GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM OUTSIDE CARBON DIOXIDE TRANSMITTER CD2OS SERIES PRODUCT DESCRIPTION The outside CO2 transmitter device uses a highly accurate and reliable non-dispersive infrared (NDIR) sensor in an vented, weatherproof enclosure to monitor outside CO2, levels. The sensor uses dual wavelength optics and LTA (long term adjustment) signal processing technology to deliver industry leading long-term accuracy and reliability. Standard features include a field selectable output signal of either 4-20 mA, 0-5 Vdc or 0-10 Vdc for the highest versatility, programmable CO2 measurement span, a backlit alpha-numeric LCD and easy menu operation for configuration. Optional features include a resistive temperature sensor output and a control relay with programmable setpoint,hysteresis and time delay. TYPICAL INSTALLATION For complete installation and wiring details, please refer to the product installation instructions. The CD2OS should be mounted on an outside North facing wall, under the eaves which will provide protection from direct sunlight and wind. The CD2OS can be mounted directly to buildings wall face using the provided mounting holes. There are 0.85” knockouts for conduit connection. The basic CD2OS has a 3 wire configuration with a screw block terminal provided for connection to the Building Automation System. GAS TYPE DETECTED Carbon Dioxide (CO2) SENSOR TYPE Dual Wavelength Non-Dispersive Infrared (NDIR) SENSOR ACCURACY ± (30ppm + 3% of measured value) MEASUREMENT RANGE 0-2000ppm, adjustable 1000 - 10,000ppm ALTITUDE ADJUSTMENT 0-2550m in 50m increments TEMPERATURE DEPENDENCY ±2.5ppm/°C RESPONSE TIME 20 seconds (T63) - See Note WARM-UP TIME 1 minute SENSOR LIFE SPAN >15 years TRANSMITTER ACCURACY ±0.25% of span (including linearity, hysteresis and repeatability) POWER SUPPLY 24 Vdc ± 20% or 24 Vac ± 10% (non-isolated half-wave rectified) PROTECTION CIRCUITRY Reverse voltage and transient protected INPUT VOLTAGE EFFECT Negligible over specified operating range OUTPUT SIGNAL TYPE 4-20 mA (3-wire), 0-5 or 0-10 Vdc (field selectable) CURRENT CONSUMPTION (4-20 mA OUTPUT) Heated: 1.0A max @ 24 Vdc 1.1 A max @ 24 Vac Unheated: 75 mA max @ 24 Vdc 150 mA max @ 24 Vac CURRENT CONSUMPTION (0-5/10 Vdc OUTPUT) Heated: 1.0 A max @ 24 Vdc

1.1 A max @ 24 Vac

Unheated: 50 mA max @ 24 Vdc 100 mA max @ 24 Vac OUTPUT DRIVE @ 24 VDC Current: 550Ω max Voltage: 10,000Ω min OPERATING CONDITIONS Heated: -40 to 50°C (-40 to 122°F) Unheated: 0 to 50°C (32 to 122°F) 5 to 90 %RH non-condensing STORAGE CONDITIONS -40 to 70°C (-22 - 158°F), 5 to 90 %RH non-condensing CONCEALED LCD DISPLAY (USED FOR SETTING PARAMETERS) Units: ppm (CO2) Range: 0-10,000ppm Size: 35mm W x 15mm H (1.4” x 0.6”), Alpha-numeric 2 line x 8 character OPTIONAL TEMPERATURE SENSOR Type: Thermistor and RTD (see ordering chart) Accuracy: See ordering chart Output: 2-wire resistive OPTIONAL RELAY (2-WIRE OUTPUT) Selectable CO2 high or CO2 low Rating: Form A (N.O.), 2 Amps @ 140 Vac / 30 Vdc ENCLOSURE 110mm W x 180mm H x 89mm D (4.3” x 7.125” x 3.5”) IP65 (NEMA 4X) WIRING CONNECTIONS Screw terminal block (14 to 22 AWG) Optional Temperature: Pigtail, 2 or 3 wire APPROVALS CE COUNTRY OF ORIGIN Canada SPECIFICATIONS NOTE: The outside enclosure slows the sensor response time to approximately 30 minutes for a 90% step change of CO2 concentrations. 95mm 3.75” 165mm 6.5” 109mm 5.3” 89mm 3.5” 180mm 7.125” North Outside CO2 Transmitter

PRINTED IN CANADA Copyright © Greystone Energy Systems Inc. All Rights Reserved www.greystoneenergy.com PS-CD2OSXXX-01 Greystone Energy Systems, Inc.

150 English Drive, Moncton,

New Brunswick, Canada E1E 4G7 Ph: +1 (506) 853-3057 Fax: +1 (506) 853-6014 North America: 1-800-561-5611 E-mail: mail@greystoneenergy.com WIRING INFORMATION CO2 SENSOR RELAY CO2 COM PWR MENUUPDOWNVOLT mA CO2 COM PWR TERMINAL FUNCTION CO2 Analog Output COM COMMON PWR Supply Voltage RELAY Relay Output OPTIONAL TEMPERATURE Pigtail, 2 or 3 wire TERMINAL FUNCTION CO2 Analog Output COM COMMON PWR Supply Voltage RELAY Relay Output OPTIONAL TEMPERATURE Pigtail, 2 or 3 wire CO2 SENSOR RELAY CO2 COM PWR MENUUPDOWNVOLT mA HEATED UNHEATED PRODUCT CD2OS Outside Carbon Dioxide Transmitter ENCLOSURE H N Weatherproof, heated Weatherproof, unheated OPTIONAL TEMPERATURE SENSOR XX None 100Ω Platinum, IEC 751, 385 Alpha, thin film, 3 wire 1801Ω NTC Thermistor, ±0.2°C 3000Ω NTC Thermistor, ±0.2°C 10,000Ω Type 3, NTC Thermistor, ±0.2°C 2.252KΩ NTC Thermistor, ±0.2°C 1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel, Class B, DIN 43760 10,000Ω Type 3, NTC Thermistor, ±0.2°C c/w 11,000 shunt resistor 20,000Ω NTC Thermistor, ±0.2°C 10,000Ω Type 2, NTC Thermistor, ±0.2°C RELAY X R None Relay ORDERING CD2OS PART NUMBER NOTE: Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.