Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 - giacomini.com Versions and product codes SERIES PRODUCT CODE CONNECTIONS MANIFOLD x OUTLETS N. OF OUTLETS R583S Delivery manifolds with regulation lockshields R583SY112 G 1” x 3/4”E R583SY113 3 R583SY114 4 R583M Delivery manifolds with flow meters R583MY112 G 1” x 3/4”E R583MY113 3 R583MY114 4 R583V Return manifolds with handwheel R583VY112 G 1” x 3/4”E R583VY113 3 R583VY114 4 R583S, R583M, R583V Datasheet 1110EN 02/2024 Modular delivery and return manifolds Brass modular manifolds for HVAC systems, available in three versions:
- R583S delivery manifolds with balancing lockshields.
- R583M delivery manifolds with flow meters (dual-scale: 0,5÷5 l/min and 0,15÷1,5 GPM) with fluid regulation/shutting off.
- R583V return manifolds with shut-off valves with handwheel, preset for thermo-electric actuator. Metal supports, end pieces, ball valves and metal cabinet to complete the manifold are available on request. R583M R583S R583V
Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 - giacomini.com Optional
- R500-1: metal cabinet for flush-mount installation, 110÷120 mm adjustable depth
- R500-2: metal cabinet for flush-mount installation, 85÷130 mm adjustable depth
- P583Y001: metal support with plastic clip
- R859: chrome-plated brass shut-off ball valve with female-male tail piece
- R554B-1: manifold end piece, female thread, with automatic air vent valve and drain cock
- R554C-1: manifold end piece, female thread, with manual air vent valve and drain cock
- R473: normally-closed thermo-electric actuator, 2-conductor wire, IP40, 2,5 W
- R473M: normally-closed thermo-electric actuator, 4-conductor wire, with stroke-end microswitch, IP40, 2,5 W
- R473E: normally-closed thermo-electric actuator, 2-conductor wire, IP54, 1 W R473ER473 / R473M R583V R583M R859 R859 RED BLUE R554B-1 R554C-1 R500-1 R500-2 P583Y001P583Y001 R583S
Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 - giacomini.com Technical data R583V
- Fluids: water, glycol-based solutions (max 30 %)
- Temperature range: 5÷110 °C
- Max working pressure: 10 bar
- Center distance between outlets: 50 mm
- Shut-off valves with handwheel, preset for thermo-electric actuator after installation of the appropriate ring nut adaptor Materials
- Manifolds: UNI EN 12165 CW617N brass
- Self-sealing gaskets: EPDM R583M
- Fluids: water, glycol-based solutions (max 30 %)
- Temperature range: 5÷70 °C
- Max working pressure: 6 bar (10 bar for system testing)
- Center distance between outlets: 50 mm
- Dual-scale flow meters (0,5÷5 l/min and 0,15÷1,5 GPM) with fluid regulation/shutting off Losses of pressure 10 100100 1000Q [l/h] 100 1000 10000 ∆p [mm H2O] 1,0 10,0 100 ∆p [KPa] 0,01 0,1 1,0 ∆p [bar] F.O. N. of turns of the flow meter ring nut F. O. Kv 0,83 R583S
- Fluids: water, glycol-based solutions (max 30 %)
- Temperature range: 5÷110 °C
- Max working pressure: 10 bar
- Center distance between outlets: 50 mm
- Balancing lockshields adjustable with 5-mm Allen Wrench (not included in the package) Losses of pressure 10 100100 1000Q [l/h] 100 1000 10000 ∆p [mm H2O] 1,0 10,0 100 ∆p [KPa] 0,01 0,1 1,0 ∆p [bar] 1 2 F.O. N. of turns of the lockshield 1 2 3 4 5 F. O. Kv 0,56 0,78 1,10 1,33 1,37 1,44
Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 - giacomini.com Regulating the system circuits 1 2 3 Regulating R583M delivery manifolds The individual circuits must be regulated through the flow meters which also work as regulation lockshields. To do so, follow the steps below: 1) Remove the red protection cap; 2) Manually turn in counterclockwise direction the black ring nut at the base of the flow meter to open the circuit or in clockwise direction to close it; the desired flow rate value is shown on the graduated scale of the flow meter; 3) Replace the red protection cap once the circuit has been regulated. Regulating R583S delivery manifolds The individual circuits must be regulated through the balancing lockshields. To do so, follow the steps below: 1) Turn the lockshield all the way through in clockwise direction using a 5-mm Allen Wrench; 2) Turn the lockshield in counterclockwise direction till reaching the desired balancing value (which can be deduced from the diagram “Losses of pressure”). CLOSING OPENING 5 mm CLOSING OPENING 5 mm Installation The modular delivery and return manifolds, available with 2 or 4 outlets, are provided disassembled. To connect them, screw one manifold to the other as far as it will go. Then it’s possible to unscrew the manifold up to a maximum of 45° (1/8 turn) until the indicator notches stamped on the manifold are perfectly aligned. The O-Ring on male thread, ensures proper sealing with no need to use hemp or PTFE. WARNING. Installation must be carried out by qualified operators according to the instructions provided. WARNING. Before assembling the manifolds, lubricate the EPDM O-Ring with an appropriate lubricant. O-Ring O-Ring 45° A A A A
Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 - giacomini.com Regulating R583V return manifolds The individual circuits on the return outlets can be regulated by turning the red handwheel to open the water port or by installing thermo-electric actuators. 15° R473 R473M PUSH “TAK” CLICK 15° R473 R473M PUSH “TAK” CLICK 15° R473 R473M PUSH “TAK” CLICK 15° R473 R473M PUSH “TAK” CLICK To install the R473/R473M normally-closed thermo-electric actuators, follow the steps below: 1) Remove the handwheel and place the ring nut included in the actuator package; 2) Press the thermo-electric actuator on the ring nut so as to assemble it properly; 3) Turn the thermo-electric actuator in clockwise direction by approx. 15° till it clicks into position (max tightening torque 5 Nm). To remove the thermo-electric actuator turn it by 15° in counterclockwise direction; 4) Push the red block button inwards and wire the thermo-electric actuator carefully following the diagram of the instructions provided. To install R473E normally-closed thermo-electric actuators, follow the steps below: 1) Remove the handwheel and place the ring nut included in the actuator package; 2) Press the thermo-electric actuator on the ring nut so as to assemble it properly; 3) Wire the actuator carefully following the diagram of the instructions provided. R473E CLICK R473E CLICK R473E CLICK
Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia consulenza.prodotti@giacomini.com +39 0322 923372 - giacomini.com Dimensions SERIES PRODUCT CODE N. OF OUTLETS A B C D [mm] E [mm] F [mm] G [mm] H [mm] I [mm] R583S R583SY112 2 G 1”M G 1”F 3/4”E 32 50 32 114 65 wr.37R583SY113 3 164 R583SY114 4 214 R583M R583MY112 2 G 1”M G 1”F 3/4”E 32 50 32 114 114 wr.37R583MY113 3 164 R583MY114 4 214 R583V R583VY112 2 G 1”M G 1”F 3/4”E 32 50 32 114 79 wr.37R583VY113 3 164 R583VY114 4 214 A B H CD E G F I R583S A B H CD E G F I R583M A B H CD E G F I R583V Product specifications R583S Modular delivery manifold with balancing lockshields for HVAC systems. Connections: G 1” x 3/4”E. Available with 2, 3 or 4 outlets. Center distance between outlets 50 mm. Temperature range: 5÷110 °C. Max working pressure: 10 bar. Body: UNI EN 12165 - CW617N brass; EPDM self-sealing gaskets. R583M Modular delivery manifold with flow meters (dual-scale: 0,5÷5 l/min and 0,15÷1,5 GPM) with fluid regulation/shutting off, for HVAC systems. Connections: G 1” x 3/4”E. Available with 2, 3 or 4 outlets. Center distance between outlets 50 mm. Temperature range: 5÷70 °C. Max working pressure: 6 bar (10 bar for system testing). Body: UNI EN 12165 - CW617N brass; EPDM self-sealing gaskets. R583V Modular return manifold with shut-off valves and handwheel, preset for thermo-electric actuator, for HVAC systems. Connections: G 1” x 3/4”E. Available with 2, 3 or 4 outlets. Center distance between outlets 50 mm. Temperature range: 5÷110 °C. Max working pressure: 10 bar. Body: UNI EN 12165 - CW617N brass; EPDM self-sealing gaskets. Package Disposal. Carton boxes: paper recycling. Plastic bags and bubble wrap: plastic recycling. Product Disposal. Do not dispose of product as municipal waste at the end of its life cycle. Dispose of product at a special recycling platform managed by local authorities or at retailers providing this type of service. Safety Warning. Installation, commissioning and periodical maintenance of the product must be carried out by qualified operators in compliance with national regulations and/or local standards. A qualified installer must take all required measures, including use of Individual Protection Devices, for his and others’ safety. An improper installation may damage people, animals or objects towards which Giacomini S.p.A. may not be held liable. Additional information. For more information, go to giacomini.com or contact our technical at any time, without notice and for technical or commercial reasons, the items included herewith. The information included in this technical sheet do not exempt the user from strictly complying with the rules and good practice standards in force.