ground. Current Monitor (IMON) Current source which mirrors magnitude of the output current. Signal return is referenced to RS-. Current Limit (CL) Output bi-level signal. Bi-level output signal is open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Output is in current mode control and is current limiting. Logic 1 : Normal operation. Remote Enable (ENABLE) Input bi-level signal. Bi-level input signal shall be no greater than 5VDC. Logic 0 : Output inhibited. Logic 1 : Normal operation. Reset (RESET) Input bi-level signal. Bi-level input signal shall be no greater than 5VDC. Logic 0 : Resets fault indicators without unit shut-down. Logic 1 : Normal operation. AC Good (AC OK) Output bi-level signal. Bi-level output signal is open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : AC input below normal operating range. Logic 1 : AC input within steady-state operating range (170 to 264VAC). Voltage monitoring (VMARG) Input analog signal referenced to RS-. Adjusts output up to 4VDC higher than the nominal set point.
Features
Live insertion and removal OR-ing diodes provided on output. Voltage monitoring jacks Located on front panel. LED’s (located on front panel) Power Good - Green Power Fail - Red AC Good - Green Protection Thermal protection - automatic shut-off for fan failure or internal overtemperature. Output Overload and Short Circuit - automatic shut-down after 30 seconds. Current regulated output down to less than 1VDC. Output Overvoltage - automatic shut-down for both main (60VDC max.) and auxiliary (15.6VDC max.) outputs. Output Undervoltage - automatic shut-down below 42VDC. Current Share Active current sharing for up to 9 AFE2000 power modules. Short Pin Short pin located in the output connector initiates shut-down of the power supply output when the power supply is removed from the host power shelf.
2000 Watt
AC/DC PFC front-end for distributed power architectures DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES | 2000W AC/DC PAGE 2http://www.artesyn.com Please consult our website for the following items: ✔ Application Note International Safety Standard Approvals EN60950/IEC950 File No. E9972397 UL1950 File No. E135734
(J2) DC connector Elcon 279-0468-00100 or equivalent. (J1) AC connector Power Dynamics 42R08-1122 or equivalent. (J2) DC mating connector Elcon 278-0468-00200 or equivalent. (J1) AC mating connector Power Dynamics 43R06-2114 or equivalent. PAGE 3 AC/DC PFC front-end for distributed power architectures 2000W AC/DC | DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES PIN CONNECTIONS PIN NO. FUNCTION PIN NO. FUNCTION PIN NO. FUNCTION PIN NO. FUNCTION A1 Short Pin B1 DOWN C1 RS+ D1 +Vout A2 AUX+ B2 VMARG C2 RS- D2 +Vout A3 AUX- B3 MM C3 MM D3 PWR RTN A4 RS- B4 I SHR C4 F/F- D4 PWR RTN A5 Not Used B5 RESET C5 F/F+ D5 CGND (2) A6 Not Used B6 IMON C6 INHIBIT/ENABLE A7 AC OK B7 Power Good C7 CL A8 PFW B8 ISO GND (3) C8 OTW SHORT SIGNAL PIN D5 D4 D3 D2 D1 6.75 (171.45) 4.83 (122.68) REF 0.475 (12.065) 1.30 (33.02) 0.074 (1.879) AIR FLOW NORMAL 11.46 (291.08) 0.25 (6.35) 6.44 (163.58) 4.23 (107.44) 0.0875 (2.2225) 5.725 (145.415) AC INPUT POWER DYNAMICS 42R08-1122 MATE - POWER DYNAMICS 43R06-2114 TAPERED GUIDE PIN HOLE TAPERED GUIDE PIN HOLE MAIN DC OUTPUT/SIGNALS ELCON 279-0468-00100 MATE - ELCON 278-0468-00200 0.050 (1.270) 0.800 (20.32) 2.063 (52.400) 0.625 (15.875) 0.375 (9.525)0.462 (11.735) INSERTION/EJECTOR HANDLE WITH 6-32 CAPTIVE SCREW V OUT AC GOOD PWR FAIL PWR GOOD Notes 1 PFW signal warning issued 5 msec prior to shutdown. 2 Chassis or safety ground. 3 Isolated signal ground. 4 Output ground - referenced to RS-.
5 Refer to Application Note 106 for installation of the AFE2000 power
modules into the AFS4000 power shelf.
6 Refer to Application Note 110 for description of outputs and signals
available with AFE2000 power modules installed in Artesyn standard front- end power shelf.
7 Class A for power module, Class B when installed in AFS4000 shelf
(subject to cable/system configuration). 8 NOTICE: Some models do not support all options. Please contact your local Artesyn representative or use the on-line model number search tool at http://www.artesyn.com/powergroup/products.htm to find a suitable alternative. Datasheet © Artesyn Technologies® 2005 The information and specifications contained in this datasheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompa ny the sale of any such product(s) or information contained herein. ds_afe2000_20050824.PDF