R401PX232 GIACOMINI | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
ValVes with thermost a tic option for radia tors, with presetting R401PTG R402PTG R415PTG R403PTG R411PTG R412PTG Versions and codes All versions are interchangeable with TG-series body valves Series Product code Connections Type R401PTG R401PX232 3/8” x 3/8” Iron pipe AngleR401PX233 1/2” x 1/2” R401PX234 3/4” x 3/4” R402PTG R402PX232 3/8” x 3/8” StraightR402PX233 1/2” x 1/2” R402PX234 3/4” x 3/4” R403PTG R403PX252 3/8” x 3/8” (LEFT) Double angle R403PX254 1/2” x 1/2” (LEFT) R403PX262 3/8” x 3/8” (RIGHT) R403PX264 1/2” x 1/2” (RIGHT) R403PX224 1/2” x 18 mm (LEFT) Adaptor for copper, plastic, multilayer pipe R403PX234 1/2” x 18 mm (RIGHT) R411PTG R411PX232 3/8” x 16 mm Angle R411PX233 1/2” x 16 mm R412PTG R412PX232 3/8” x 16 mm Straight R412PX233 1/2” x 16 mm R415PTG R415PX242 1/2” x 16 mm Reverse angle
Description
The PTG valves with thermostatic option and presetting are used to slice the delivery water flow rate in a radiator. When the special worksite protection handwheel is fully closed, it is possible to exceed static pressure values of 10 bar with the system disabled. In any case, it is advised to connect the heating elements before carrying out the pressurised seal tests on the system. LEFT version: frontal thermostatic head connection and supply from below; valve to the left of the radiator. RIGHT version: frontal thermostatic head connection and supply from below; valve to the right of the radiator. Spare parts
- P12AX006: spare parts kit (bonnet, numbered ring, regulation key, instrucion) for PTG series valves.
ValVes with thermost a tic option for radia tors, with presetting Valve presetting PTG valves are equipped with a special bonnet (P12AX006) which determines a specific flow section based on the position set, thus generating the desired pressure losses within the hydraulic circuit. These valves can be pre-set to efficiently balance the circuit. By combining them with radiator thermostatic heads and chronothermostats they offer great energy saving. The bonnet has a numbered bush: position 0,5 (single notch) - 1 - 2 - 3 - 4 - 5 - 6 - 7 - N (fully open). To make the presetting, proceed as follows: Note. To adjust the flow rate of the valve, use the R73PY010 key. 1 Remove the red worksite protection using a screwdriver. The stem “B” is positioned on N (fully open). A BB N 654 3 3 N 654 N
2 Set the R73PY010 key on the bonnet stem, fitting it in the only position
allowed (letter “N” visible from the slot of R73PY010 key and facing the reference “A” on the valve body). A BB N 654 3 3 N 654 N
3 Turn the bonnet stem using the key R73PY010 until the desired presetting
number number appears from the slot of the key. A BB N 654 3 3 N 654 N
4 Remove the key R73PY010, the stem “B” will be on the desired presetting
position, marked by the number on the valve ring. Adjustment positions 0,5 (single notch) - 1 - 2 - 3 - 4 - 5 - 6 - 7 - N (fully open). A BB N 654 3 3 N 654 N Technical data
- Temperature range: 5÷110 °C
- Max. working pressure: 16 bar (with thermostatic head or thermo-electric actuator: 10 bar)
- Maximum differential pressure: 1,4 bar Losses of Pressure The diagrams show the values of the loss of pressure in straight and angled valves with thermostatic heads ∆t = 2 °C. R401PTG - R402PTG - R411PTG - R412PTG ∆p [mm H20] 1000 100 Q [l/h] 100 100010 5 6 N710,5 2 3 4 Regulation position 0,5 1 2 3 4 5 6 7 N Kv 0,08 0,15 0,17 0,20 0,22 0,26 0,31 0,35 0,41 R403PTG ∆p [mm H20] 1000 100 Q [l/h] 100 100010 5 6 N71 2 3 40,5 Regulation position 0,5 1 2 3 4 5 6 7 N Kv 0,08 0,18 0,22 0,24 0,28 0,33 0,45 0,50 0,54 R415PTG ∆p [mm H20] 1000 100 Q [l/h] 100 100010 5 6 N71 2 3 40,5 Regulation position 0,5 1 2 3 4 5 6 7 N Kv 0,08 0,10 0,16 0,20 0,24 0,28 0,35 0,44 0,76
ValVes with thermost a tic option for radia tors, with presetting
3 Unscrew the valve bonnet by turning the R400 Allen key with a 6 mm
Allen spanner. Push the stem slightly while performing this step to prevent the bonnet from detaching. Refer to the R400 Allen key instructions. 6 mm A R400 D EA C B 5 mm
4 Tighten the “D” ball valve using a 5 mm Allen spanner, purge the water
from the “E” drain and remove the R400 Allen key stem together with the bonnet to be replaced. Refer to the R400 Allen key instructions. 6 mm A R400 D EA C B 5 mm
5 Remove the P12AX006 bonnet and reassemble it inside the valve in
reverse order. Once completed this step, reassemble the numbered ring on the valve paying attention to the position of the numbers: the letter “N” must face the radiator. Now is possible to make the new presetting as described in the paragraph “Valve presetting” . 6 mm A R400 D EA C B 5 mm Replacement of P12AX006 bonnet Warning. With thermostatic head installed on the valve body, to avoid excessive loads on the seal gasket of the thermostatic bonnet (with the resulting risk of jamming and locking) during the summer, it is recommended to place the handwheel of the thermostatic head in the fully open position, marked by the symbol . R400 In case of malfunction of the bonnet (P12AX006) is possible to replace it, using the appropriate key R400. To replace the bonnet, proceed as follows: 1 Remove the *A* numbered ring using pliers for elastic rings (seeger). 6 mm A R400 D EA C B 5 mm 2 Move the “B” stem of the R400 Allen key about half the way back. Fit the “C” plastic threaded ring connecting it to the valve body pins. Screw the R400 Allen key on the ring nut and install the valve bonnet with the R400 stem, fitting it in correct position. Refer to the R400 Allen key instructions. 6 mm A R400 D EA C B 5 mm
ValVes with thermost a tic option for radia tors, with presetting Dimensions Connection Product code GxB H [mm] I [mm] I’ [mm] J [mm] K [mm] L [mm] L’ [mm] M [mm] W [mm] Iron pipe R401PX232 3/8” x 3/8” 55 51 - 20 22 64 - 23 27 R401PX233 1/2” x 1/2” 59 53 - 23 27 68 - 23 30 R401PX234 3/4” x 3/4” 61 61 - 25 32 79 - 23 38 R402PX232 3/8” x 3/8” 58 54 - 15 22 76 - 23 27 R402PX233 1/2” x 1/2” 60 55 - 17 27 82 - 23 30 R402PX234 3/4” x 3/4” 65 56 - 21 32 82 - 23 38 R403PX252 3/8” x 3/8” (LEFT) 43 50 57 27 27 65 71 23 30 R403PX254 1/2” x 1/2” (LEFT) 43 50 57 27 27 65 71 23 30 R403PX262 3/8” x 3/8” (RIGHT) 43 50 57 27 27 65 71 23 30 R403PX264 1/2” x 1/2” (RIGHT) 43 50 57 27 27 65 71 23 30 Adaptor for copper, plastic, multilayer pipe R411PX232 3/8” x 16 mm 57 53 - 21 - 66 - 23 30 R411PX233 1/2” x 16 mm 57 53 - 21 - 66 - 23 30 R412PX232 3/8” x 16 mm 61 51 - 17 - 75 - 23 30 R412PX233 1/2” x 16 mm 61 51 - 17 - 75 - 23 30 R403PX224 1/2” x 18 mm (LEFT) 41 50 58 24 - 63 71 23 30 R403PX234 1/2” x 18 mm (RIGHT) 41 50 58 24 - 63 71 23 30 R415PX242 1/2” x 16 mm 53 45 - 36 - 95 - 23 30 R401PTG R402PTG R403PTG I B L W K H G J M M WK H B G J I L W B G H J I B L M J W H ADAPTOR CONNECTION M H H G I B L B J J W W K K IRON CONNECTION R411PTG R412PTG R415PTG M W G H J I B L B W M H G J I L W G H J I B L M
ValVes with thermost a tic option for radia tors, with presetting Product specifications R401PTG Valve with thermostatic option and presetting, angled, chrome-plated, with iron pipe connection. Body in brass UNI EN 12165 CW617N. Worksite protection pressure 16 bar (10 bar with thermostatic head or thermo-electric actuator). R402PTG Valve with thermostatic option and presetting, straight, chrome-plated, with iron pipe connection. Body in brass UNI EN 12165 CW617N. Worksite protection pressure 16 bar (10 bar with thermostatic head or thermo-electric actuator). R403PTG Valve with thermostatic option and presetting, double angled, chrome-plated, with iron pipe connection or connection for adaptor for copper / plastic / multilayer pipe. Body in brass UNI EN 12165 CW617N. Worksite protection handwheel in PP-H. Monobloc command stem in stainless steel. Seal on command stem with O-Ring in EPDM. Temperature range 5÷110 °C. Max. working pressure 16 bar (10 bar with thermostatic head or thermo-electric actuator). R411PTG Valve with thermostatic option and presetting, angled, chrome-plated, with connection for adaptor for copper / plastic / multilayer pipe. Body in brass UNI EN 12165 CW617N. Worksite protection handwheel in PP-H. Monobloc command stem in stainless steel. Seal on command stem with O-Ring in EPDM. Temperature range 5÷110 °C. Max. working pressure 16 bar (10 bar with thermostatic head or thermo-electric actuator). R412PTG Valve with thermostatic option and presetting, straight, chrome-plated, with connection for adaptor for copper / plastic / multilayer pipe.Body in brass UNI EN 12165 CW617N. Worksite protection handwheel in PP-H. Monobloc command stem in stainless steel. Seal on command stem with O-Ring in EPDM. Temperature range 5÷110 °C. Max. working pressure 16 bar (10 bar with thermostatic head or thermo-electric actuator). R415PTG Valve with thermostatic option and presetting, reverse angled, chrome-plated, with connection for adaptor for copper / plastic / multilayer pipe. Body in brass UNI EN 12165 CW617N. Worksite protection handwheel in PP-H. Monobloc command stem in stainless steel. Seal on command stem with O-Ring in EPDM. Temperature range 5÷110 °C. Max. working pressure 16 bar (10 bar with thermostatic head or thermo-electric actuator).
ValVes with thermost a tic option for radia tors, with presetting Additional information For more information, go to www.giacomini.com or contact our technical assistance service: ' +39 0322 923372 6 +39 0322 923255 * consulenza.prodotti@giacomini.com The information included in this technical sheet do not exempt the user from strictly complying with the rules and good practice standards in force. Giacomini S.p.A. Via per Alzo, 39 - 28017 San Maurizio d’Opaglio (NO) Italy