TLAP GREYSTONE | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM ALL PURPOSE DUCT/IMMERSION LOW LIMIT THERMOSTAT TLAP SERIES PRODUCT DESCRIPTION The single point duct/immersion low limit thermostat incorporates a precision thermistor sensor and provides a Form C relay output (NO/NC) with an adjustable setpoint. The sensor is encapsulated in a 6mm (0.236”) OD, 304 stainless steel probe and is available in various lengths (see ordering chart). All probes provide excellent heat transfer, fast response and resist moisture penetration. A hinged and gasketed Polycarbonate enclosure is provided for ease of installation. TYPICAL INSTALLATION For complete installation and wiring details, please refer to the product installation instructions. The duct type probes are installed through a hole in the side of the duct to monitor a single point temperature within the duct. Since the probes are tip sensitive, select a probe length that places the sensor well into the duct. Install the probe in a straight section of duct at a suitable distance downstream from any heating, cooling or humidification devices. The enclosure provides mounting tabs for ease of installation. NOTE: For immersion applications, T2 series thermowell is required. When using a T1 series thermowell an adapter will be required. POWER SUPPLY 12 to 28 Vac/dc SENSOR ACCURACY ±0.2°C, 0 to 70°C (±0.36°F, 32 to 158°F) PROBE SENSING RANGE -40 to 100°C (-40 to 212°F) PROBE MATERIAL 304 series stainless steel PROBE DIAMETER 6 mm (0.236”) STANDARD LENGTHS 50, 100, 150, 200, 300, and 450 mm WIRE MATERIAL PVC insulated, parallel bonded, 22 AWG CONSUMPTION 50 mA max RELAY CONTACTS SPDT, Form C contacts (N.O. and N.C.)

5 Amps @ 30 Vdc/250 Vac resistive

1.5 Amps @ 30 Vdc/250 vac inductive

RELAY ACTION Activates on temperature fall SETPOINT OPERATION Single-turn knob-pot on PCB ADJUSTABLE SETPOINT -4 to 10°C (25 to 50°F) SETPOINT TEMPERATURE Low: 1.1°C (2°F) Mid: 2.8°C (5°F) High: 5.6°C (10°F) Jumper selectable TEMPERATURE SENSOR Precision thermistor AMBIENT OPERATING RANGE -10 to 50°C (14 to 122°F), 5 to 95 %RH, non-condensing STORAGE CONDITIONS -30 to 70°C (-22 to 158°F), 5 to 95 %RH, non-condensing WIRING CONNECTIONS Screw terminal block (14 to 22 AWG) ENCLOSURE B: Grey polycarbonate UL94-V0, IP65 (NEMA 4X) F: Same as B with thread adapter (1/2” NPT to M16) and cable gland fitting COUNTRY OF ORIGIN Canada SPECIFICATIONS Various Probe Lengths See Specifications 116.5 mm 4.58" 0.5" NPT Foam Gasket

304 Series S/S

53.7 mm 2.11" 6.00 mm 0.236" 112.5 mm 4.43" 99.7 mm 3.93" DUCT MOUNTING THERMOWELL MOUNTING T1-AP THERMOWELL ADAPTER THERMOWELL PLACEMENT MOUNTING STYLES

PRINTED IN CANADA Copyright © Greystone Energy Systems Inc. All Rights Reserved www.greystoneenergy.com PS-TLAPXXX-02 06/20 Greystone Energy Systems, Inc.

150 English Drive, Moncton,

New Brunswick, Canada E1E 4G7 Ph: +1 (506) 853-3057 Fax: +1 (506) 853-6014 North America: 1-800-561-5611 E-mail: mail@greystoneenergy.com WIRING INFORMATION TERMINAL FUNCTION PWR Power Supply COM Power Supply Common TEMP (2) Temperature Sensor Input NO Relay Output - Normally Open Contact COM Relay Common NC Relay Output - Normally Closed Contact CABLE GLAND FITTING THREAD ADAPTER 1/2” NPT TO M16 ACCESSORIES - INCLUDED WITH F ENCLOSURE OPTION PRODUCT TLAP All Purpose Duct/Immersion Low Limit Thermostat ENCLOSURE B F Polycarbonate, with hinged and gasketed cover Same as B, with thread adapter (1/2” NPT to M16) and cable gland fitting SENSOR 24 10,000Ω, Type 2, NTC Thermistor, ±0.2°C PROBE LENGTH A B C D E F 50mm (2”) 100mm (4”) 150mm (6”) 200mm (8”) 300mm (12”) 450mm (18”) ADJUSTABLE SETPOINT RANGE 01 -4 to 10°C (25 to 50°F) ORDERING TLAP PART NUMBER NOTE: Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NO COM NC DIFFERENTIAL HIGH LOW MID TEMP COM PWR