SS12 SYSTEMSENSOR | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- 93mA avg. current draw at 24VDC, regulated power supply for SS241575ADA
- Multiple light intensities –24 VDC: 15, 15/75, 75, or 110 cd models –12 VDC: 15 or 15/75 cd
- No measurable in-rush in excess of peak current
- Intended for primary signaling
- Installer Easy strobe features –Mounts to single gang box with MP-SF plate –Plug-in terminal strip –Wire strip gauge and wiring diagram on back
- Available with Multi-Alert™ horn, Sound Choice™ SP101, or V400 Series speaker
- 3 year warranty Specifications Input terminals: 18 – 12 A WG Shipping Weight: SS Series Strobes: 5 oz. (141g) MASS Series Horn/Strobes: 10.4 oz. (293g) Operating Temperature Range: 32 °F to 120°F (0°C to 49°C) Mounting: Surface: 4 ″ × 4″ × 1 1/2″ standard backbox (21/8″ recommended) Semiflush: 4 ″ × 4″ × 11/2″ standard backbox (21/8″ recommended) with MP-SF semi-flush mounting plate (order separately) Dimensions: TOP TOP 53/32″ SS12/24ADA Series MASS12/24ADA Series
Sound Output Selection Guide Multi-Alert Sounder – MA12/24D Current (mA) Sound Output (dBA) Clips on DC Regulated/FWR Unfiltered 2 Average* Peak* UL (dBA) Ratings Available Sounds Tabs (ABC) 1 12V 24V 30V 12V 24V 12V 24V 12V 24V Slow Whoop ABC 21/40 38/56 46/72 85 92 93 100 79 85
800 Hz continuous
(factory setting) BC 15/24 28/45 35/55 87 93 94 99 79 85 800–1000 Hz Alternating AC 17/32 34/46 43/58 85 92 91 98 79 85
2400 Interrupted AB 19/23 35/56 43/64 89 90 96 98 79 85
2400 Continuous C 21/31 38/59 46/73 85 94 93 104 79 85
1200 Interrupted B 13/19 23/33 27/41 85 91 95 101 75 82
Swept Frequency A 17/24 34/47 43/60 85 92 96 101 79 85 Fast Warble None 15/27 30/47 38/59 85 92 93 100 79 85 Multi-Alert Sounder – MA12/24EH Current (mA) Sound Output (dBA) Clips on DC Regulated/FWR Unfiltered
2 Average* Peak* UL (dBA) Ratings
Available Sounds Tabs (ABC) 1 12V 24V 30V 12V 24V 12V 24V 12V 24V Fast Whoop ABC 21/40 38/56 46/72 85 92 93 100 79 85
800 Hz Continuous BC 15/24 28/45 35/55 87 93 96 101 79 85
800/1000 Hz Fast Dual AC 17/32 34/46 43/58 85 92 95 101 79 85 Chirp AB 19/23 35/56 43/64 89 90 93 104 79 85
2400 Hz Continuous C 21/31 38/59 46/73 85 94 96 98 79 85
Bell B 13/19 23/33 27/41 85 91 91 98 75 82 Laser A 17/24 34/47 43/60 85 92 94 99 79 85 Electro-Mechanical None 15/27 30/47 38/59 85 92 93 100 79 85 (factory setting) * dBA measured in anechoic room at 10 feet. 1.See Tone Selection diagram below for tab clip removal and storage. 2.All models can be powered using uncoded full wave rectified, unfiltered supplies. Under no circumstances can the MA12/24 or SS12/24 Series device input voltage exceed 33 VDC or be less than 9.6 VDC. Engineering Specifications Strobe shall be a System Sensor Model ______ listed to Standard UL 1971 for the Hearing Impaired and shall be approved for Fire Protective Service. Strobe shall be wired as a Primary Signaling Notification appliance. Strobe shall also comply with the Americans with Disabilities Act requirements for visible signaling appliances. Strobe shall operate on 12 or 24VDC from a regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be powered from a non-coded power supply when powered with the horn or powered independently. Strobe shall have no measurable in-rush current in excess of operating peak current. Visual signaling devices are to be installed in all non-sleeping/corridor and sleeping areas per plans and specifications. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. All strobes shall be capable of mounting to a standard 4″ × 4″ × 1 1/2″ backbox, in either a surface mount or semiflush mount with separate mounting plate. CLIP STORAGE CLIPS REMOVED OR ADDED TO SELECT DESIRED TONE. COVER SLOT TAB A TAB B TAB C FOR STORING UNUSED CLIPS: SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST. SLIDE COVER FOR CLIP STORAGE USE A SMALL- BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS MA Sounder Tone Selection
– VDC + VDC + VDC – VDC STROBE SOUNDER NON- CODED SUPPLYCAN BE CODED SUPPLY From panel or previous device To Next Device or EOL – VDC + VDC Note: NON- CODED SUPPLY Jumpers (included in screw-pack) must be installed as shown for tandem operation. Break off tab Horn/Strobe CombinationStrobe Only From panel or previous device To Next Device or EOL – VDC + VDC IN(–) OUT(–) IN(+) OUT(+) (–)IN (–)OUT (+)IN (+)OUT Standard Light Distribution Vertical Dispersion Horizontal Dispersion A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the Standard UL 1971 for the Hearing Impaired, with specific minimum intensity percentages as shown in the graphs above. LIGHT –45˚45˚ 90˚ –90˚ WALL Degree Percent of Rating 0 100 5-25 90 30-45 75 50 55 55 45 60 40 65 35 70 35 75 30 80 30 85 25 90 25 ZERO AXIS W A L L FLOOR 30354045505560657075808590˚ Degree Percent of Rating 0 100 5-30 90 35 65 40 46 45 34 50 27 55 22 60 18 65 16 70 15 75 13 80 12 85 12 90 12
Ordering Information
Models – ADA Compliant, UL 1971 Listed Electromechanical Operating Strobe Current Red Beige(B)/White(W) Tone Product Voltage (Average mA) Candela Signaling Strobes SS2415ADA SS2415ADAB Signaling Strobe 24 VDC 75 15 SS241575ADA SS241575ADAB Signaling Strobe 24 VDC 93 15/75 SS2475ADA SS2475ADAB Signaling Strobe 24 VDC 170 75 SS24110ADA SS24110ADAB Signaling Strobe 24 VDC 210 110 SS1215ADA SS1215ADAB Signaling Strobe 12 VDC 170 15 SS121575ADA SS121575ADAB Signaling Strobe 12 VDC 225 15/75 Multi-Alert Sounder with Signaling Strobe MASS2415ADA MASS2415ADAB MAEH2415ADA Sounder with Signaling Strobe 24 VDC * 15 MASS241575ADA MASS241575ADAB MAEH241575ADA Sounder with Signaling Strobe 24 VDC * 15/75 MASS2475ADA MASS2475ADAB MAEH2475ADA Sounder with Signaling Strobe 24 VDC * 75 MASS24110ADA MASS24110ADAB MAEH24110ADA Sounder with Signaling Strobe 24 VDC * 110 MASS1215ADA MASS1215ADAB MAEH1215ADA Sounder with Signaling Strobe 12 VDC * 15 MASS121575ADA MASS121575ADAB MAEH121575ADA Sounder with Signaling Strobe 12 VDC * 15/75 V400 Series Speaker with Signaling Strobe V4R2415ADA Speaker with Signaling Strobe 24 VDC 75 15 V4R241575ADA Speaker with Signaling Strobe 24 VDC 93 15/75 V4R2475ADA Speaker with Signaling Strobe 24 VDC 170 75 V4R24110ADA Speaker with Signaling Strobe 24 VDC 210 110 SP101 Series Speaker with Signaling Strobe SP1R2415ADA SP1W2415ADA Speaker with Signaling Strobe 24 VDC 75 15 SP1R241575ADA SP1W241575ADA Speaker with Signaling Strobe 24 VDC 93 15/75 SP1R2475ADA SP1W2475ADA Speaker with Signaling Strobe 24 VDC 170 75 SP1R24110ADA SP1W24110ADA Speaker with Signaling Strobe 24 VDC 210 110 *Total current = strobe current + sounder current Note: All 1575ADA strobe products are recommended for 20 ′ × 20′ areas or less. How to Order SS1215ADAB B=Beige Strobe 12 = 12 Volt 24 = 24 Volt SS = Signal Strobe MASS = Multi-Alert Sounder/Strobe MAEH = Multi-Alert Sounder/Strobe with Electromechanical Tone V4R = 400 Series Speaker, Red SP1R = SP101 Series Speaker (Strobe), Red SP1W = SP101 Series Speaker (Strobe), White 15 = 15 cd, UL 1971 Strobe 1575 = 15 cd, UL 1971, 75 cd on axis 75 = 75 cd, UL 1971 Strobe 110 = 110 cd, UL 1971 Strobe Electrical Ratings – Strobe Only Average Operating Current In-rush Current in Average Operating Current Model Supply from Regulated Supply Excess of Peak Peak Operating from Full Wave Rectified, Red Beige Voltage Range (mA) Operating Current (mA) Current (mA) Unfiltered Supply (mArms)* SS2415ADA SS2415ADAB 20–30 VDC 75 0 180 90 SS241575ADA SS241575ADAB 20–30 VDC 93 0 220 120 SS2475ADA SS2475ADAB 20–30 VDC 170 0 400 200 SS24110ADA SS24110ADAB 20–30 VDC 210 0 500 245 SS1215ADA SS1215ADAB 12–14 VDC 170 0 380 200 SS121575ADA SS121575ADAB 12–14 VDC 225 0 560 270 * For additional information, see installation manual D900-01-00 Actual 12 volt operating voltage cannot be less than 9.6 VDC or greater than 15.4 VDC; actual 24 volt operating voltage cannot be less than 16 VDC or greater than 33 VDC System Sensor Worldwide Distribution In Canada: System Sensor Canada
6581 Kitimat Road, Unit #7
Mississauga, Ontario Canada L5N 3T5 Telephone: 905-812-0767 Fax: 905-812-0771 In the United Kingdom: System Sensor Europe, Ltd. Horsham Gates III, North St. Horsham, West Sussex RH13 5PJ, United Kingdom Telephone: 44-1403-276500 Fax: 44-1403-276501 In India: System Sensor India A-204 Maheshwari Nagar Orkay Mills Lane Andheri East, Mumbai 400093 Telefax: 91-022-8202564 In the Far East: System Sensor Pittway Far East, Ltd. Suite 706, New T&T Centre
7 Canton Road
Tsimshatsui, Kowloon, Hong Kong Telephone: 852-2730-9090 Fax: 852-2736-6580