702030 JUMOUKLTD | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 12
Technical content
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com Page 1/12 JUMO Quantrol LC100/LC200/LC300 Universal PID Controller Series Brief description The Quantrol series is available in the three DIN formats 48 mm x 48 mm, 48 mm x 96 mm, and 96 mm x 96 mm. It is used for two-state and three-st ate control applications as well as for the control of regulating valves or SCR power controllers via a continuous controller output. The universal analog input for RTD temperature probes, thermocouples, or current/voltage sig- nals is user programmable. The setpoint value, the actual value, and all parameters are dis- played on two seven-segment LED displays (red/gr een) with one or two decimal place(s). The values can be displayed in °C or °F. Depending on the format, up to five relay outputs with a switching capacity of 3 A / 230 V or up to four logic outputs 0/14 V are available. The switch po- sition of the relays or logic outputs is displayed using yellow LEDs. Different functions can be as- signed to these outputs. An analog output 0 to 10 V or 0(4) to 20 mA is configurable as continuous controller output, actual value output, or setpoint value output. Using the binary input, the device settings and operation can be locked, a ra mp or the timer can be activated, or self- optimization can be initiated. The supply vo ltage is optionally AC 110 to 240 V or AC/DC 20 to 30 V. The controller has a ramp function with adjustable gradient for constant setpoint change. In ad- dition, a special firing curve for small pottery ki lns can be used which allows controlled starting and time dependent firing. The user can enter set point values, gradient, and firing time directly at the device. The device can be connected to host systems or devices using the RS485 se rial interface. In- stead of operating the device from the front, the us er can also program the controller using the setup program and USB interface; this require s no additional voltage supply for the controller. The Quantrol series, like all JUMO controllers, is also equipped with reliable JUMO self-optimi- zation (autotuning). LC100 (702031) LC200 (702032) LC300 (702034) Block diagram Options are delivered ex-factory acc. to the order details. Option 1 Option 2 Option 3 Option 4 X X X X Relay output (N/O contact) X X X X Logic output X Analog output X RS485 interface Analog input Binary input Setup interface Option 4* Relay (N/O contact) Option 3* Option 2 Option 1 LC100 LC200 LC300 * Option for LC200/LC300 Special features
- 48 × 48, 48 × 96, 96 × 96 mm formats
- Two-state/three-state and continuous con- troller
- Sensor monitoring
- Up to 5 outputs
- Self-optimization (autotuning) for exact PID control
- Manual/automatic mode
- Configurable limit value monitoring (alarms)
- Setpoint changeover
- Level inhibit and key lock
- RS485 interface (Modbus RTU)
- Ramp and timer function
- Firing curve for pottery kilns
- Push-in controller insert
- Setup interface (USB Mini-B) Approvals/approval marks (see "Technical data") Data Sheet 702030 2013-09-23/00600565
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 2/12
Description
Self-optimization (autotuning) Standard features include the tried and tested self-optimization (oscil lation method), which makes it possible for the controller to be matched to the control loop by a user who is not a control technology expert. Here, the re- action of the control path to the specific vari- able changes is evaluated and the controller parameters proportional band, reset time, de- rivative time, cycle time, and filter time con- stant are calculated. Ramp function The ramp function is used for a constant change of setpoint value w up to the ramp limit value SP (entered setpoint value). A rising or a falling edge arises depending on the actual value at the time of ramp start t0. The slope is defined by a gradient which is entered during the controller configuration. Firing curve The firing curve is used for controlled starting and time-dependent firing of small pottery kilns. The user can enter setpoint values, gra- dient, and firing time directly at the device. Limit value monitoring The controller is equipped with two limit value monitoring functions, each with eight configu- rable alarm functions. Any analog signals can be selected as actual and setpoint value from a selector. When a limit value is exceeded, a signal can be displayed or an internal control- ler function initiated. With the limit value mon- itoring, extensive alarm and limit value functions can be implemented. t Setpoint value Actual value Timer The timer is started manually or automatically (after power on, for example). When the timer expires, the timer output signal changes its state (configurable). The timer can be used to implement functions like time-limited control or setpoint changeover. Setup program The setup program provides the user with an easy and comfortable way to configure the controller using a PC. The PC has to be connected to the controllers USB interface (Mini-B type) with a USB cable. Thereby the controller is powered over the USB interface. As a result, no mains supply is required during the configuration.
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 3/12 Controller parameters All the parameters and their meanings are included in the table. Some parameters may be missing or meaningless for a particular type of controller. Technical data Thermocouple input RTD temperature probe input Parameters Value range Factory setting Meaning Proportional band 1 (Pb1) 0 to 9999 digit 0 digit Size of the proportional band The controller structure is not effective with Pb = 0 (behavior identical to limit value monitoring). For a continuous controller, Pb1 must be > 0. Proportional band 2 (Pb2) 0 to 9999 digit 0 digit Derivative time (dt) 0 to 9999 s 80 s Influences the differential component of the controller output signal Reset time (rt) 0 to 9999 s 350 s Influences the integral component of the controller output signal Cycle time 1 (Cy1) 0 to 999.9 s 20.0 s When using a switch ed output, the cycle time should be chosen so that the energy supply to the process is as continuous as possible without overloading the switching elements. Cycle time 2 (Cy2) 0.0 to 999.9 s 20.0 sec Contact spacing (db) 0.0 to 999.9 digit 0.0 digit Spacing between the two control contacts of the three-state controller Switching differential 1 (HyS1) 0.0 to 999.9 digit 1.0 digit Switching differential of a switching controller with proportional band Pb = 0 (behavior identical to limit value monitoring)Switching differential 2 (HyS2) 0.0 to 999.9 digit 1.0 digit Working point (y0) -100 to +100 % 0 % Output level for P and PD controller (if x = w then y = y0) Output value limit 1 (y1) 0 to 100 % 100 % Maximum output value limit (only effective if Pb > 0) Output value limit 2 (y2) -100 to +100 % -100 % Minimum output value limit (only effective if Pb > 0) Description Standard Measuring range a a This information refers to the ambient temperature of 20 °C. Measuring accuracyb b Incl. measuring accuracy at the cold junction. The accuracy values refer to the measuring range. Ambient temperature influence Fe-CuNi "L" Fe-CuNi "J" Cu-CuNi "T" NiCr-Ni "K" NiCr-CuNi "E" NiCrSi-NiSi "N" Pt10Rh-Pt "S" Pt13Rh-Pt "R" EN 60584 EN 60584 EN 60584 EN 60584 EN 60584 EN 60584 EN 60584 -150 to +900 °C -200 to +1200 °C -200 to +400 °C -200 to +1372 °C -200 to +1000 °C -100 to +1300 °C -40 to +1768 °C -40 to +1768 °C ≤ 0.4 % ≤ 0.4 % ≤ 0.4 % ≤ 0.4 % ≤ 0.4 % ≤ 0.4 % ≤ 0.4 % ≤ 0.4 % ≤ 100 ppm/K ≤ 100 ppm/K ≤ 100 ppm/K ≤ 100 ppm/K ≤ 100 ppm/K ≤ 100 ppm/K ≤ 100 ppm/K ≤ 100 ppm/K Cold junction: KTY internal Designation, connection type Measuring range Measuring accuracy a Ambient temperature influence Pt100 EN 60751 2-wire connection 3-wire connection -200 to +650 °C ≤ 0.4 % ≤ 0.4 % ≤ 50 ppm/K Pt1000 EN 60751 2-wire connection 3-wire connection -200 to +650 °C ≤ 0.4 % ≤ 0.4 % ≤ 50 ppm/K KTY , R25 = 1000 Ω 2-wire connection -50 to +150 °C ≤ 1.0 % ≤ 50 ppm/K KTY , R25 = 2000 Ω 2-wire connection -50 to +80 °C ≤ 1.0 % ≤ 50 ppm/K Cu-50 3-wire connection -50 to +200 °C ≤ 1.0 % ≤ 50 ppm/K
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 4/12 Input for standard signals Binary input Measuring circuit monitoring In the event of a malfunction, the outputs move to a defined (configurable) status. Outputs Probe wire resistance: max. 30 Ω per wire with 3-wire circuit Measuring current: Pt100 approx. 1 mA; Pt1000 and KTY approx. 100 μA Lead compensation: not required for 3-wire circuit. For a 2-wire circuit, the lead resistance can be compensated by correcting the actual value. a The accuracy values refer to the measuring range. Measuring range Measuring accuracy a a The accuracy values refer to the maximum measuring range. Ambient temperature influence Voltage 0 to 10 V Input resistance > 650 kΩ Current 0(4) to 20 mA Voltage drop > 2.2 V Input for potential-free contact Open = inactive; Closed = active Measuring probe Overrange/underrange Probe/cable short circuit Probe/cable break Thermocouple • - • RTD temperature probe • • • Voltage 0 to 10V - - - Current 4 to 20 mA • • • Current 0 to 20 mA - - -
- = detected - = not detected Relay (N/O contact) Contact rating Contact life Max. 3 A at 230 V AC resistive load 150,000 operations at nominal load 350,000 operations at 1 310,000 operations at 1 A and cosϕ > 0.7 Logic output 0/14V / 20mA max. Voltage (option) Output signal Load resistance Accuracy 0 to 10V > 600 Ω < 0.5 % Current (option) Output signals Load resistance Accuracy 0 to 20 mA / 4 to 20 mA < 450 Ω < 0.5 % Designation, connection type Measuring range Measuring accuracy a Ambient temperature influence
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 5/12 Controller Timer Electrical data Requirements for core-end ferrules and cable lugs Case and ambient conditions Controller type Two-state controller, thr ee-state controller, continuous controller Controller structures P/PI/PD/PID Sampling rate 250 ms A/D converter 16-bit resolution Accuracy 0.8 % ± 10 ppm/K ± 250 ms Voltage supply (switch mode PSU) AC 110 to 240V +10/-15 %, 48 to 63Hz AC/DC 20 to 30V, 48 to 63Hz Electrical security Acc. to DIN EN 61010, pa rt 1; overvoltage category III, pollution degree 2 Power consumption Max. 14 VA Electrical connection On the rear via screw terminals; with core-end ferrule of a pipe shape, open cable lug or pin cable lug Conductor cross section Fine-strand 0.25 to 1.5 mm 2 Tightening torque 0.5 Nm Electromagnetic compatibility Acc. to DIN EN 61326-1 Interference emission Class A - only for industrial use - Interference immunity Industrial requirements Setup interface USB socket, type Mini-B 5-pole Core-end ferrule Pipe shape, without pl astic sheath acc. to DIN 46228 part 1, with plastic sheath acc. to DIN 46228 part 4 Cable lug Open crimp cable lug, dimensionally adapted to DIN 46237 for closed crimp cable lugs Pin cable lug Acc. to DIN 46231 For UL applications Use of the cabl e lugs or ferrules acc. to UL 486A-B (UL listed or recognized) Case type Plastic case for panel mounting acc to. IEC 61554 (indoor use) Dimensions (front) LC100: 48 mm x 48 mm; LC200: 48 mm x 96 mm (portrait format); LC300: 96 mm x 96 mm Weight (fully fitted) LC100: approx. 150 g; LC200: approx. 200 g; LC300: approx. 300 g Protection class Acc. to DIN EN 60529, at the front IP 65, at the rear IP 20 Operating position Any Panel cut-out LC100: 45 mm x 45 mm; LC200: 45 mm x 92 mm; LC300: 92 mm x 92 mm Minimum spacing horizontal/vertical LC100: 11 mm / 30 mm (65 mm with USB cable); LC200/LC300: 22 mm / 30 mm (65 mm with USB cable) Depth behind panel LC100: max. 95 mm; LC200/LC300: max. 80 mm Ambient/storage temperature range -5 to +55 °C / -40 to +70 °C Climatic conditions Rel. humidity < 90 % annual average, without condensation Site altitude Up to 2000 m above sea level
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 6/12 Interface 7-segment displays Approvals/approval marks Interface type RS485 Protocol Modbus RTU Baud rate 9600, 19200 Data format 8 data bits, no parity bit, 1 stop bit Device address 0 to 254 No. of subscribers Max. 32 Digit height LC100, LC200 Upper display: 10 mm; lower display: 7 mm LC300 Upper display: 20 mm; lower display: 13 mm Color Upper display: red; lower display: green Places 4 (including decimal places) Decimal places 0, 1, 2 (configurable) Display range -1999 to 9999 Approval mark Testing agency Certificate/certification number Inspection basis Valid for c UL us Underwriters Laboratories E201387 UL 61010-1, CAN/CSA C22.2 No. 61010-1 all versions
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 7/12 Dimensions LC100 (1) Setup interface (USB) on the device top (2) Panel cut-out +0.6 +0.6 (1) (2)
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 8/12 LC200 (1) Setup interface (USB) on the device bottom (2) Panel cut-out +0.8 +0.8 (1) (2)
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 9/12 LC300 Minimum spacing of panel cut-outs (1) Setup interface (USB) on the device bottom (2) Panel cut-out Type Without USB cable With USB cable Horizontal Vertical Horizontal Vertical LC100 11 mm 30 mm 11 mm 65 mm LC200 22 mm 30 mm 22 mm 65 mm LC300 22 mm 30 mm 22 mm 65 mm +0.8 +0.8 (1) (2)
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 10/12 Display and control elements Electrical isolation Connection diagram The connection diagram in the data sheet prov ides preliminary information about the connection possibilities. For the electrica l connection only use the brief instructions or the operating manual. The knowledge and the correct technical execut ion of the safety information /instructions con- tained in these documents are mandatory for installation, electrical connection, and startup as well as for safety during operation. The terminal strips on the device rear are equipped with screw terminals. Please refer to the technical data for specifications concerning the con- ductor cross section. (A) Programming / one level deeper (B) Value reduction / previous parameter (C) Value increase / next parameter (D) Function key / leave level (E) Red 7-segment display (factory-set: actual value); 4-digit, configurable decimal place (automatic adjustment on display over- flow) (F) Green 7-segment display (factory-se t: setpoint value); 4-digit, configurable decimal place; also display of level and parameter symbols (G) LED 1 to 3(5): switching position of bi nary output (LED is lit = output active) (H) LED ramp function or firing curve The software version is displayed on the device when simultaneously pressing keys (A) and (C). (1) Analog input (2) Binary input (3) Setup interface (USB) (4) Voltage supply (5) RS485 interface (6) Analog output (7) Relay outputs (8) Logic outputs LC100 LC200 LC300 (H) (G) (E) (F) (A) (B) (C) (D) (4) (3) (2) (1) (7)(6)(5) (8)
30 V AC
50 V DC2300 V
50 V DC
N(L-) L1(L+) USB N(L-) L1(L+) USB N(L-) L1(L+) USB
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 11/12 Connection Symbol LC100 LC200/LC300 Analog input Thermocouple 9 10 81 1 RTD temperature probe, 2-wire 10 9 81 1 RTD temperature probe, 3-wire 10 9 91 0 81 1 Voltage DC 0 to 10 V (usable alternatively to binary input) 12 7 11 8 Current DC 0(4) to 20 mA 91 0 81 1 Binary input for potential-free contact (usable alternatively to analog input DC 0 to10 V) 11 7 12 8 O u t p u t : 12312345 Analog output DC 0 to 10 V, DC 0(4) to 20 mA 13 12 14 13 Relay output (N/O contact) (max. 3 A at AC 230 V, resistive load) 41 36 41 2 1 4 1 6 1 8 51 47 51 3 1 5 1 7 1 9 Logic output (DC 0/14 V) 13 7 12 14 16 18 1 4 6 1 31 51 71 9 RS485 interface 71 4 61 5 Output 1 as standard; outputs 2 to 5 optional (options 1 to 4) Voltage supply L1 (L+) L1 (L+) N (L-) N (L-) Setup interface USB socket, type Mini-B 5-pole U - x Ix x IxU , U - x RxD/TxD AC/DC
JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: 315-437-5866 1-800-554-5866 Fax: 315-437-5860 E-mail: info.us@jumo.net Internet: www.jumousa.com 2013-09-23/00600565 Data Sheet 702030 Page 12/12 Order details Scope of delivery Accessories (1) Basic type
702031 Quantrol LC100 (format 48 mm x 48 mm) 1x analog input (universal), 1x binary input a, 1x relay
output (N/O contact) a Binary input for potential-free contact (usable alternatively to analog input DC 0 to 10 V).
702032 Quantrol LC200 (format 48 mm x 96 mm, portrait format) 1x analog input (universal), 1x binary
inputa, 1x relay output (N/O contact)
702034 Quantrol LC300 (format 96 mm x 96 mm) 1x anal og input (universal), 1x binary inputa, 1x relay
output (N/O contact) (2) Version X X X 8 Standard with factory settings X X X 9 Customer-specific configuratio n (specifications in plain text) (3) Option for expansion slot 1 X X X 0 Not used X X X 1 1 relay output (N/O contact) X X X 2 1 logic output X X X 3 1 analog output (configurable) (4) Option for expansion slot 2 X X X 0 Not used X X X 1 1 relay output (N/O contact) X X X 2 1 logic output X X X 4 1 RS485 interface (5) Option for expansion slot 3 X X X 0 Not used X X 1 1 relay output (N/O contact) X X 2 1 logic output (6) Option for expansion slot 4 X X X 0 Not used X X 1 1 relay output (N/O contact) X X 2 1 logic output (7) Voltage supply X X X 23 AC 110 to 240 V +10/-15 %, 48 to 63 Hz X X X 25 AC/DC 20 to 30 V, 48 to 63 Hz Order code /- - Order example 702034 / 8 - 3 4 1 2 - 23 1 controller in the ordered version (including seal and fastening elements) 1 Brief Instructions B 702030.7 in DIN A6 format (multilingual) Description Part no. USB cable, A-connector to Mini-B-connector, length 3 m 00506252