Diversified Electronics 800.727.5646 atcdiversified.com SPECIFICATIONS VOLTAGE TRIP Drop-Out ±10% of Setting POINTS Pick-Up ± 7% of Setting FREQUENCY TRIP Drop-Out ±4% of 60 Hz (380 V , 50 Hz) POINTS Pick-Up ±3% of 60 Hz (380 V , 50 Hz) UNBALANCE TRIP Drop-Out 7% POINTS Pick-Up 5% RESET Automatic; Manual; Automatic with Memory* PHASE SEQUENCE ABC (Will Not Operate CBA) OUTPUT RATING DPDT, 360 VA Inductive; 1/2 hp

3 A Resistive @ 600 VAC

SLM (120, 230) ASE - DPDT, 470 VA 10A Resistive@240VAC TERMINATIONS #8-32 Screw Terminals INDICATORS Designation Color State Condition LED* Time Delay Green Flashing Timing Output Normal ON Energized Under Voltage Red ON Fault Over Voltage Red ON Fault Phase Sequence, Red ON Fault Shift Frequency Shift Red ON Fault Unbalance Red ON Fault Operate Sampling 2 SEC Reset Delay (Sampling Delay) + (1.5 seconds to 5 minute Delay) Adjustable in one (1) minute increments Release Under Voltage 1.5 SEC, (approx.) Over Voltage 1.5 SEC, (approx.) Frequency Shift 1.5 SEC, (approx.) Unbalance 2.0 SEC, (approx.) *Phase 1.0 SEC, (approx.) Loss/Shift TEMPERATURE Operate 32° to +131°F (0° to +55°C) RATING Storage -49° to 185°F (-45° to +85°C) POWER REQUIRED 7 VA Typical TRANSIENT 2500 Volts for 10 ms PROTECTION ENCLOSURE Lexan Surface Mounted WEIGHT 22 oz.

  • Models available up to 690 VAC
  • Automatic or Manual Reset
  • Delay-on-Make Timer
  • LED Indicators for Fault Conditions
  • Last Fault Memory SCREWDRIVER ADJUSTMENT FOR:
  • Time Delay
  • Voltage
  • Mode of Operation PROTECTS 3-PHASE EQUIPMENT AGAINST:
  • Under Voltage
  • Over Voltage
  • Phase Loss
  • Phase Reversal
  • Phase Unbalance
  • Phase Shift
  • Frequency Shift *Automatic with Memory MODE: The last fault is indicated and remains on when condi- tions return to normal. The indicator extinguishes only with reset or when new fault condition occurs. PHASE VOLTAGE MONITORS SLM Series Microprocessor Based 3-Phase Monitor IND. CONT . EQ. 496Y DIMENSIONS (INCHES) WIRING NOMINAL MODEL PHASE-TO-PHASE MAXIMUM NUMBER VOLTAGE SET POINTS VOLTAGE SLM-120-ASE 105, 110, 115, 120, 125, 130 143 VAC SLM-230-ASE 200, 210, 220, 230, 240, 250 275 VAC SLM-380-ASE 350, 365, 380, 390, 400, 415 457 VAC SLM-440-ASE 440, 450, 460, 470, 480, 490 540 VAC SLM-575-ASE 525, 550, 575, 600 690 VAC *Automatic with Memory MODE: The last fault is indicated and remains on when conditions return to normal. The indicator extinguishes only with reset or when new fault condition occurs. The SLM Series is UL Listed under UL File Number E55826.