Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia  consulenza.prodotti@giacomini.com  +39 0322 923372 - giacomini.com R140D Datasheet 0427EN  01/2022 Safety valve INAIL compliant  Versions and product codes PRODUCT CODE CONNEC- TIONS CALIBRATION PRESSURE [bar] R140DY104 G 1/2”F x G 3/4”F 2,25 R140DY105 2,5 R140DY106 2,7 R140DY107 3 R140DY109 3,5 R140DY110 4 R140DY111 4,5 R140DY112 5 R140DY113 5,4 R140DY115 6 R140DY117 7 R140DY119 8 PRODUCT CODE CONNEC- TIONS CALIBRATION PRESSURE [bar] R140DY124 G 3/4”F x G 1”F 2,25 R140DY125 2,5 R140DY126 2,7 R140DY127 3 R140DY129 3,5 R140DY130 4 R140DY131 4,5 R140DY132 5 R140DY133 5,4 R140DY135 6 R140DY137 7 R140DY139 8 PRODUCT CODE CONNEC- TIONS CALIBRATION PRESSURE [bar] R140DY144 G 1”F x G 1-1/4”F 2,25 R140DY145 2,5 R140DY146 2,7 R140DY147 3 R140DY149 3,5 R140DY150 4 R140DY151 4,5 R140DY152 5 R140DY153 5,4 R140DY155 6 R140DY157 7 R140DY159 8 PRODUCT CODE CONNEC- TIONS CALIBRATION PRESSURE [bar] R140DY164 G 1-1/4”F x G 1-1/2”F 2,25 R140DY165 2,5 R140DY166 2,7 R140DY167 3 R140DY169 3,5 R140DY170 4 R140DY171 4,5 R140DY172 5 R140DY173 5,4 R140DY175 6 R140DY177 7 R140DY179 8  WARNING: PRODUCT INSTALLATION IN ELECTRICAL OR ELECTRONIC EQUIPMENT (EEE) The product can be installed only if the EEE - Electrical and / or Electronic Equipment - is excluded or not falling within the scope of Directive 2011/65/EU according to the provisions at point e) of par. 4 of art. 2 of the Directive itself, as a product intended for large fixed installations. 0100 The R140D safety valves are used in hot water thermal systems with a closed expansion tank, to ensure that the pressure of the fluid in the heat generator does not exceed the project limits. The valves comply with Directive “PED” 2014/68/EU, and are calibrated and approved by INAIL (in accordance with “R” collection - Technical application specifications of Title II of Ministerial Decree 1.12.75 - Italy).  CONFORMITY DECLARATION Frame the QR code with your smartphone or tablet to view the conformity declaration.

Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia  consulenza.prodotti@giacomini.com  +39 0322 923372 - giacomini.com  Technical data Performance

  • Fluids: hot water, air
  • Nominal pressure: 10 bar
  • Temperature range: 5÷110 °C
  • Opening overpressure: 10 %
  • Closure range: 20 %
  • PED cat.: IV Materials
  • Body: brass CW617N - UNI EN 12165
  • Knob: ABS
  • Spring: steel PRODUCT CODE CONNECTIONS Ø ORIFICE [mm] NET SECTION [mm2] CALIBRATION PRESSURE [bar] HEATING - DOMESTIC HOT WATER OUTFLOW COEFFICIENT Kd DRAINAGE CAPACI- TY IN ACCORDANCE WITH “R” COLL. [kg/h] MAX. GENERATOR POWER [kW] R140DY104 G 1/2”F x G 3/4”F 15 176,71 2,25 0,736 210,91 122,3 R140DY105 2,5 229,52 133,1 R140DY106 2,7 243,86 141,4 R140DY107 3 263,04 152,6 R140DY109 3,5 296,34 171,9 R140DY110 4 329,73 191,2 R140DY111 4,5 360,16 208,9 R140DY112 5 396,79 230,1 R140DY113 5,4 425,65 246,9 R140DY115 6 450,2 261,1 R140DY117 7 520,23 301,7 R140DY119 8 585,26 339,5 R140DY124 G 3/4”F x G 1”F 20 314,16 2,25 0,771 392,78 227,8 R140DY125 2,5 427,44 247,9 R140DY126 2,7 454,16 263,4 R140DY127 3 489,88 284,1 R140DY129 3,5 551,89 320,1 R140DY130 4 614,07 356,2 R140DY131 4,5 670,76 389 R140DY132 5 738,97 428,6 R140DY133 5,4 792,71 459,8 R140DY135 6 838,44 486,3 R140DY137 7 968,87 561,9 R140DY139 8 1089,98 632,2

Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia  consulenza.prodotti@giacomini.com  +39 0322 923372 - giacomini.com PRODUCT CODE CONNECTIONS Ø ORIFICE [mm] NET SECTION [mm2] CALIBRATION PRESSURE [bar] HEATING - DOMESTIC HOT WATER OUTFLOW COEFFICIENT Kd DRAINAGE CAPACI- TY IN ACCORDANCE WITH “R” COLL. [kg/h] MAX. GENERATOR POWER [kW] R140DY144 G 1"F x G 1-1/4"F 25 490,87 2,25 0,736 585,86 339,8 R140DY145 2,5 637,55 369,8 R140DY146 2,7 677,4 392,9 R140DY147 3 730,68 423,8 R140DY149 3,5 823,17 477,4 R140DY150 4 915,92 531,2 R140DY151 4,5 1000,47 580,3 R140DY152 5 1102,21 639,3 R140DY153 5,4 1182,37 685,8 R140DY155 6 1250,59 725,3 R140DY157 7 1445,12 838,2 R140DY159 8 1625,76 942,9 R140DY164 G 1-1/4"F x G 1-1/2"F 32 804,24 2,25 0,723 1073,33 622,5 R140DY165 2,5 1168,04 677,5 R140DY166 2,7 1241,04 719,8 R140DY167 3 1338,65 776,4 R140DY169 3,5 1508,1 874,7 R140DY170 4 1678,03 973,3 R140DY171 4,5 1832,92 1063,1 R140DY172 5 2019,32 1171,2 R140DY173 5,4 2166,18 1256,4 R140DY175 6 2291,16 1328,9 R140DY177 7 2647,56 1535,6 R140DY179 8 2978,5 1727,5

Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia  consulenza.prodotti@giacomini.com  +39 0322 923372 - giacomini.com The R140D safety valves are factory calibrated. Each valve is supplied with an original copy of the calibration report; this document contains not only the technical data of the valve, but also the serial number (also shown on the top of the handwheel fixed to the valve body). The document is printed and validated by the INAIL technician who witnessed the calibration operation. The user is responsible for maintaining the safety valve calibration, avoiding any type of intervention that could alter its correct functioning.  Calibration  NOTE. The calibration report must be stored with care; copies cannot be issued if the original is lost. When the thrust of the pressurised fluid triggers a return spring on the disc, the valve discharges a specific amount of fluid to prevent the defined pressure level from being exceeded, and then re-closes within the permitted closure range.  Operation  Installation Before installing the R140D safety valves, the personnel in charge must size them correctly, in accordance with the current The safety valves must be installed in the highest part of the heat generator, or on the delivery pipe, no more than 1 m distance from the generator. They must be clearly visible and easy to check. The pipe connecting the safety valve to the generator must be free of any interception and with a diameter no less than that of the valve itself. The safety valve drainage must be clearly visible and channelled into a pipe with a diameter no less than that of the valve itself, using a funnel (R141 or R141C) if necessary. HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) R140D R141 R141C R140D R141 R141C R140D R141 R141C R140D R141 R141C ≤ 1 m HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) R140D R141 R141C R140D R141 R141C R140D R141 R141C R140D R141 R141C ≤ 1 m HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) R140D R141 R141C R140D R141 R141C R140D R141 R141C R140D R141 R141C ≤ 1 m HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) HEAT GENERATOR (BOILER) R140D R141 R141C R140D R141 R141C R140D R141 R141C R140D R141 R141C ≤ 1 m  WARNING. The safety valves can be installed vertically or horizontally, but not upside down (to prevent system impurities from settling); respect the flow direction indicated by the arrow on the body. The valve must be checked at least once a year, by increasing the system pressure to induce drainage. If this is not possible, is possible to rotate the knob and check the drainage visually. Any impurities that form on the housing can be removed by means of regular purging.  Maintenance

Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia  consulenza.prodotti@giacomini.com  +39 0322 923372 - giacomini.com It is appropriate to channel the fluids drained by the safety valves with the aid of a relief funnel R141 or R141C (to be ordered separately).  Relief funnels R141 SERIES R141C SERIES SAFETY VALVE DISCHARGE SIZE R141Y014 R141CY004 3/4” R141Y015 R141CY005 1” R141Y016 R141CY006 1-1/4” R141Y017 - 1-1/2”  NOTE. The use of the R141 or R141C relief funnels (plus curved fittings R19 and R189 if necessary) prevents any fluid spray from reaching the electric components.  Dimensions PRODUCT CODE CONNEC- TIONS DIMENSIONS AxBxC [mm] R140DY104 G 1/2”F x G 3/4”F 53 x 109 x 39 R140DY105 R140DY106 R140DY107 R140DY109 R140DY110 R140DY111 R140DY112 R140DY113 R140DY115 R140DY117 R140DY119 PRODUCT CODE CONNEC- TIONS DIMENSIONS AxBxC [mm] R140DY124 G 3/4”F x G 1”F 66 x 138 x 49 R140DY125 R140DY126 R140DY127 R140DY129 R140DY130 R140DY131 R140DY132 R140DY133 R140DY135 R140DY137 R140DY139 PRODUCT CODE CONNEC- TIONS DIMENSIONS AxBxC [mm] R140DY144 G 1”F x G 1-1/4”F 77 x 170 x 59 R140DY145 R140DY146 R140DY147 R140DY149 R140DY150 R140DY151 R140DY152 R140DY153 R140DY155 R140DY157 R140DY159 PRODUCT CODE CONNEC- TIONS DIMENSIONS AxBxC [mm] R140DY164 G 1-1/4”F x G 1-1/2”F 88 x 186 x 69 R140DY165 R140DY166 R140DY167 R140DY169 R140DY170 R140DY171 R140DY172 R140DY173 R140DY175 R140DY177 R140DY179 A C B

Giacomini S.p.A. Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia  consulenza.prodotti@giacomini.com  +39 0322 923372 - giacomini.com R140D Safety valve - INAIL compliant (Italy). Female-female threaded connections: G 1/2”F x G 3/ 4”F, G 3/ 4”F x G 1”, G 1”F x G 1-1/ 4”F, range 5÷110 °C. Nominal pressure 10 bar. Opening overpressure 10%. Closure range 20%. Compliance with Directive “PED” 2014/68/EU (cat.IV). Factory calibration: 2,25 - 2,5 - 2,7 - 3 - 3,5 - 4 - 4,5 - 5 - 5,4 - 6 - 7 - 8 bar.  Product specifications  Package Disposal. Carton boxes: paper recycling. Plastic bags and bubble wrap: plastic recycling.  Product Disposal. Do not dispose of product as municipal waste at the end of its life cycle. Dispose of product at a special recycling platform managed by local authorities or at retailers providing this type of service.  Safety Warning. Installation, commissioning and periodical maintenance of the product must be carried out by qualified operators in compliance with national regulations and/or local standards. A qualified installer must take all required measures, including use of Individual Protection Devices, for his and others’ safety. An improper installation may damage people, animals or objects towards which Giacomini S.p.A. may not be held liable.  Additional information. For more information, go to giacomini.com or contact our technical at any time, without notice and for technical or commercial reasons, the items included herewith. The information included in this technical sheet do not exempt the user from strictly complying with the rules and good practice standards in force.