Page 1/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc.

6724 Joy Road

East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 JUMO miroVIEW Smart digital indicator with limit value monitoring function Brief description The smart digital indicator is used for the electronic display of a process temperature. The device acquires this via an analog input for a RTD temperature probe. Further functionalities are limit value monitoring, min/max value storage, hold function and tare function. The device is available with 1 relay (normally open contact AC 250 V, 16 A). The difference between the two types of devices is the diameter of the front panel: Type 701590 Ø 60.5 mm, Type 701591 Ø 80.5 mm. The round housing design allows the device to be used wherever round dial instruments were previously in use. The device is characterized by simple, clearly structured operation supported by texts in English, German, French, and Spanish. Process values, texts, and parameters are shown in two 18-seg- ment LCD displays. Additional d isplay elements inform about the switch position of the output, the timer status, and temperature unit. Pluggable terminal strips with PUSH IN technology enable fast electrical installation. Operation, parameterization, and configuration are carried out via a membrane keyboard with four keys. The setup program on a PC allows the device to be configured without any problems. No separate voltage supply is required when configuring via the USB interface (USB-powered). miroVIEW Type 701590 Block diagram Membrane keypad Type 701590/701591- AC 230 V +10/-15 %, 48 to 63 Hz - AC 115 V +10/-15 %, 48 to 63 Hz - DC 12 to 24 V 15 %±

1 Relay (NO contact AC 250 V, 16 A)

2-wire RTD temperature probe Pt100, Pt1000 Analog input Digital input for potential-free contact Digital input Digital output Special features

  • Integrated timer function
  • Service and operating hours counter
  • Fast wiring through pluggable terminal strips with PUSH IN technology
  • High-quality display and intuitive opera- tion
  • Configuration on the device or with the setup program (accessories) via USB in- terface (USB-powered
  • Operator guidance with text support in 4 languages
  • Limit value monitoring function Approvals and approval marks (see technical data)

Page 2/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Device types Type 701590 Type 701591

Description

In addition to the classic display of the mea- sured value, the device has additional func- tions such as min/max v alue display, a hold function for freezing the measured value and a tare function for weighing applications. Some functions can be configured via the membrane keypad on the front. Inputs and outputs An RTD temperature probe in two-wire circuit can be connected via the analog input for tem- perature measurement. As relay output 1 nor- mally open contact is available. The digital input is provided to connect a potential-free contact. USB device interface The device is equipped with a USB device in- terface (micro-B socket on the rear side). This is intended for connecting to a PC and for con- figuring the device via the setup program. Thereby the device is powered via the USB in- terface. As a result, no mains supply is re- quired during the configuration. Electrical connection The electrical connection saves time by using practical spring-cage terminals (Push-In tech- nology). Limit value monitoring functions The device is equipped with three limit value monitoring functions, each with two configu- rable alarm functions. Any analog signal from a selector is selected as the value to be moni- tored. An absolute value serves as the limit value. Special functions such as switch-on/ switch-off delay, pulse function, alarm sup- pression in the switch-on phase or in case of a parameter change, alarm latch, and lock with acknowledgment are available. With the limit value monitoring function, extensive alarm and limit value functions can be implemented. Timer After the timer is started, a signal is output for the duration of the timer running time; this sig- nal is invertible. It is also possible to start the timer after the lead time has elapsed or after reaching a tolerance limit. A timer end signal can be output after the timer has elapsed (limit by time or acknowledgement). Service counter The service counter is used either to count the switching frequency of a binary signal or to de- termine its switch-on duration. When the set limit value is reached, a b inary signal is acti- vated that needs to be acknowledged. In addition, an operating hours counter is available that determines the device's opera- tion time. Setup program The setup program, which is available as an accessory, provides the user with an easy and comfortable way to configure the device using a PC. This allows data records to be created, edited and transferred to the device, as well as read out from there. A recording function for start-up is available. Customer-specific Linearization Sensor signals with special characteristic line properties can also be used through custom- er-specific linearization. Programming is car- ried out in the setup program on the basis of a value table with up to 40 value pairs or through a formula (4th order polynomial).

Page 3/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Technical data Analog input RTD temperature probe Measuring circuit monitoring The device behavior in the event of a malfunction is configurable. Digital input Digital output Interface Display Designation Standard ITS Connection type Measuring range Accuracy a Measuring current Pt100 DIN EN 60751:2008 IEC 60751:2008 ITS-90 Two-wire -200 to +600 °C ≤ 0.25 % 500 μA Pt1000 DIN EN 60751:2009 IEC 60751:2008 ITS-90 Two-wire -200 to +600 °C ≤ 0.25 % 100 μA Customer-specific 150 to 3000 Ω≤ 0.25 % < 500 μA a Accuracy refers to the measuring range. Ambient temperature influence ≤ 300 ppm/K Sensor line resistance Max. 30 Ω per line Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s Measuring probe Measuring range un- derflow Measuring range overflow Short-circuit (probe/ line) Break (probe/line) Reverse polarity RTD temperature probe ++ ++ ++ ++ --- ++ = is detected --- = is not det ected (+) = is detected in certa in conditions Input for potential-free contact Function Contact closed: input is active (R ON < 1 kΩ) Contact open: input is inactive (ROFF > 100 kΩ) 1 relay (normally open contact) Order code 25 Switching capacity Max. 16 A at AC 250 V, resistive load Contact life 100,000 switching operations at rated load USB device Connector type Micro-B (socket) Standard Low-Speed, Full-Speed Max. cable length 5 m 18-segment LCD displays Upper display: Lower display: Digit height 13 mm 4 mm Color white Green Places, including decimal places 4 7 Decimal places 0, 1, or automatic (configurable)

Page 4/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Electrical data Environmental influences Voltage supply according to the ordered version

02 AC 230 V -15/+10 %, 48 to 63 Hz

05 AC 115 V -15/+10 %, 48 to 63 Hz

30 DC 12 to 24 V, -15/+15 % SELV

Electrical safety acc. to DIN EN 61010, part 1 Overvoltage category II to 300 V mains voltage, Pollution degree 2 Power consumption Type AC 230 V: Type AC 115 V: Type DC 12 to 24 V: Accuracy of timer 1 % Sampling rate 250 ms Electrical connection On the back v ia plug connectors with spring-cage terminals (PUSH IN technology) Conductor cross section, mechanical Wire or stranded wire (without ferrule) Min. 0.2 mm2, max. 1.5 mm2 (terminal strips 3 and 4: max. 2.5 mm2) Stranded wire with ferrule Without plastic collar: min. 0.25 mm 2, max. 1.5 mm2 (terminal strips 3 and 4: max. 2.5 mm2) With plastic collar: min. 0.25 mm2, max. 0.75 mm2 (terminal strips 3 and 4: max. 2.5 mm2) Stripping length 8 mm Conductor cross section, electric 5 A load current Min. 0.75 mm 2 10 A load current Min. 1.0 mm 2 16 A load current Min. 1.5 mm 2 Ambient temperature range Storage -30 to +70 °C Operation -10 to +55 °C Site altitude Max. 2000 m above sea level Climatic environmental influences According to DIN EN 60721-3 with extended temperature range Resistance to climatic conditions ≤ 90 % rel. humidity without condensation Storage According to class 1K2 Operation According to class 3K3 Mechanical environmental influences According to DIN EN 60721-3 Storage According to class 1M2 Transport According to class 2M2 Operation According to class 3M3 Electromagnetic compatibility (EMC) Product family standard DIN E N 61326-1 Interference emission Class B a a The product is suitable for industrial use as well as for households and small businesses Interference immunity Industrial requirement

Page 5/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Case Approvals and approval marks The device is approved if the relevant approval mark is pictured on the device. Case type Plastic case for panel mounting according to IEC 61554 (indoor use), cobalt blue RAL 5013 Case front Membrane keyboard, upper slope cobalt blue RAL 5013, lower slope silver grey RAL 7001 Panel thickness 1 to 10 mm Case mounting In panel using the supplied mounting frame or both mounting elements Operating position Any a a The maximum admissible ambient temperature only applies for the installation with the display in a vertical position. Protection type According to DIN EN 60529, IP65 on the front, IP20 on the back Weight Type 701590 Max. 160 g Type 701591 Max. 240 g Approval mark Test facility Certificates/Certification numbers Inspection basis Valid for c UL us Underwriters Laboratories E201387 UL 61010-1 (3rd Ed.), CAN/CSA-22.2 No. 61010-1 (3rd Ed.) All types

Page 6/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Dimensions Type 701590 4,8 Ø Ø 64,4 76,4 80 Ø 68 60,6

Page 7/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Type 701591 Installation dimensions 4,8 Ø Ø8 0 Ø9 5 Ø 88 60,6 Type Panel cut-out Ø Mounting depth without seal Minimum spacing of panel cut-outs (for close mounting) Horizontal Vertical 701590 60.5 +0.5 mm 80 mm 15 mm 30 mm 701591 80.5 +0.5 mm

Page 8/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Galvanic isolation (a) (1) AC 3000 V (b) (a) AC 3000 V (3) (4) (5) (6) (7) (8) a The voltage specifications correspond to the test voltag- es (alternating voltage, rms values) according to DIN EN 61010-1 (VDE 0411-1):2020-03 b Functional galvanic isolation for connecting SELV or PELV electrical circuits

1 Relay output

3 USB interface 4 or

5 Voltage supply DC 12 V to 24 V 6 Voltage supply 230 V, 48 to 63 Hz

1 1 5V , 4 8t o6 3H z

7 Digital input 8 Analog input

Page 9/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Display and control elements (1) (2)(8) (3)(4) (7) (5)(6) 1 Display 1 - 18-segment LCD display (e.g. actual val- ue), 4-digit, white; also for displaying menu items, parameters and text 2 Display 2 - 18-segment LCD display (e.g. setpoint val- ue), 7-digit green; displaying of menu items, parameters, text and values; here individually configured measuring point designa- tion (ZONE 1)

3 Menu/OK (call up main menu, switch to submenu/level,

switch to editing mode, exit editing mode with change)

4 Back (in menu: back to previous menu level, exit editing

mode without change; in basic status: configurable function)

5 Down (in the menu: reduce value, select next menu

item or parameter)

6 Up (in the menu: increase value, select previous menu

item or parameter)

7 Timer (illuminated = on , flashing = started),

8 Switch position of the digital outputs (yellow = active)

Page 10/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Connection diagram The connection diagram in the data sheet provides information on product selection. For the electrical connection, only use the installation instructions or the operating manual. Type 701590 (Ø 60) and Type 701591 (Ø 80) Ø6 0m m Ø8 0m m Terminal strip 2 Analog input, digital input Terminal strip 3 L1(L+), N(L-) Terminal strip 4 Digital output RTD temperature probe in two-wire circuit and digital input Voltage supply (see name- plate) AC 230 V, 48 to 63 Hz or AC 115 V, 48 to 63 Hz or DC 12 to 24 V 1 relay normally open contact 1 2 3 1 2

Page 11/11Data Sheet 701590 JUMO GmbH & Co. KG Delivery address: Mackenrodtstraße 14 Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 Email: mail@jumo.net Internet: www.jumo.net JUMO Instrument Co. Ltd. JUMO House Temple Bank, Riverway Harlow, Essex, CM20 2DY, UK Phone: +44 1279 63 55 33 Fax: +44 1279 62 50 29 Email: sales@jumo.co.uk Internet: www.jumo.co.uk JUMO Process Control, Inc. East Syracuse, NY 13057, USA Phone: +1 315 437 5866 Fax: +1 315 437 5860 Email: info.us@jumo.net Internet: www.jumousa.com 70159000T10Z001K000 Order details Scope of delivery Accessories (1) Basic type

701590 Type 701590 with 1 relay, format (Ø 60 x 80) mm

701591 Type 701591 with 1 relay, format (Ø 80 x 80) mm

(2) Version

0 Standard version

1 Customized hardware

2 Customized software

3 Customized hardware and software

(3) Input (measurement input group) 01 1 RTD temperature probe Pt100 , Pt1000 in two-wire circuit, 1 digital input (4) Output 25 1 relay (normally open contact AC 250 V, 16 A) resistive load (5) Voltage supply

02 AC 230 V, +10/-15 %, 48 to 63 Hz

05 AC 115 V, +10/-15 %, 48 to 63 Hz

a

30 DC 12 to 24 V +15/-15 %

(6) Extra codes

000 None

a Minimum order quantity 50 pieces Order code /---- Order example 701590 / 0 - 01 - 25 - 02 - 000 1 device in the ordered version 1 quick start guide 2 panel fasteners Pluggable terminal strips Description Part no. Setup program 00777355 USB cable, A connector to Micro-B connector, length 3 m 00616250