Wall-Mount Horns, Strobes, and Horn/Strobes AUDIBLE/VISIBLE NOTIFICATION System Sensor’s SpectrAlert® wall-mount series includes a complete line of electronic horns, strobes, and horn/strobes. Intended for primary signaling use, SpectrAlert products meet UL1971, UL464, and Americans with Disabilities Act requirements. Technology. With its extremely efficient reflector design and Xenon flash tube, SpectrAlert offers current draw reductions as high as 40% over previous gener- ation designs. By consuming less current, the flexibility to connect more devices per loop is possible, for a lower installed cost. Installation. SpectrAlert products offer installation ease which also lowers the installed cost. By taking up no room in the back box, SpectrAlert strobes and horn/strobes make wiring connections simpler and faster. Each SpectrAlert includes a universal mounting plate for 4 ″ square and single gang back box mounting. Accessory mounting plates are also available for small footprint or surface mount applications. Flexibility. SpectrAlert offers the flexibility to meet a broad range of requirements. The SpectrAlert horns and horn/strobes feature a number of field-selectable/reversible horn tones. For visible requirements, SpectrAlert strobes and horn/strobes are available in a wide variety of configurations to address non-sleeping area, sleeping area, and corridor requirements. Offerings include 24-volt models at 15, 15/75, 30, 75, and 110 candela, and 12-volt devices at 15 and 15/75 candela. Aesthetics. To meet building owner aesthetic requirements, SpectrAlert incorporates a stylish, low profile design. And this aesthetic is consistent across all SpectrAlert wall-mount products. Models Available* Horn/Strobes P1215 P121575 P2415 P241575 P2430 P2475 P24110 Strobes S1215 S121575 S2415 S241575 S2430 S2475 S24110 Horns H12/24Product Overview Horn/Strobe Meet UL and ADA signaling requirements Lower current draw More devices per loop Lower installed cost Universal mounting plate included Accessory mounting plates available Field-selectable horn tones Electromechanical / 3kHz Temporal 3 / Non-temporal 3 High / Low dBA output Available in 15, 15/75, 30, 75, and 110 candela Synchronizable horns and strobes with Sync•Circuit ™ module Aesthetic design Strobe Horn Back Box Skirt *Refer to Ordering Information for other configurations

Walk Test SpectrAlert horn/strobe and horn only work on “walk tests” with time durations of 4 seconds or greater Input Terminals 12 to 18 AWG Dimensions Strobe and horn/strobe with universal plate 5″ x 5 5/8″ x 2 15/16″ Strobe and horn/strobe with small footprint plate Horn with universal mounting plate 5″ x 5 5/8″ x 1 5/16″ Horn without mounting plate 15/16″ x 55/16″ x 1 5/16″ Weight, horn only 7.2 oz. Weight, strobe and horn/strobe 8.8 oz. Mounting 4″ x 4″ x 11/2″ or 2″ x 4″ x 17/8″ standard boxes Indoor Operating Temperature 32°F to 120°F (0°C to 49°C) Maximum humidity 95% as tested per UL464 Weatherproof (horn and horn/strobes) Operating Temperature 32°F to 150°F (0°C to 66°C) (outdoor strobe only) –40°F to 158°F (–40°C to 70°C ) ULC Canadian Models –40°C to 66°C Voltages 12 or 24VDC and FWR unfiltered Operating voltage range* 12V: 10.5-17V; 24V: 20-30V Operating voltage range* (with Sync•Circuit module, MDL) 12V, 11-17V; 24V, 20-30V * These products should be operated within their rated voltage range; UL does, however, test functional integrity to -20% and +10% of manufacturer's stated ranges. U.S. Patent Numbers 5,593,569 5,914,665 6,049,446 Specifications Engineering Specifications General SpectrAlert horns, strobes and horn/strobes shall be capa- ble of mounting to a standard 4 ″ x 4″x 11/2″ back box or a single gang 2″ x 4″ x 17/8″ back box using the universal mounting plate included with each SpectrAlert product. Also, SpectrAlert products, when used in conjuction with the accessory Sync

  • Circuit Module, shall be pow- ered from a non-coded power supply and shall operate on 12 or 24 volts. 12 volt rated devices shall have an operating voltage range of 10.7–17 volts. 24-volt rated devices shall have an operating voltage range or 20–30 volts. SpectrAlert products shall have an operating tem- perature of 32° to 120°F and operate from a regulated DC or full wave rectified, unfiltered power supply. Horn Horn shall be a System Sensor SpectrAlert Model capable of operating at 12 and 24 volts. Horn shall be listed to UL 464 for fire protective signaling systems. The horn shall have two tone options, two audibility options (at 24 volts) and the option to switch between a temporal 3 pattern and a non-temporal continuous pattern. All horn models shall operate on a coded power supply. Strobe Strobe shall be a System Sensor SpectrAlert Model listed to UL 1971 and be approved for fire protective service. The strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appli- ances, flashing at 1Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn/Strobe Combination Horn/Strobe shall be a System Sensor SpectrAlert Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. Horn/strobe shall be wired as a primary signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two tone options, two audibility options (at 24 volts) and the option to switch between a temporal 3 pattern and a non-temporal continuous pattern. Strobes shall be powered independently of the sounder with the removal of factory installed jumper wires. The horn on horn/strobe models shall operate on a coded or non-coded power supply (the strobe must be powered continuously). Synchronization Module Module shall be a System Sensor Sync•Circuit listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1Hz and horns at temporal 3. Also, the module shall silence the horns on horn/strobe models, while operating the strobes, over a single pair of wires. The module shall be capable of mounting to a 4 11/16″ x 411/16″x 21/8″ back box and shall control two Style Y (class B) or one Style Z (class A) circuit. Module shall be capable of multiple zone synchronization by daisy chaining multiple modules together and re-synchronizing each other along the chain. The module shall not operate on a coded power supply.

Sound Output Guide (dBA) UL Reverberant Room dBA @ volts DC Anechoic Room Peak dBA @ 10ft./volts DC 10.5 12 17 20 24 30 10.5 12 17 20 24 30 Temporal Low Tone Electromechanical NA NA NA 75 75 79 NA NA NA 94 96 98

3000 HZ Interrupted NA NA NA 75 79 79 NA NA NA 94 96 98

High Tone Electromechanical 75 75 79 82 82 82 94 95 98 100 101 102

3000 HZ Interrupted 75 75 79 82 85 85 94 95 98 100 101 102

Non-Temporal Low Tone Electromechanical NA NA NA 79 82 85 NA NA NA 94 96 98

3000 HZ Interrupted NA NA NA 82 82 85 NA NA NA 94 96 98

High Tone Electromechanical 79 79 85 85 88 88 94 95 98 100 101 102

3000 HZ Interrupted 79 82 85 88 88 88 93 95 98 100 101 102

Average Current (mA) 12V Models 24V Models 10.5V 12V 17V 20V 24V 30V Candela DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR 15 133 159 114 157 81 128 50 61 43 60 38 60 15/75 168 182 142 171 99 150 56 65 49 64 44 62

30 NA NA NA NA NA NA 78 84 67 82 58 72

75 NA NA NA NA NA NA 145 170 123 159 102 141

110 NA NA NA NA NA NA 169 220 140 191 115 174

SpectrAlert Current Draw Table Strobe Only Horn Only Average Current (mA) 12V Models 24V Models High/Low Temp/ 10.5V 12V 17V 20V 24V 30V Tone Volume Non DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR Electro- High Temp 10 11 10 10 14 14 19 21 25 18 29 26 mech. Non 10 16 10 19 14 25 17 29 23 34 30 42 Low Temp NA NA NA NA NA NA 11 12 13 13 17 15 Non NA NA NA NA NA NA 12 16 14 19 17 24

3000 Hz High Temp 11 13 11 11 16 16 24 26 28 23 37 33

Interrupt. Non 11 17 11 21 14 28 19 34 27 39 35 45 Low Temp NA NA NA NA NA NA 14 14 17 15 21 19 Non NA NA NA NA NA NA 13 18 16 21 22 25 In Rush Current (mA) 12V Models 24V Models 10.5V 12V 17V 20V 24V 30V DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR 80 108 92 124 140 190 97 129 116 152 147 198 76 104 88 126 160 185 97 135 116 164 147 211 NA NA NA NA NA NA 97 129 116 152 147 198 NA NA NA NA NA NA 190 240 230 280 290 380 NA NA NA NA NA NA 190 230 220 290 290 370 Horn/Strobe 15 cd Average Current (mA) 12V Models 24V Models High/Low Temp/ 10.5V 12V 17V 20V 24V 30V Tone Volume Non DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR Electro- High Temp 143 170 124 167 95 142 69 82 68 78 67 87 mech. Non 143 170 124 167 95 142 67 90 66 94 68 103 Low Temp NA NA NA NA NA NA 61 73 56 73 55 76 Non NA NA NA NA NA NA 62 77 57 79 55 85

3000 Hz High Temp 144 172 125 168 97 144 74 87 71 83 75 94

Interrupt. Non 144 173 125 168 95 146 69 95 70 99 73 106 Low Temp NA NA NA NA NA NA 64 75 60 75 59 80 Non NA NA NA NA NA NA 63 79 59 81 60 86 Horn/Strobe 1575 cd Average Current (mA) 12V Models 24V Models High/Low Temp/ 10.5V 12V 17V 20V 24V 30V Tone Volume Non DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR Electro- High Temp 178 193 152 181 113 164 75 86 74 82 73 88 mech. Non 178 193 152 181 113 164 73 94 72 98 74 104 Low Temp NA NA NA NA NA NA 67 77 62 77 61 77 Non NA NA NA NA NA NA 68 81 63 83 61 86

3000 Hz High Temp 179 195 152 183 115 166 80 91 77 87 81 95

Interrupt. Non 179 196 152 183 113 168 75 99 76 103 79 107 Low Temp NA NA NA NA NA NA 70 79 66 79- 65 81 Non NA NA NA NA NA NA 69 83 65 85 66 87 Horn/Strobe 30 cd Average Current (mA) 24V Models High/Low Temp/ 20V 24V 30V Tone Volume Non DC FWR DC FWR DC FWR Electro- High Temp 97 105 92 100 87 98 mech. Non 95 113 90 116 88 114 Low Temp 89 96 80 95 75 87 Non 90 98 81 101 75 96

3000 Hz High Temp 102 108 95 105 95 105

Interrupt. Non 97 116 94 121 93 117 Low Temp 92 96 84 97 79 91 Non 91 100 83 103 80 97 Horn/Strobe 75 cd Average Current (mA) 24V Models High/Low Temp/ 20V 24V 30V Tone Volume Non DC FWR DC FWR DC FWR Electro- High Temp 164 191 148 167 131 167 mech. Non 163 188 146 169 132 169 Low Temp 156 182 136 162 119 156 Non 157 182 137 162 119 157

3000 Hz High Temp 169 196 151 172 139 174

Interrupt. Non 164 192 150 175 137 177 Low Temp 159 184 140 164 123 160 Non 158 188 139 163 124 162 Horn/Strobe 110 cd Average Current (mA) 24V Models High/Low Temp/ 20V 24V 30V Tone Volume Non DC FWR DC FWR DC FWR Electro- High Temp 188 241 165 209 144 200 mech. Non 186 238 163 211 145 202 Low Temp 180 232 153 204 132 189 Non 181 232 154 204 132 190

3000 Hz High Temp 193 246 168 214 152 207

Interrupt. Non 188 242 167 217 150 210 Low Temp 183 234 157 206 136 193 Non 182 232 156 205 137 195 Peak Current (mA) 12V Models 24V Models 10.5V 12V 17V 20V 24V 30V DC FWR DC FWR DC FWR DC FWR DC FWR DC FWR 460 460 450 460 420 480 135 204 135 208 135 185 490 520 490 520 460 480 150 199 150 207 150 198 NA NA NA NA NA NA 183 201 183 219 183 216 NA NA NA NA NA NA 350 440 340 460 330 480 NA NA NA NA NA NA 460 560 450 570 420 620

Avg. mA* Avg. mA* Red White Voltage Candela @Nom. VDC @Nom.FWR** Horn/Strobes P1215 P1215W 12 15 124 167 P121575 P121575W 12 15/75 152 181 P2415 P2415W 24 15 68 78 P241575 P241575W 24 15/75 74 82 P2430 P2430W 24 30 92 100 P2475 P2475W 24 75 148 167 P24110 P24110W 24 110 165 209 P121575K (weatherproof) — 12 15/75 124 167 P241575K (weatherproof) — 24 15/75 74 82 P2475K (weatherproof) — 24 75 148 167 P24110K (weatherproof) — 24 110 165 209 P241575P (no lettering) P241575PW 24 15/75 74 82 P241575AG (AGENT) — 24 15/75 74 82 P241575EV (EVAC) — 24 15/75 74 82 Canada P2415A P2415WA 24 15 68 78 P241575A P241575WA 24 15/75 74 82 P2475A P2475WA 24 75 148 167 P24110A P24110WA 24 110 165 209 P241575KA (weatherproof) — 24 15/75 74 82 P2475KA (weatherproof) — 24 75 148 167 P24110KA (weatherproof) — 24 110 165 209 Latin America P241575F (FUEGO) — 24 15/75 74 82 Strobes S1215 S1215W 12 15 114 157 S121575 S121575W 12 15/75 142 171 S2415 S2415W 24 15 43 60 S241575 S241575W 24 15/75 49 64 S2430 S2430W 24 30 67 82 S2475 S2475W 24 75 123 159 S24110 S24110W 24 110 140 191 S121575K (weatherproof) — 12 15/75 142 171 S241575K (weatherproof) — 24 15/75 49 64 S2475K (weatherproof) — 24 75 123 159 S24110K (weatherproof) — 24 110 140 191 S241575P (no lettering) S241575PW 24 15/75 49 64 S241575AG (AGENT) — 24 15/75 49 64 S241575EV (EVAC) — 24 15/75 49 64 Canada S2415A S2415WA 24 15 43 60 S241575A S241575WA 24 15/75 49 64 S2475A S2475WA 24 75 123 149 S24110A S24110WA 24 110 140 191 S241575KA (weatherproof) — 24 15/75 49 64 S2475KA (weatherproof) — 24 75 123 149 S24110KA (weatherproof) — 24 110 140 191 Latin America S241575F (FUEGO) — 24 15/75 49 64 Horns H12/24 H12/24W 12/24 NA 10/25 10/18 H12/24K (weatherproof) — 12/24 NA 10/25 10/18 Canada HC12/24A HC12/24WA 12/24 NA 10/25 10/18 HC12/24KA — 12/24 NA 10/25 10/18 Sync•Circuit MDL MDLW 12/24 NA 10/11 12/15 Module Canada MDLA MDLWA 12/24 NA 10/11 12/15 Small Footprint Mounting Plate for Single Gang Only S-MP S-MPW NA NA NA NA Surface Mount Back Box Skirt BBS BBSW NA NA NA NA Universal Mounting Plate (replacement) D-MP D-MPW NA NA NA NA Weatherproof Back Box WBB — NA NA NA NA Notes: Agency Listings – Indoor models: UL, ULC, FM, CSFM, MEA. Weatherproof models: UL, CSFM (strobe only), MEA, ULC. All of these SpectrAlert products are designed for wall mount only. All weatherproof models must use weatherproof back box model WBB. Installation of less than 75 can- dela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.2). However, it is the responsibility of the person or entity designing the fire alarm system to determine the acceptability of less than 75 candela strobes. All 15/75 candela strobes or horn/strobes are recommended for 20′× 20′ rooms or less. *Horn and horn/strobe current draws assume horn is set at temp 3, electromechanical tone and high audibility. ** FWR = Full Wave Rectified SpectrAlert Ordering Information System Sensor Sales and Service System Sensor Headquarters

3825 Ohio Avenue

St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 Documents-on-Demand 800/736-7672 x3 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor Europe Ph: 44.1403.276500 Fx: 44.1403.276501 System Sensor in China Ph: 86.29.524.6253 Fx: 86.29.524.6259 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor – Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor – Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor – India Ph: 91.124.637.1770 x.2700 Fx: 91.124.637.3118 © 2002 System Sensor. The company reserves the right to change product specifications without notice. A05-0936-010•9/02•#1002