GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM STRAP-ON LOW LIMIT THERMOSTAT TLSO SERIES PRODUCT DESCRIPTION The single point strap-on low limit thermostat incorporates a precision thermistor temperature sensor and provides a Form C relay output (NO/ NC) with an adjustable setpoint. The sensor is encapsulated in a 38.1 mm x 12.7 mm (1.5” x 0.5”) machined aluminum heat sink. A 254 mm (10”) S/S Pipe clamp is provided to secure the assembly to various sizes of pipe. All probes are constructed to provide excellent heat transfer, fast response and are potted to resist moisture penetration. A hinged and gasketed Polycarbonate enclosure is included for ease of installation. TYPICAL INSTALLATION For complete installation and wiring details, please refer to the product installation instructions. The strap-on temperature transmitter series can be mounted directly to various sizes of pipes and secured using a 254 mm (10”) S/S pipe clamp. If necessary, remove a section of insulation from the pipe. The 254 mm (10”) S/S pipe clamp is a “Quick Release” type and can be separated by moving the tightening screw so that it is perpendicular to the clamp and slide the clamp apart. Position the aluminum plate on the pipe so it makes the best contact, wrap the clamp around the pipe and re-assemble and tighten. Any excess clamp may be cut off. For best results, thermal conductive compound should be applied to pipe prior to mounting the probe. Wiring connections are made inside the enclosure. POWER SUPPLY 12 to 28 Vac/dc SENSOR ACCURACY ±0.2°C, 0 to 70°C (±0.36°F, 32 to 158°F) PROBE SENSING RANGE -40 to 100°C (-40 to 212°F) PROBE MATERIAL Machined aluminum heat sink PROBE DIMENSIONS 38.1mm x 12.7mm (1.5” x 0.5”) WIRE MATERIAL PVC insulated, parallel bonded CONSUMPTION 50 mA max RELAY CONTACTS SPDT, Form C contacts (N.O. and N.C.)

5 Amps @ 30 Vdc/250 Vac resistive

1.5 Amps @ 30 Vdc/250 vac inductive

RELAY ACTION Activates on temperature fall SETPOINT OPERATION Single-turn knob-pot on PCB ADJUSTABLE SETPOINT -4 to 10°C (25 to 50°F) TEMPERATURE DIFFERENTIAL Low: 1.1°C (2°F) Mid: 2.8°C (5°F) High: 5.6°C (10°F) Jumper selectable TEMPERATURE SENSOR 10,000Ω curve matched precision thermistor OPERATING CONDITIONS -10 to 50°C (14 to 122°F), 5 to 95 %RH, non-condensing STORAGE CONDITIONS -30 to 70°C (-22 to 158°F), 5 to 95 %RH, non-condensing WIRING CONNECTIONS Screw terminal block (14 to 22 AWG) ENCLOSURE B: Grey polycarbonate UL94-V0, IP65 (NEMA 4X) F: Same as B with thread adapter (1/2” NPT to M16) and cable gland fitting COUNTRY OF ORIGIN Canada SPECIFICATIONS CABLE GLAND FITTING THREAD ADAPTER 1/2” NPT TO M16 ACCESSORIES - INCLUDED WITH F ENCLOSURE OPTION 114.3 mm 4.5" 99.7 mm 3.93" 112.5 mm 4.43" 53.7 mm 2.11" 28.6 mm 1.125" 0.5" NPT 254 mm (10") S/S Pipe Clamp Quick Release Machined Aluminum

PRINTED IN CANADA Copyright © Greystone Energy Systems Inc. All Rights Reserved www.greystoneenergy.com PS-TLSOXXX-03 Greystone Energy Systems, Inc.

150 English Drive, Moncton,

New Brunswick, Canada E1E 4G7 Ph: +1 (506) 853-3057 Fax: +1 (506) 853-6014 North America: 1-800-561-5611 E-mail: mail@greystoneenergy.com WIRING INFORMATION TERMINAL FUNCTION PWR Power Supply COM Power Supply Common TEMP (2) Temperature Sensor Input NO Relay Output - Normally Open Contact COM Relay Common NC Relay Output - Normally Closed Contact PRODUCT TLSO Strap-on Low Limit Thermostat ENCLOSURE B F Polycarbonate, with hinged and gasketed cover Same as B, with thread adapter and cable gland fitting SENSOR 24X 10,000Ω, Type 2, NTC Thermistor, ±0.2°C ADJUSTABLE SETPOINT RANGE 01 -4 to 10°C (25 to 50°F) ORDERING TLSO PART NUMBER NOTE: Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NO COM NC DIFFERENTIAL HIGH LOW MID TEMP COM PWR