Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 1
Technical content
The CMU Series is used to detect UNDER CURRENT conditions. The internal relay is energized (Pick-up) when the monitored current is above the preset trip point. The relay de-energizes (Drop-out) when the current falls below the trip point for longer than the adjustable delay. The delay is incorporated to prevent nuisance tripping caused by momentary line dips. The relay re-energizes when the current rises 5% above the Drop-out trip point for longer than 0.1 seconds. The relay has the automatic reset feature. An external CT may be used to extend the range of the Current Monitor. DIMENSIONS (INCHES) WIRING SPECIFICATIONS CONTROL VOLTAGE 24 or 120 VAC/DC; 50/60 Hz TRIP POINTS Pick-up 5% above Drop-out Drop-out See order information OUTPUT DPDT, 10 Amp @ 120 VAC Resistive HYSTERESIS 5% RESPONSE TIME Operate 0.1 SEC Release 0.1 to 5 SEC, Adjustable INDICATORS Glows When Current is Above Preset Current Trip Point (Style E Enclosure Only) RESET Automatic TEMPERATURE Operate 32° to 131°F (0° to +55°C) RATING Storage -49° to 185°F (-45° to +85°C) ENCLOSURE Style A Lexan Dust Cover; 11-pin Plug-in Style E Lexan Surface Mounted: #8-32 Screw Terminals SOCKET RB-11 Socket for Style A. WEIGHT Style A 5 oz. Style E 10.5 oz. CURRENT MONITORS MODEL NUMBER CMU A S CONTROL VOLTAGE
24 VAC/DC; 50/60 Hz 24
120 VAC/DC; 50/60 Hz 120
0.05 to 0.25 amp adj. .25 0.2 to 1 amp adj. 1 1.0 to 5.0 amps adj. 5 2.0 to 10 amps adj. 10 4.0 to 20 amps adj. (E Housing Only) 20 MODEL NUMBER