AFE1200 ARTESYN | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 3

Technical content

[ 2 YEAR WARRANTY ]

  • Approved to EN61000, IEC-1000, UL1950, CSA 22.2 No. 950-95
  • Operating ambient temperature of 0°C to +50°C
  • Complies with ETS300 132-1 and EN61000-3-2
  • Hot-swap capability
  • 11.5 x 6.75 x 3.35 inch size
  • N+1 redundancy capability
  • Extensive features available
  • Compatible with AFS standard shelves for configuring rack-mounted power systems The AFE1200 power module is a rack mountable single phase AC to DC power supply, designed to be a cost-competitive front-end power supply for distributed power systems. It is particularly suitable for use in data processing, datacom and telecom applications. The outputs are fully floating, enabling users to adopt whatever rail reference configuration they require. The AFE1200 power modules are designed for hot-swap operation and can be mounted into AFS2400/4800 power shelves for redundant-mode operation. SPECIFICATION All specifications are typical at nominal input, full load at 25 °C unless otherwise stated PAGE 1 OUTPUT SPECIFICATIONS Output voltage Main: 24/48Vdc ±1.5% Auxiliary: 12Vdc ±1.0% Output power Main 1200W Auxiliary 12W Regulation Line, load, IT, ageing ±3.0% Turn-on Output rise time 100 to 400ms Turn-on (AC applied) 4s max. Turn-on (inhibit removed) 1.5s max. Ripple and noise <50MHz 480mV pk-pk Transmission noise 100 to 3kHz 35dBrnC Overvoltage protection 60VDC max. Undervoltage protection >44.5VDC Delivers full power <42VDC for >5s Latch-off Short circuit protection <30s Automatic recovery >30s Latch-off Current sharing Active current share ±10% (50% to 100% loading) Remote sense 1.0V max. distribution line loss INPUT SPECIFICATIONS Input voltage range 115/230VAC nom. 85 to 264VAC Input frequency range 50/60Hz nom. 47Hz to 63Hz Input inrush current 25°C cold start 12A typical Safety ground 254VAC @ 60Hz 1.5mA max. leakage current 1.1mA typ. Input current 220VAC, 1200W 7.0A rms Power factor 0.99 min. EMC CHARACTERISTICS Conducted emissions FCC-CFR, part 15, subpart A Class A CISPR 22 Class A Radiated emissions FCC-CFR, part 15, subpart A (Note 8) CISPR 22 (Note 8) Immunity - radiated IEC1000-3 Level 3 Immunity - ESD IEC1000-2 Level 3 Line harmonics per EN61000-3-2 Compliant GENERAL SPECIFICATIONS Hold-up time 75 to 85VAC 500ms (See Note 2) 0 to 75VAC 20ms Efficiency 120VAC 83% 220VAC 86% Isolation voltage Input/output 3000VAC Input/chassis 1500VAC Output/chassis 100VAC Switching frequency 200kHz Approvals and EN60950, IEC950, UL1950 standards CSA C22.2 No. 950 Case material Electrolytic zinc coated CRS, ASTM A591, light beige paint Weight 4.0kg (8Ibs) MTBF MIL-HDBK-217E 150,000 hours Demonstrated 300,000 hours ENVIRONMENTAL SPECIFICATIONS Thermal performance Operating ambient 0°C to +50°C Non-operating -40°C to +100°C Cooling Forced air Relative humidity Operating 5% to 95% RH Altitude Operating 13,000 feet max. Vibration 5Hz to 500Hz 0.75G rms peak Shock 15G, 1/2 Sine, 11ms

RIPPLE TOTAL REMOTE PARALLEL MODEL NUMBER VOLTAGE MIN MAX REGULATION ON/OFF INTERFACES 48VDC 0A 25A 480mV ±3.0% Inhibit All AFE1200-96S48NA 24VDC 0A 50A 240mV ±3.0% Inhibit All AFE1200-96S24NA Parallel interface specifications All signals are referenced to ISO_GND unless otherwise indicated. Isolated signal ground (ISO_GND) May be connected to any voltage in the range from +Vout+5VDC to -Vout- 5VDC. Overtemperature (OTW) Output bi-level signal. Bi-level signals with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Signal precedes OT shutdown by 5ms. Logic 1 : Normal operation. Remote On/Off (INHIBIT) Input bi-level signals. Bi-level input signals shall be no greater than 5VDC. Logic 0 : Output inhibit. Logic 1 : Normal operation. Voltage margin down (DOWN) Input bi-level signals. Bi-level input signals shall be no greater than 5VDC. Logic 0 : Nominal output voltage. Logic 1 : 44.5 to 45.5VDC output. Power good signal (PWR_GOOD) Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Output undervoltage. Logic 1 : Output voltage normal. Fault fail signal (F/F ±) Differential relay contact, isolated from all outputs and returns within the power module. Relay closed : Power supply failure Relay open : Normal operation. Power fail warning signal (PFW) Output bi-level signal. Bi-level signals are open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Signal precedes loss of output power by 5ms. Logic 1 : Normal operation. Module Missing Pin (MM) Provision for detection of unseated or removed module. MM pins are common internal to the power supply. Internal pull-up resistor to +5VDC logic bias, referenced to isolated GND Auxiliary Output (AUX ±) 12VDC auxiliary output. Isolated from the main output. May be utilized for external housekeeping supply and connected to either main output. Current Monitor (IMON) Current source which mirrors magnitude of the output current. Signal return is referenced to RS-. Current Limit (CL) Output bi-level signal. Bi-level output signal with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : Output is in current mode control and is current limiting. Logic 1 : Normal operation. Reset (RESET) Input bi-level signal. Bi-level input signal shall be no greater than 5VDC. Logic 0 : Normal operation. Logic 1 : Resets fault indicators without unit shut-down. AC Good (AC OK) Output bi-level signal. Bi-level output signal is open-collector (drain) with a 5mA sink capability and maximum voltage stand-off of 60VDC. Logic 0 : AC input below normal operating range. Logic 1 : AC input within steady-state operating range. Voltage monitoring (VMARG) Input analog signal referenced to RS-. Adjusts output up to 4VDC higher than the nominal set point.

Features

Live insertion and removal OR-ing diodes provided on output. Voltage monitoring jacks Located on front panel. LED’s (located on front panel) Power Good - Green Power Fail - Red AC Good - Green Protection Thermal protection - automatic shut-off for fan failure or internal overtemperature. Output Overload and Short Circuit - automatic shut-down after 30 seconds. Current regulated output down to less than 1VDC. Output Overvoltage - automatic shut-down for both main (60VDC max.) and auxiliary (15.6VDC max.) outputs. Output Undervoltage - automatic shut-down below 42VDC. Current Share Active current sharing for up to 9 AFE1200 power modules. Short Pin Short pin located in the output connector initiates shut down of the power supply output when the power supply is removed from the host power shelf.

1200 Watt

AC/DC PFC front-end for distributed power architectures DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES | 1200W AC/DC PAGE 2http://www.artesyn.com Please consult our website for the following items: ✔ Application Note International Safety Standard Approvals AFE1200-96S24NA safety approval is pending EN60950/IEC950 File No. E9972397 UL1950 File No. E135734

(J2) DC connector Elcon 377-0002-00100A or equivalent. (J1) AC connector Power Dynamics 42R08-1122 or equivalent. (J2) DC mating connector Elcon 376-0002-00200A or equivalent. (J1) AC mating connector Power Dynamics 43R06-2114 or equivalent. PAGE 3 AC/DC PFC front-end for distributed power architectures 1200W AC/DC | DISTRIBUTED POWER FRONT END AC/DC POWER SUPPLIES AC INPUT POWER DYNAMICS 42R08-1122 MATE - POWER DYNAMICS 43R06-2114 MAIN DC OUTPUT/SIGNALS ELCON 377-0002-00110A (PINS) MATE-ELCON 376-0002-00200A (SOCKETS) INSERTION / EJECTOR HANDLE WITH 6-32 CAPTIVE SCREW NORMAL .074 (1.880) 1.30 (33.02) 6.75 (171.45) 3.35 (85.09) .483 (12.268) .662 (16.815) .350 (8.890) 2.098 (53.289) 5.750 (146.05) 6.44 (163.58) 2.75 (69.85) .800 (20.320) .050 (1.270) 6.44 (163.58) 11.46 (291.08) 1.150 (29.210) REF AIR FLOW GUIDE PIN HOLE GUIDE PIN HOLE ALL MEASUREMENTS INCHES (MM) Notes 1 PFW signal warning issued 5 msec prior to shutdown. 2 Chassis or safety ground. 3 Isolated signal ground. 4 Secondary return and RS- are common and tied together internally.

5 Refer to Application Note 110 for installation of the AFE1200 power

modules into the AFS2400/AFS4800 power shelf.

6 Refer to Application Note 110 for description of outputs and signals

available with AFE1200 power modules installed in Artesyn standard front- end power shelf.

7 Class A for power module, Class B when installed in AFS2400/4800 power

shelf (subject to cable/system configuration). 8 NOTICE: Some models do not support all options. Please contact your local Artesyn representative or use the on-line model number search tool at http://www.artesyn.com/powergroup/products.htm to find a suitable alternative. PIN CONNECTIONS PIN NO. FUNCTION PIN NO. FUNCTION PIN NO. FUNCTION PIN NO. FUNCTION

1 Not Used 10 SGND (4) 19 PFW (1) 27 VMARG

2 Not Used 11 RS- (4) 20 ISO GND (3) 28 EXT VCC+

3 PWR RTN 12 RS+ 21 IMON 29 AUX-

4 PWR RTN 13 F/F- 22 Power Good 30 I SHR

5 PWR RTN 14 CL 23 F/F+ 31 OTW

6+ Vout 15 N/U 24 MM 32 AUX+ 7+ Vout 16 MM 25 DOWN 33 SHORT PIN 8+ Vout 17 AC OK 26 INHIBIT 34 CGND (2)

9 Not Used 18 RESET

Datasheet © Artesyn Technologies® 2005 The information and specifications contained in this datasheet are believed to be correct at time of publication. However, Art esyn Technologies accepts no responsibility for consequences arising from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompa ny the sale of any such product(s) or information contained herein. ds_afe1200_20050824.PDF