2W-B SYSTEMSENSOR | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

Features

Plug-in detector line, mounting base included Large wire entry port In-line terminals with SEMS screws Mounts to octagonal and single-gang backboxes, 4-square backboxes, or direct to ceiling Stop-Drop ’N Lock attachment to base Removable detector cover and chamber Built-in remote maintenance signaling Drift compensation and smoothing algorithms Simplified sensitivity measurement Wide angle, dual color LED indication Loop testing via EZ Walk feature Built-in test switch Installation ease. The i3 line redefines installation ease with its plug-in design. This allows an installer to pre-wire the bases included with the heads. The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods, as well as direct mounting with drywall anchors. To complete the installation, i3 heads plug in to the base with a simple Stop-Drop ’N Lock™ action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the i3 line to minimize nuisance alarms. Two-wire i3 detectors needing cleaning can generate a remote maintenance signal, when connected to the 2W-MOD2 loop test/maintenance module, or to a panel equipped with the i3 protocol. This signal is indicated by LEDs located at the module and the panel. The SENS-RDR, a wireless device, displays the sensitivityof i3 detectors in terms of percent per-foot-obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector’s condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on two-wire i3 detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector. 2093290-01-E7272-1209:2103011446S911

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2006 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0318-006 • 7/06 • #1676

Ordering Information

Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max. limited by control panel 2WT-B Yes 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 mA @ 12V, 23mA @ 24V 4WT-B Yes 4-wire 20 mA @ 12V, 23mA @ 24V Accessories 2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 in. (16.76cm) diameter Smoke Detector Specifications Architectural/Engineering Specifications Smoke detector shall be a System Sensor i3 Series model number_______, listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C). The detector shall include a mounting base for mounting to 3½-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws. The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shall provide dual color LED indication which blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel, and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24V non-polarized Minimum: 8.5V Maximum: 35V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 µA maximum average; 4-wire: 50 µA maximum average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12V, 23mA @ 24V Peak Standby Current 2-wire: 100 µA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30V AC/DC Physical Specifications Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz. (178 grams) Operating Temperature Range 2W-B and 4W-B: 32°F–120°F (0°C–49°C); 2WT-B and 4WT-B: 32°F–100°F (0°C–37.8°C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135°F (57.2°C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41°F (5°C) Sensitivity 2.5%/ft. nominal Input Terminals 14–22 AWG Mounting 3½-inch octagonal back box 4-inch octagonal back box Single gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Modes Power Up Sequence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid