TLFL GREYSTONE | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM FLYING LEAD LOW LIMIT THERMOSTAT TLFL SERIES CABLE GLAND FITTING THREAD ADAPTER 1/2” NPT TO M16 ACCESSORIES - INCLUDED WITH F ENCLOSURE OPTION PRODUCT DESCRIPTION The single point flying lead low limit thermostat incorporates a precision thermistor temperature sensor and provides a Form C relay output (NO/ NC) with an adjustable setpoint. The sensor is encapsulated in a 6 mm (0.236”) OD X 50 mm (2”), 304 series stainless steal probe. Standard wire length is 3.05m (10’). All probes are constructed to provide excellent heat transfer, fast response and are potted to resist moisture penetration. A hinged and gasketed Polycarbonate enclosure is provided for ease of installation. TYPICAL INSTALLATION For complete installation and wiring details, please refer to the product installation instructions. A typical application for the flying lead type probes is to monitor a single point temperature within the duct. Install the probe in a straight section of duct at a suitable distance downstream from any heating, cooling or humidification devices. Drill a 3/8” hole in the top of the duct and hang the sensor in the airstream. The enclosure provides mounting tabs for ease of installation. POWER SUPPLY 12 to 28 Vac/dc SENSOR ACCURACY ±0.2°C, 0 to 70°C (±0.36°F, 32 to 158°F) PROBE SENSING RANGE -40 to 60°C (-40 to 140°F) PROBE MATERIAL 304 series stainless steel PROBE DIAMETER 6mm (0.236”) WIRE MATERIAL FT-6 Plenum rated cable WIRE LENGTH 3.05 m (10’) CONSUMPTION 50 mA max RELAY CONTACTS SPDT, Form C contacts (N.O. and N.C.)

5 Amps @ 30 Vdc/250 Vac resistive

1.5 Amps @ 30 Vdc/250 vac inductive

RELAY ACTION Activates on temperature fall SETPOINT OPERATION Single-turn knob-pot on PCB ADJUSTABLE SETPOINT -4 to 10°C (25 to 50°C) SETPOINT TEMPERATURE Low: 1.1°C (2°F) Mid: 2.8°C (5°F) High: 5.6°C (10°F) Jumper selectable TEMPERATURE SENSOR 10,000Ω curve matched precision thermistor AMBIENT OPERATING RANGE -40 to 50°C (-40 to 122°F), 5 to 95 %RH, non-condensing STORAGE CONDITIONS -30 to 70°C (-22 to 158°F), 5 to 95 %RH, non-condensing WIRING CONNECTIONS Screw terminal block (14 to 22 AWG) ENCLOSURE B: Grey polycarbonate UL94-V0, IP65 (NEMA 4X) F: Same as B with thread adapter (1/2” NPT to M16) and cable gland fitting COUNTRY OF ORIGIN Canada SPECIFICATIONS 112.5 mm 4.43" 99.7 mm 3.93" 3.05 m 10.00’ 6.00 mm 0.236" 50 mm FT-6 Rated Plenum Cable, 22 AWG 304 Series S/S Probe 116.5 mm 4.58" 53.7 mm 2.11" 0.5" NPT

PRINTED IN CANADA Copyright © Greystone Energy Systems Inc. All Rights Reserved www.greystoneenergy.com PS-TLFLXXX-03 Greystone Energy Systems, Inc.

150 English Drive, Moncton,

New Brunswick, Canada E1E 4G7 Ph: +1 (506) 853-3057 Fax: +1 (506) 853-6014 North America: 1-800-561-5611 E-mail: mail@greystoneenergy.com WIRING INFORMATION TERMINAL FUNCTION PWR Power Supply COM Power Supply Common TEMP (2) Temperature Sensor Input NO Relay Output - Normally Open Contact COM Relay Common NC Relay Output - Normally Closed Contact PRODUCT TLFL Flying Low Limit Thermostat ENCLOSURE B F Polycarbonate, with hinged and gasketed cover Same as B, with thread adapter and cable gland fitting SENSOR 24X 10,000Ω, Type 2, NTC Thermistor, ±0.2°C ADJUSTABLE SETPOINT RANGE 01 -4 to 10°C (25 to 50°F) ORDERING TLFL PART NUMBER NOTE: Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NO COM NC DIFFERENTIAL HIGH LOW MID TEMP COM PWR