PDRP-1001 SYSTEMSENSOR | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 56
Technical content
Deluge - Preaction Control Panel Instruction Manual
3825 Ohio Avenue
St. Charles, IL 60174 1-800-SENSOR2 Fax: (630) 377-6495 PN 50734:D0 ECN 00-543 Document 50734 I56-933-01 04/06/2001 Rev: D
LimWarLg.p65 01/10/2000 An automatic fire alarm system –typically made up of smoke detectors, heat detectors, manual pull stations, audible warn- ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. The Manufacturer recommends that smoke and/or heat detec- tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer- gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de- signed to provide early warning against fire, they do not guar- antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build- ing. A second-floor detector, for example, may not sense a first-floor or basement fire. Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be- cause: Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located. Smoke particles may be blown away from detectors by air outlets. Smoke particles may be drawn into air returns before reaching the detector. The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion- izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ- ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec- tor may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede- termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro- tection specialist. Heat detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys- tem for the connection of alarm transmission wiring, communi- cations, signaling, and/or power. If detectors are not so lo- cated, a developing fire may damage the alarm system, crip- pling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica- tion. Please note that: Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil- ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically com- patible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele- phone line failure, backup radio transmission systems are rec- ommended. The most common cause of fire alarm malfunction is inade- quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan- dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte- nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro- fessional fire alarm installers only. Adequate written records of all inspections should be kept. While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!Fire Alarm System Limitations
LimWarLg.p65 01/10/2000 WARNING - Several different sources of power can be con- nected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equip- ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft- ware. Reacceptance testing is required after any change, ad- dition or deletion of system components, or after any modifica- tion, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software func- tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert- ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de- vices, must also be tested and proper system operation veri- fied. This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity of 85% RH (non- condensing) at 30 ° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi- nal room temperature of 15-27 ° C/60-80° F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light- ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased sus- ceptibility to nearby lightning strikes. Consult with the Techni- cal Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or in- serting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi- cations, verify that they will not interfere with battery, trans- former, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re- moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. Adherence to the following will aid in problem-free installation with long-term reliability: WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. FCC Warning Installation Precautions
4 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
This control panel complies with the following NFPA standards:
- N F P A 1 3 - Sprinkler Systems
- N F P A 1 5 - Water Spray Systems
- N F P A 1 6 - Foam-Water Deluge Systems and Foam-Water Spray Systems
- NFPA 72 - Central Station Signaling Systems (Automatic, Manual, and Waterflow) - Protected Premises Unit Requires NOTI-FIRE 911AC DACT or 411UDAC Universal Digital Alarm Communicator
- NFPA 72 - Local Fire Alarm Systems (Automatic, Manual, Waterflow and Sprinkler Supervisory)
- NFPA 72 - Auxiliary Fire Alarm Systems (Automatic, Manual, and Waterflow) Requires 4XTM
- NFPA 72 - Remote Station Fire Alarm Systems (Automatic, Manual, and Waterflow) Requires 4XTM or NOTI•FIRE 911AC DACT or 411UDAC Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved. NFPA Standards
- The above listed documentation
- NFPA 72 - Automatic Fire Detectors
- NFPA 72 - Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems
- NFPA 72 - Testing Procedures for Signaling Systems Underwriters Laboratories Documents
- UL 38 - Manually Actuated Signaling Boxes
- UL 217 - Smoke Detectors, Single and Multiple Station
- UL 228 - Door Closers - Holders for Fire Alarm Systems
- UL 268 - Smoke Detectors for Fire Alarm Systems
- UL 268A - Smoke Detectors for Duct Applications
- UL 346 - Waterflow Indicators for Fire Protective Signaling Systems
- UL 464 - Audible Signaling Appliances
- UL 521 - Heat Detectors for Fire Protective Signaling Systems
- UL 864 - Standard for Control Units for Fire Alarm Systems
- UL 1481 - Power Supplies for Fire Protective Signaling Systems
- UL 1638 - Visual Signaling Appliances
- UL 1971 - Signaling Devices for the Hearing Impaired
- CAN/ULC-S524-M91 Standard for In stallation of Fire Alarm Systems
- CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm System Other
- NEC Article 300 - Wiring Methods
- NEC Article 760 - Fire Protective Signaling Systems
- Applicable Local and State Building Codes
- Requirements of the Local Authority Having Jurisdiction
- ADA - Americans with Disabilities Act Refer to "Appendix B: Compatible Devices" on page 39 for a listing of all compatible initiating, indicating and releasing devices. Before proceeding, the installer should be familiar with the following documents.
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 5 Table of Contents 1. Product Description 2. Installation
6 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
- System Operation Appendix A: Secondary Power Calculations Appendix B: Compatible Devices Appendix C: NFPA Standard-Specific Requirements NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)45 Appendix D: Testing & Maintenance
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 7 1. Product Description Overview The PDRP-1001 Series Deluge - Preaction Control System has been designed as a control center for use in single- and dual-hazard deluge and preaction applications. The panel is a feature-packed control unit suitable to perform detection and control functions associated with the release of water-based fire protection systems. The panel is designed for maximum reliability with 100% solid state circuitry and isolated relay contacts for outside interfacing and features programmable options to allow on-site customization of the unit for various operating configurations. An integral standby battery system, with charger, is provided. In case of commercial AC power interruption, automatic switchover to the battery system will provide power to the panel for a minimum of 24 hours. The control panel is supplied complete with backbox, hinged door, control switches, and indicator LEDs. The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm) conduit knockouts available. The PDRP-1001 and PDRP-1001A are 110/120 V AC control panels. The PDRP-1001E is a 220/240 V AC control panel.
Features
Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.
- Microprocessor-controlled
- Alarm and trouble resound
- Four Style B/D Initia ting Device Circuits
- Two Style Y/Z Notification Appliance Circuits
- Two Style Y Release Circuits
- General alarm and trouble relays
- Designed for sprinkler standards NFPA 13, 15 & 16.
- Disable/enable controls pe r Initiating Device Circuit
- Last Event Recall
- Battery/Earth fault supervision
- Current protection on al l notification circuits
- RMS regulated output power, 2.25 amps
- 7 amp-hour (AH) to 18 AH battery options, up to 90 hours standby
- Resettable and nonreset table regulated power outputs
- Extensive transient protection
- Watchdog timer to supervise microprocessor
- Output circuits protecte d against false activations
- Slide-in zone identification labels
- Steel cabinet 14.5” (36.83cm) wide by 16.00” (40.64cm) high by 4.75” (12.07cm) deep
- Dual Hazard operation
- Municipal Box output
- Adjustable discharge timer
- 4XTM Transmitter Module - Complies with NFPA
72 Auxiliary and Remote Station Protective
- 4XZM Zone Relay Module for zone/function relays
- RZA-4X Supervised remo te annunciator (requires 4XLM Interface Module)
- 411UDAC or NOTI•FIRE 911AC Digital Communicator - Complies with NFPA 72 Central Station and Remote Station Protective Signaling systems
- 4XMM V olt/Amp Meter Module
- Cross-zone option
- Dead-front dress panel option (DP-4X) (Required for Canadian applications)
- Trim ring for flush mount between 16 in. (40.64 cm) center studs (TR-4XR)
- Product Description Circuits
8 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Initiating Device Circuit #1 (Style B/D) Initiating Device Circuit #2 (Style B/D) Waterflow (Style B/D) Supervisory (Style B/D) Output circuits NAC 1 - Alarm/Waterflow (Style Y/Z) NAC 2 - Waterflow/Supervisory (Style Y/Z) Releasing Circuit 1 (Style Y) Releasing Circuit 2 - Supervisory (Style Y) Note: Zone Relay Module (4XZM) tracks these four circuits. Front Panel Control Switches Switch 1 - Tone Silence Switch 2 - Alarm Silence Switch 3 - Alarm Activate Switch 4 - System Reset Suplemental Documentation The table below lists document sources containing additional information regarding the PAR-3: Digital Alarm Communicator/Transmitters NOTI-FIRE 911AC Instruction Manual 411UDAC Instruction Manual 74-06200-005 51073 Remote Station Receiver Fire•L ite RS82-9 Instruction Manual 15400 V oltmeter/Ammeter 4X Seri es Power Meter PID 15396
Control Panel 1. Product Description PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 9 Control Panel Figure 1 Control Panel SW1 TB1 TB2 TB3 TB4 JP1 GEN ALM2 SUPV 1 SUPV 2 GEN ALM1 OPT1 OPT2 J10 AMP TB5 OUT#1 B+ A+ A– B– OUT#3 B+ B– OUT#4 B+ B– OUT#2 B+ A+ A– B– IN #1 B+ A+ A– B– IN #2 B+ A+ A– B– IN #3 B+ A+ A– B– IN #4 B+ A+ A– B– TONE SILENCE ALARM SILENCE ALARM ACTIVATE SYSTEM RESET AC POWER SYSTEM ALARM RELEASE SUPERVISORY SYSTEM TROUBLE CIRCUIT TROUBLE ALARM SILENCED POWER TROUBLE ZONE 1 WATERFLOW SUPERVISORY PEM2-board.cdr Battery Fail LED Ground Fault LED SW1 - DIP Switch Micro Fail LED J4 - J5 - J7 - J8 Optional Module Connectors Notification Appliance Circuits Style Z (Class A) / Style Y (Class B) Relays Alarm Contacts Trouble Contacts Initiating Device Circuits - #1 to #4 Style D (Class A) / Style B (Class B) 24VDC Regulated Nonresettable Regulated Resettable RMS-Regulated Releasing Circuits Style Y (Class B) Super- visory Water- flow
- Product Description DIP Switch Functions
10 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
The table below describes the DIP switch functions. For a more detailed explaination see "Setting Mode of Operation" on page 28. Options Three optional modules are available for use on the control panel. The control panel provides mounting slots for two of these optional module boards. Transmitter Module - 4XTM The Transmitter Module provides a supervised output for a Local Energy Municipal Box transmitter and alarm and trouble reverse polarity circuits for Remote Station Service. Also included is a DISABLE switch and disable trouble LED. Note: As a jumper option, the alarm reverse polarity circuit will open on trouble if no alarm exists. Specifications for Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System) Supervisory current: 5.0 mA. Trip current: 0.35 amps (subtracted from Notification Appliance power). Coil V oltage: 3.65 VDC. Coil resistance: 14.6 ohms. Maximum allowable wire resistance between panel and trip coil: 3 ohms. Municipal Box wiring can leave the building. Specifications for Remote Station Service (NFPA 72 Remote Station Fire Alarm System) Maximum load for each circuit: 10 mA. Reverse polarity output voltage: 24 VDC. Remote Alarm and Remote Trouble wiring can leave the building. Zone Relay Module - 4XZM The Zone Relay module provides Form-C contacts for the following:
- Relay #1 - Alarm/Alarm Pressure NAC
- Relay #2 - Alarm Pressure/Auxiliary Supervisory NAC
- Relay #3 - Release 1
- Relay #4 - Auxiliary Supervisory NAC/Release 2
- Relay #5 - System Alarm
- Relay #6 - System Trouble Note: As a jumper option, the first four relays can be made silenceable. Specifications Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 V AC (resistive). #1 & #2 Mode of Operation Determines how NACs and Releasing Circuits respond to an alarm. #3, #4 & #5 Timer Selects Discharge Timer setting. Note: See “Setting Mode of Operation” on page 28 for a more detailed explanation of DIP switch functions. TB1 TBL 4XTMF.cdr TB1 LATCH DISABLE 4XZMF.cdr
Options 1. Product Description PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 11 Remote Annunciator - RZA-4X The Remote Annunciator mounts on a standard single-gang box, and provides LED indication of the same functions as the Zone Relay Module.
- Alarm/Alarm Pressure (red)
- Alarm Pressure/Aux Supervisory (red)
- Releasing Circuit 1 (red)
- Aux Supervisory/Releasing Circuit 2 (red)
- System Trouble LED (yellow) A local trouble sounder and silence switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of information. Note: The Remote Annunciator requires the use of an LED Interface Module as described below. LED Interface Module - 4XLM The LED Interface Module supports the RZA-4X Remote Annunciator Module. Annunciator wiring is supervised for open conditions by this module. The module mounts to the main board on the J8 option connector. Specifications Maximum voltage/current, each output: 27.6 V / 8 mA. Outputs are power-limited. Meter Module (Volts-Amps) - 4XMM The Meter Module provides a voltmeter to measure the voltage across the batteries and an ammeter to measure the charging current to the batteries. The meters are provided as an assembly that mounts to the lower left-hand corner of the cabinet. SYSTEM TROUBLE RE-SOUND TONE SILENCE FIRE ALARM ANNUNCIATOR RXA-4XF.cdr TB1 4XLMF.cdr 10 20 30 DC VOLTS DC AMPERES 4XMMF.cdr
- Product Description Specifications
12 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
PDRP-1001 and PDRP-1001A: 110/120 V AC, 50/60 Hz, 1.2 amps PDRP-1001E: 220/240 V AC, 50/60 Hz, 0.6 amps Wire size: minimum #14 AWG with 600V insulation Battery (lead acid only) Maximum Charging Circuit: 27.6V , 1.5 amps Maximum Battery Capacity: 18 AH. Note: Batteries larger than 12 AH require Notifier BB-17 or other UL-listed external battery cabinet. Initiating Device Circuits Power-limited circuitry Operation: Style B (Class B) or Style D (Class A) Normal Operating V oltage: 24 VDC (ripple = 1.0V p-p) Alarm current: 15 mA minimum Short circuit current: 40 mA maximum Maximum detector current in standby: 2 mA (max) per zone Maximum loop resistance: 100 ohms End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed) Detector loop current is sufficient to ensure operation of one alarmed detector per zone. Supervisory current: 5 mA (including End-of-Line Resistor) Notification Appliance and Releasing Circuits Power-limited circuitry Maximum allowable voltage drop due to wiring: 2 VDC Normal Operating V oltage: 24 VDC Total current available to all external devices: 2.25 amps Maximum signaling current per circuit: 1.5 amps End-of-Line Resistor: 4.7K, 1/2-Watt (p/n 71252 UL listed) Alarm and Trouble Relays Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 V AC (resistive). Note: Any power connected to these relay contacts must come from a power-limited supply. Fail-safe operation ensures trouble relay functioning under loss of both primary power (AC) and secondary (battery power). Resettable Power Up to 200 mA is available for powering four-wire smoke detectors. Maximum ripple voltage: 1.0 V p-p. Nonresettable Power Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke detector power). Maximum ripple voltage: 1.0 V p-p. RMS Regulated Power Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available to Notification Appliance Circuits). Maximum ripple voltage: 100 mV p-p.
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 13 2. Installation Cabinet Mounting Carefully unpack the system and check for shipping damage. Select a suitable location in a clean, dry, vibration-free environment that is not subject to extreme temperatures. Locate the top of the cabinet approximately five feet above the floor with the hinge on the left. The panel must be easily accessible for maintenance; the hinged door requires a minimum clearance of 14 in. (35.56cm) to open. Removal of Circuit Board To prevent damage to the printed circuit board it should be removed prior to mounting of cabinet. Mounting of Cabinet Securely mount the cabinet using the mounting holes provided. Attaching Conduit Select and remove knockouts according to the number of conduits required. Attach conduits to backbox as required. Determine the number of conductors required for the devices to be employed. Pull required conductors into the box through the knockouts provided. Note: All wiring should be in accordance with the National and/or Local codes for fire alarm systems, including "Power-limited Wiring Requirements" on page 17. Step Action
1 Disconnect the transformer wires from the circuit board at the J1
connector.
2 Remove the four (4) phillips head screws securing circuit board to
backbox rails. 3 Carefully set board aside in a secure place. Step Action
1 Mark and predrill holes for the top tw o keyhole mounting screws using the
dimensions shown in Figure 2 on page 14. 2 Install two upper screws in the wall with the heads protruding. 3 Using the upper keyholes, mount the backbox over the two screws. 4 Mark and drill the lower two holes.
5 Secure backbox by installing the rema ining fasteners and tightening all
screws.
6 If required, attach optional Trim Ring (TR-4XR) using the provided
instructions.
- Installation Cabinet Mounting
14 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
The figure below shows the exterior dimensions and mounting hole locations for the cabinet backbox and dimensions of the optional trim ring: Figure 2 Cabinet Mounting Dimensions Reinstallation of Circuit Board Reinstall the printed circuit board as follows: Step Action
1 Position circuit board over stand-offs on backbox rail and secure with four
(4) phillips screws. Tighten securely. 2 Connect transformer wires to J1 connector on circuit board. 14.625” (37.15cm) 16.125” (40.96cm) 5.375” (13.65cm) 16.00” (40.64cm) 4.75” (12.07cm) 14.50” (36.83cm) 12.50” (31.75cm) 9.50” (24.13cm) 1.00” (2.54cm) 1.00” (2.54cm) 1.5” (3.81cm) 16.125” (40.96cm) 14.625” (37.15cm) MS44-cabdim.cdr MS44-trimring.cdr
Installing Optional Voltmeter/Ammeter 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 15 Installing Optional Voltmeter/Ammeter To monitor battery voltage and battery charging current, a 4XMM Meter Module is required. To install the power meter module follow the steps below: The figure below shows the mounting location and connections for the V oltmeter/Ammeter. Figure 3 Mounting and Connecting the Meters Step Action 1 Cut the jumper wire labeled “AMP”. 2 Secure the module to the backbox with the hardware provided. Refer to Product Installation Drawing (PID) for detailed instructions. 3 Connect meter cable P2 to connector J2 on the main circuit board. 4 Connect meter cable P3 to connector J3 on the main circuit board. AMP TB5 10 20 30 DC VOLTS DC AMPERES MS44-mminst.cdr ‘AMP’ Jumper
- Installation Power Connections
16 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
WARNING: Do not apply any type power to this control panel until all connections have been made and verified. AC Connections Disconnect (open) the circuit breaker in the AC main breaker panel and tag it “Out of Service”. Note: Refer to "Power-Up Procedure" on page 30 before closing AC breaker. Primary power required for the PDRP-1001 and PDRP-1001A control panels is 110/120 V AC, 50/60 Hz, 1.2 amps and for the PDRP-1001E is 220/240 V AC, 50/60 Hz, 0.6 amps. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use #14 AWG (2.00 mm2) or larger wire with 600V insulation rating. A separately fused and protected power connection to the panel should be supplied to prevent voltage fluctuation and interruption of power. Figure 4 AC Power Connections Battery (DC) Connections WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. CAUTION: Do NOT connect the battery interconnect wire at this time. Make this connection AFTER initial system primary power connection. Place batteries into bottom of cabinet as shown below. See "Appendix A: Secondary Power Calculations" on page 37 for calculation of correct battery rating. Note: Batteries are shipped separately and should be mounted only after the cabinet has been installed, the conduit connected, and all wiring pulled, tested, and made ready to be terminated. Continued on the next page... AMP TB5 MS44-ACconn.cdr Ground Neutral Hot
- Installation Initiating Device Circuits
18 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Initiating Device Circuits The control panel provides four (4) Initiating Device Circuits (#1, #2, #3 and #4) and they may be configured as either Style D (Class A) or Style B (Class B). Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and Waterflow alarm devices. Note: Refer to the "Appendix B: Compatible Devices" on page 39 for compatible devices.
- Wire all alarm initiating devices sequentially for proper supervision.
- Observe polarity when connecting polarized devices.
- All circuits are supervised and power-limited.
- Leave dummy load resistor (provi ded) on all unused circuits. Figure 7 Initiating Device Circuits Style D (Class A) Initiating Device Circuit Style B (Class B) Initiating Device Circuit Style B (Class B) Supervisory Circuit PAR3-idc.cdr Note: Silk screen printing on circuit board moved to bottom for clarity 4.7K, 1/2-Watt ELR PN 71252 (UL listed) Normally Open Waterflow Devices Normally Open Tamper or Pressure Switches Heat Detector Two-wire Smoke Detector Manual Pull Station Style B (Class B) Initiating Device Circuit
Initiating Device Circuits 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 19 Four-Wire Smoke Detector Connections A maximum of 200mA is available from the 24VDC Resettable Power circuit on TB1 (+24VR terminals). Any power that is drawn from the 24VDC Nonresettable Power on TB2 (+24VNR terminal) must be subtracted from available resettable power. See "Specifications" on page 12 and "Powering External Devices" on page 22. Note: Refer to the "Appendix B: Compatible Devices" on page 39 for suitable 4-wire smoke detectors. Notes on Style D (Class A) and Style B (Class B) field wiring: 1. The Power Supervision Relay coil leads must be connected to the last detector base 24V screw terminals. 2. Calculation of the maximum allowable resistance in the 24VDC resettable power wiring: Where: Rmax = maximum resistance of the 24 VDC wires Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current Figure 8 Typical Connection for Four-Wire Smoke Detectors Rmax = (20.6 - V om) (N x Is) + (Na x Ia) + (Ir) TB1 TB4 IN #1 B+ A+ A– B– IN B+ A+ MS44-4wiresd.cdr24 VDC Four-wire Smoke Detectors 4.7K, 1/2-Watt ELR PN 71252 (UL listed) Power Supervision Relay (A77-716B) Style B Initiating Device Circuit Control Panel Power Circuit
- Installation Output Circuits
20 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Notification Appliance Circuits The control panel provides two Style Z (Class A) or Style Y (Class B) Notification Appliance Circuits, which are supervised and power-limited. Each circuit is capable of 1.5 amps of current. Total current drawn from both NACs and both Releasing Circuits (see "Releasing Circuits" on page 21) cannot exceed 2.25 amps. Note: Refer to the "Appendix B: Compatible Devices" on page 39 for suitable devices.
- For DIP switch configuration, see "Setting Mode of Operation" on page 28.
- For non-silenceable service on NAC#1, s ee "Non-Silenceable Service" on page 34.
- Unused circuits must be connected with a dummy load as shown. Figure 9 Notification Appliance Circuits TB2 MRP44-nac.cdr Polarized Horn Polarized Strobe Polarized Bell Style Z (Class A) 4.7K, 1/2-Watt ELR PN 71252 (UL listed) Unused Style Y Circuit 4.7K, 1/4-Watt ELR PN 71252 (UL listed) Style Y (Class B)
Output Circuits 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 21 Releasing Circuits CAUTION: To prevent accidential discharge, connect releasing devices after initial panel tests are completed. The control panel provides two Style Y (Class B) Releasing Circuits, which are nonpower-limited. Note: All wiring must follow the requirements as specified under "Power-limited Wiring Requirements" on page 17. Each circuit is capable of 1.5 amps of current. Total current drawn from both Releasing Circuits and both NACs (see "Notification Appliance Circuits" on page 20) cannot exceed 2.25 amps.
- UL listed and FM approved releasing devices must be used.
- Unused circuits must be connected with a dummy load as shown. Figure 10 Releasing Circuits Wiring must be configured to maintain a minimum voltage of 20.4 VDC on releasing Circuits. Calculation of maximum allowable resistance: Where: Rmax = maximum allowable resistance of wiring Is = Solenoid current TB2 TB2 Releasing Circuits Canadian Applications MRP44-rel.cdr REL-4.7K Unused Releasing Circuits 4.7K, 1/4-Watt ELR PN 71252 (UL listed) Rmax = 20.6 VDC – 20.4 VDC Is
- Installation Powering External Devices
22 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
One Form-C dry contact alarm relay is provided in the basic panel for controlling supplementary devices. Contacts are rated 2 amps at 30 VDC and 0.5 amps at 30 V AC (resistive) and are non-silenceable when an alarm occurs. Trouble Relay Circuit One Form-C dry contact trouble relay is provided in the basic panel for controlling supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 V AC (resistive) and will restore to normal when the trouble condition is cleared. Note: Power connected to these relay contacts must come from a power-limited supply. Power may be obtained from TB1 Terminals 24VU or 24VR and TB2 Terminals 24VNR, or a UL-listed power-limited power supply. Figure 11 Schematic Representation of Alarm/Trouble Coils & Contacts Powering External Devices CAUTION: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while this unit is energized. DC power connections are available from TB1 and TB2 on the control panel as shown below: Figure 12 Power Terminals TB3 MS44-relay.cdr !!! TB1 TB2 RMS-Regulated Power -
24 VDC power for inductive-type
devices such as door holders can be connected to these terminals. This output is not suitable for powering devices requiring filtered DC power. Resettable Power -
24 VDC filtered, resettable power for four-wire smoke
detectors can be obtained from these terminals. The combined current draws from the Resettable and Nonresettable outputs cannot exceed 200 mA. Nonresettable Power -
24 VDC filtered, nonresettable power
can be drawn from these terminals. The combined current draws from the Resettable and Nonresettable outputs cannot exceed 200 mA. MS44-dcpower.cdr
Optional Modules 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 23 Optional Modules Overview The control panel has two module connectors - J5 (upper position) and J8 (lower position). Three modules are available for the panel and they can be used in any combination, including duplicate modules. The corresponding option jumper must be cut before installation of an optional module, to enable module supervision.
- The 4XZM Zone Relay and the 4XTM Transmitter Modules can be installed in either position.
- The 4XLM Interface Module must be installed in the lower position only. Installation - Upper Position To install either the 4XZM or 4XTM module in the upper position follow these instructions: Figure 13 Module Installation - Upper Position Step Action 1 Cut jumper ‘OPT1’ on main circuit board.
2 Insert the two stand-offs into the holes located on the right-side edge of the
main board. Secure with nuts and tighten securely.
3 Align the pins of J5 (and J4) connector s on the main board with the holes on
the underside of the J2 (and J1) connector on the optional board. Carefully press down on the optional board until the pins are through the connectors and it rests on the stand-offs. 4 Secure optional board to stand-offs with screws. Tighten securely.
5 Affix the terminal identification la bel (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module. TB4 OPT1 OPT2 J10 IN #2 B+ A+ A– B– IN #3 B+ A+ A– B– IN #4 B+ A+ A– B– TB1 LATCH DISABLE MS44-instmod1.cdr OPT1 - Cut prior to installation of module Install Stand-offs here
- Installation Optional Modules
24 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Installation - Lower Position To install either the 4XTM, 4XZM or 4XLM module in the lower position follow these instructions: Figure 14 Module Installation - Lower Position Step Action 1 Cut jumper ‘OPT2’ on main circuit board. 2 Remove the lower-right screw securing the main board to the lower rail. Replace with a stand-off and tighten securely.
3 Insert one stand-off into the other hol e located on the right-side edge of the
main board. Secure with nut and tighten securely.
4 Align the pins of J8 (and J7) connector s on the main board with the holes on
the underside of the J2 (and J1) connector on the optional board. Carefully press down on the optional board until the pins are through the connectors and it rests on the stand-offs. 5 Secure optional board to stand-offs with screws. Tighten securely.
6 Affix the terminal identification la bel (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module. TB4 OPT1 OPT2 J10 IN #2 B+ A+ A– B– IN #3 B+ A+ A– B– IN #4 B+ A+ A– B– TB1 MS44-instmod2.cdr Install Stand-offs here OPT2 - Cut prior to installation of module
Optional Modules 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 25 Setup and Configuration Transmitter Module - 4XTM Connect a Remote Alarm circuit, Remote Trouble circuit or a Municipal Box to the Transmitter Module as shown below. Polarities shown in activated positions. Note: Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected. Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building. Pushing the Disconnect Switch down will prevent unwanted activation of the Municipal Box during testing of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the Municipal Box. Cut the TBL Jumper to allow the alarm reverse polarity circuit to open on trouble, if no alarm exists. The wiring of this module must follow the requirements as specified under "Power-limited Wiring Requirements" on page 17. Figure 15 4XTM Configuration TB1 TBL 4XTMF.cdr TBL Jumper Disconnect Switch Disconnect LED Remote Alarm (Power-limited) Remote Trouble (Power-limited) Municipal Box (Nonpower-limited) No Connection
- Installation Optional Modules
26 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Note: The PAR-3 includes one (1) Zone Relay Module (4XZM). Relay #1 through #4 on this module will activate with outputs #1 through #4. For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right. Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label, located on the door of the control panel. Figure 16 Wiring the Zone Relay Module The wiring of this module must follow the requirements specified under "Power-limited Wiring Requirements" on page 17.
- If this module is used to drive both nonpower-l imited and power-limited circuits, skip one set of dry contacts to maintain the required separation between circuit types.
- If this module is used to drive both nonpower-limited and power-limited relays that are next to each other, refer to the figure below which shows the one allowable arrangement. Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits TB1 LATCH DISABLE Disable Switch“Latch” Jumper 4XZMF.cdr Power-Limited Circuit Nonpower-Limited Circuit MS44--4xzmf1.cdr No Connection
Optional Modules 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 27 LED Interface Module - 4XLM Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA- 4X Remote Annunciator. Make wiring connections with system power off. Maximum wire impedance is 50 ohm per wiring connection. The wiring of this module must follow the requirements as specified under "Power-limited Wiring Requirements" on page 17. Figure 18 Connection of 4XLM to RZA-4X SYSTEM TROUBLE RE-SOUND TONE SILENCE FIRE ALARM ANNUNCIATOR TB1 Connect to corresponding terminals of the RZA-4X Remote Annunciator. Front View Side View MS44--4xlmfconn.cdr Single-gang Box +24V Out #1 Out #2 Out #3 Out #4 Sysyem Trouble Sound Resound
- Installation Setting Mode of Operation
28 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Select operating mode by setting the SW1 DIP switches as described below. After any changes are made to the configuration of the switches, the panel must be reset. For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 34. Figure 19 DIP Switch Settings Basic Program Select the desired mode of operation and set DIP Switches 1 and 2 per the appropriate column. Note: Output 1 and 2 refer to Notification Appliance Circuits; Output 3 and 4 refer to Releasing Circuits. Mode 1 Two Zone Single Hazard Mode 2 Cross Zone Single Hazard Mode 3 Combined Release Dual Hazard Mode 4 Split Release Dual Hazard Switch 1 Switch 2 OFF OFF ON OFF OFF ON ON ON Output 1 & 3 - Activated by an alarm on either IDC 1 or 2. Output 2 - Activated by a waterflow alarm on IDC 3. Output 4 - Activated by a supervisory condition on IDC 4. Output 1 - Activated by an alarm on either IDC 1 or 2. Output 2 - Activated by a waterflow alarm on IDC 3. Output 3 - Activated by alarms on both IDC 1 and 2. Output 4 - Activated by a supervisory condition on IDC 4. Output 1 - Activated by an alarm on either IDC 1 or 2 or a waterflow alarm on IDC 3. Output 2 - Activated by a supervisory condition on IDC 4. Output 3 & 4 - Activated by an alarm on either IDC 1 or 2. Output 1 - Activated by an alarm on either IDC 1 or 2 or a waterflow alarm on IDC 3. Output 2 - Activated by a supervisory condition on IDC 4. Output 3 - Activated by an alarm on IDC 1. Output 4 - Activated by an alarm on IDC 2. SW1 MS44-dipsw.cdr Basic Programming Switch 1: Cross Zone Switch 2: Dual Hazard Discharge Timer Switch 3: Discharge Timer Switch 4: Discharge Timer Switch 5: Discharge Timer Not Used
Setting Mode of Operation 2. Installation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 29 Discharge Timer Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly.
- For NFPA 13 and 15 applications timer must be set to “Disabled”.
- For NFPA 16 applications timer may be set to “10 Minutes” or “15 Minutes”. Note: Timer will always start at Zone 2 normal to alarm transition. Upon timeout, corresponding release circuits will shut off. Note: Zone 1 will always override timer shutoff (except for Mode #4 - Split Release). Disabled 10 Minutes 15 Minutes Switch #3 OFF ON ON Switch #4 OFF ON ON Switch #5 OFF OFF ON
- Installation Power-Up Procedure
30 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
WARNING: Prior to energizing this panel, notify all personnel and authorities, including any personnel who may be working on, around, or near this unit. WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. CAUTION: Observe polarity of batteries. Improper connection will cause damage and VOID WARRANTY. Follow these steps to power-up the FACP: 1. Conduct Visual Inspection. A careful visual inspection should be made before applying power to the system. See “Inspection” on page 51. 2. Notification. Notify personnel who may be working with the AC power circuits before removing the “Out of Service” tag. 3. Apply Primary Power. Switch the circuit breaker to the ‘closed’ position, providing power to the circuit.
- The green AC power LED will illuminate.
- The Trouble LED will illuminate until battery power is applied. 4. Connect Secondary Power. Connect battery interconnect wire as shown below.
- The trouble LED will clear. If the trouble light does not clear, refer to "Troubleshooting Table" on page 52. Figure 20 Battery Connections MS44-batcable.cdr Battery Interconnect Wire
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 31 3. System Operation System Status LEDs Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily. Figure 21 System Status LEDs AC Power - Green LED that illuminates steadily to indicate presence of AC power. System Alarm - Red LED that flashes when an alarm occurs. Release - Red LED that illuminates steadily when release occurs. After the Discharge Timer has expired, the LED will flash. Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch) on IDC 4. System Trouble - Yellow LED that flashes for any trouble condition, including those associated with optional boards. Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits (notification and releasing). Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm. Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions. The following LEDs are located below the main panel and are visible only when the panel door is open. Battery Fail (BATT) - Yellow LED that illuminates steadily on motherboard when battery is low or not detected. Ground Fault (EARTH) - Yellow LED that illuminates steadily on motherboard during a ground fault condition. Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor failure. TONE SILENCE ALARM SILENCE ALARM ACTIVATE SYSTEM RESET AC POWER SYSTEM ALARM RELEASE SUPERVISORY SYSTEM TROUBLE CIRCUIT TROUBLE ALARM SILENCED POWER TROUBLE ZONE 1 ZONE 2 WATERFLOW SUPERVISORY PEM2-panel1.cdr BATT EARTH MICRO FAIL System Status LEDs
- System Operation Control Switches
32 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Figure 22 Control Panel Switches Tone Silence - Pressing this switch acknowledges alarms, troubles and supervisories. The panel has alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate steadily on TONE SILENCE and the piezo turns off. A second trouble will resound the piezo. Trouble conditions are self-restoring. Alarms latch and require pressing SYSTEM RESET to clear. Unless the unit is set for non-latching supervisory service, supervisories latch and require pressing SYSTEM RESET to clear. The piezo has three tones for different conditions (see "Piezo" on page 33). Alarm Silence - Pressing this switch acknowledges for alarms and supervisories. This switch will silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits (not the Releasing Circuits). The “Alarm Silenced” LED will illuminate. Alarm silence is a latching function and requires pressing SYSTEM RESET to clear. Note: Releasing Circuits will turn off only if Discharge timer criteria is satisfied (see "Setting Mode of Operation" on page 28). Alarm Activate - This switch may be used to activate Notification Appliance Circuits (NACs). It also activates the System Alarm Relay. This is a latching function. Pressing ALARM SILENCE silences the NACs and System Alarm Relay, and lights the Alarm Silenced LED. Pressing SYSTEM RESET returns the system to normal. System Reset - This switch breaks power to all initiating circuits, four-wire smoke detector power and optional boards and will clear any activated output circuits. If any alarm or trouble still exists after reset, they will reactivate the panel. Holding SYSTEM RESET down will perform a LAMP TEST function and will activate the piezo sounder. Zone Status LEDs The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED(s) will illuminate steadily. Figure 23 Zone Status LEDs TONE SILENCE ALARM SILENCE ALARM ACTIVATE SYSTEM RESET MS44-panel2.cdr ZONE 1 ZONE 2 WATERFLOW SUPERVISORY PEM2-panel2.cdr Alarm LED Trouble LED Not Used
Piezo 3. System Operation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 33 Piezo The piezo (local buzzer) generates different tone patterns for different event conditions:
- Alarm - Generates a steady tone, no pulse.
- Trouble - Pulses one second on, one second off. Repeats 30 pulses per minute.
- Supervisory - Pulses one-half second on, one-half second off. Repeats 60 pulses per minute. Supervisory Service Initiating Device Circuit #4 is always used for monitoring supervisory devices (such as valve tamper switches). A short circuit on this IDC (activation of a N.O. contact) will cause the Supervisory LED and the Zone 4 (Supervisory) trouble LED to flash. The piezo will sound one-half-second on, one-half-second off. Pressing TONE SILENCE will silence the piezo and cause the Supervisory LED to illuminate steadily, but the Zone 4 (Supervisory) trouble LED will continue to flash. Supervisory signals latch and require SYSTEM RESET to clear (unless unit is programmed for non-latching operation). The ALARM SILENCE switch will silence the piezo, causing the Supervisory LED to illuminate steadily and turn off the Supervisory Notification Circuit. An open circuit on Zone 4 (Supervisory) will be reported as a trouble. Note: The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching operation is the default setting. Canadian regulations require latching operation; for programming instructions, see "Sprinkler Supervisory Tracking" on page 34. Zone Disable If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the piezo or any output circuit. If both power sources are removed from the system, all zones will be re-enabled upon restoration of power. Disable status will be lost. The Zone Disable routine makes use of the four panel switches as follows: 1. Press and hold in the TONE SILENCE switch. 2. With the TONE SILENCE switch held in, press (in sequence) the ALARM SILENCE switch, the ALARM ACTIV ATE switch, and then the SYSTEM RESET switch. 3. The Zone 1 Alarm LED will flash. 4. To disable Zone 1, press the SYSTEM RESET switch. The Zone 1 yellow LED will light to show that the zone is disabled. Note: The SYSTEM RESET switch toggles disable status for the selected zone. 5. To select the next zone, pr ess the ALARM SILENCE switch. 6. To select the previous zone, press the ALARM ACTIV ATE switch. 7. When disable selections are comple te, release the TONE SILENCE switch. If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash. TONE SILENCE ALARM SILENCE ALARM ACTIVATE SYSTEM RESET Press Hold Press ---> Press ---> Press
- System Operation Last Event Recall
34 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes use of the four panel switches as follows: 1. Press and hold in the TONE SILENCE switch. 2. With the TONE SILENCE switch held in, pre ss (in sequence) the SYSTEM RESET switch, the ALARM ACTIV ATE switch, and then the ALARM SILENCE switch. 3. LEDs will light to indicate the last event recorded in the panel’s buffer. 4. Release the TONE SILENCE switch to return to normal operation. To clear the Last Event buffer, press SYSTEM RESET twice. Non-Silenceable Service Notification Appliance Circuit #1 can be programmed as non-silenceable by following these steps: 1. Press and hold in the TONE SILENCE switch. 2. With the TONE SILENCE switch held in, pre ss in sequence the ALARM SILENCE switch, then the ALARM ACTIV ATE switch, and finally the ALARM SILENCE switch again. 3. Release the TONE SILENCE switch. Note: If both primary and secondary power sources are removed from the system, these settings will be lost. When power is restored, Notification Appliance Circuit #1 will default to silenceable operation. Sprinkler Supervisory Tracking The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching operation is the default setting. Canadian regulations require latching operation. 1. Press and hold in the TONE SILENCE switch. 2. With the TONE SILENCE switch held in, pre ss in sequence the ALARM SILENCE switch, then the ALARM ACTIV ATE switch, and finally the ALARM ACTIV ATE switch again. 3. Release the TONE SILENCE switch. Note: If both primary and secondary power sources are removed from the system, this setting will be lost. When power is restored, supervisory will default to latching operation. System Events Standby Condition Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off. System Trouble Condition Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED. The Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound one second on, one second off, and repeating until silenced. Silence the piezo by pressing the TONE SILENCE switch. The panel will remain in the trouble state until the trouble condition has been cleared and the panel reset.
System Events 3. System Operation PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 35 Single Zone in Alarm (Cross Zone) Condition Upon actuation of a single-zone initiating device, a red alarm LED will illuminate to indicate whether Zone 1 or Zone 2 is in alarm. In addition to the LED, a single-zone alarm will activate the Alarm Relay; the piezo and NAC #1 will start sounding. In alarm condition, the piezo will generate a steady tone. The piezo can be silenced by pressing the trouble silence switch. If the fire is extinguished before a second zone alarm is activated, return the system to normal standby condition by pressing the reset switch inside the panel and holding it for three (3) seconds. Both Zones in Alarm (Cross Zone) Condition When the first alarm occurs, the panel will function as described above. Upon the occurrence of a second alarm, the second alarm LED will illuminate, NAC #2 will energize, and the solenoid valve(s) will energize to activate releasing devices. Brownout Condition The total power being provided to the system’s power supply should not exceed the current draw during fully loaded panel operation. Brownout circuitry annunciates degradation of the incoming AC voltage supply. A brownout condition is annunciated when the AC power decreases. When the brownout threshold is reached, the system reacts as if AC power is totally lost:
- Battery backup begins supplying power to operate the control panel
- General Trouble Relay contact transfers
- Green AC Power LED turns off
- Yellow System Trouble LED illuminates
- The piezo will sound one second on, one second off, and repeat until the Trouble is cleared. When the AC voltage returns or increases above the brownout threshold, the green AC Power LED will illuminate. The power supply circuitry will return to primary power functions and begin to recharge the backup battery supply.
- System Operation System Events
36 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 37 Appendix A: Secondary Power Calculations Standby Battery Requirements The Standby Battery Current obtained in the table below represents the amount of current that must be supplied by the secondary power source (batteries) to sustain control panel operation for one hour. Note: The control panel will support the installation of one or two optional modules, including two of the same type of module. Only one 4XLM can be included in this count. Table 1 Standby Battery Current Device Type # of Devices Current (amps) Total Current (amps) Main Circuit Board 1 X 0.088 = 0.088 4XZM Zone Relay Module [ ] X 0.008 = 4XTM Transmitter Module [ ] X 0.011 =
- R e v e r s e P o l a r i t y Alarm output [ ] X 0.005 =
- R e v e r s e P o l a r i t y Trouble output [ ] X 0.005 = RZA-4X/4XLM Remote Annunciator [ ] (1 max) X 0.019 = 4XMM Meter Module [ ] X 0.001 = 2-wire Detector Heads [ ] X [ ]1 1. Refer to the "Appendix B: Compatible Devices" on page 39 for smoke detector standby current. 4-wire Detector Heads [ ] X [ ]1 = End-of-line Relays2 2. Must use compatible listed Power Supervision Relay. [ ] X [ ] = Current Draw from TB2 (nonalarm)3 3. The total standby current must include both the resettable (TB1 - +24VR terminals) and nonresettable (TB2 - +24VNR terminals) power. Caution must be taken to ensure that current drawn from these outputs during alarm does not exceed maximum ratings specified. [ ] X [ ] = Standby Battery Current = amps
Appendix A: Secondary Power Calculations Calculating the Battery Capacity
38 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Calculating the Battery Capacity Use this table to determine the battery capacity required by the system. Table 2 Amp Hour Calculations The battery charger in this panel will charge a maximum of 18 AH of batteries within 48 hours (7 AH minimum). Batteries larger than 12 AH will require a UL-listed battery cabinet (e.g. BB-17). Select a battery with an equal or greater AH rating than the value obtained in the table above. Note: Batteries must be lead-acid type. Standby Battery Current (from Table 1) [ ] amps X Required Standby Time in Hours (typically 241, 602 or 903 hours) [ ] hrs 1. NFPA 72 Central Station and Local and Proprietar y Fire Alarm Systems require 24 hours of standby time. 2. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby time. 3. Factory Mutual Systems require 90 hours of st andby for preaction and deluge sprinkler systems. Standby Amp Hours Enter: 0.25 for 5 minutes in alarm, or 0.50 for 10 minutes in alarm Alarm4 Amp Hours 4. Alarm AH assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 AH) or for 10 minutes (0.5AH). Total Standby and Alarm Load + Multiply by derating factor X 1.2 Battery size required in AH =
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 39 Appendix B: Compatible Devices Two-wire Smoke Detectors, UL Listed Use the two-wire detectors listed below. Table 3 Two-wire Smoke Detectors Detector Model Identifier Type Base Model Identifier Standby Current (mA) Detectors per Zone System Sensor 1400 A I onization n/a n/a 0.10 20 System Sensor 1451 A I onization B401/B401B/ B406B A 0.12 15/15/1 System Sensor 1851DH A I onization DH1851DC A 0.12 15 System Sensor 2400 A Photoelectric n/a n/a 0.12 15 System Sensor 2400AIT A Photo/ Isolated Thermal/Horn n/a n/a 0.12 15 System Sensor 2400AT A Photo/ Thermal/Horn n/a n/a 0.12 15 System Sensor 2400TH A Photo/ Thermal n/a n/a 0.12 15 System Sensor 2451 A Photoelectric B401/B401B/ B406B A 0.12 15/15/1 System Sensor 2451TH A Photo/ Thermal B401/B401B/ B406B A 0.12 15/15/1 System Sensor 2851DH A Phot oelectric DH2851DC A 0.12 15 System Sensor 1451DH A I onization DH400 A 0.12 15 System Sensor 2451 A Photoelectric DH400 A 0.12 15 System Sensor 2300T A Photo/ Thermal n/a n/a 0.12 15 System Sensor 1800 A Ioni zation n/a n/a 0.12 n/a System Sensor 1851B A I onization B101B A 0.12 n/a System Sensor 1851B A I onization B107B A 0.12 n/a System Sensor 2800 A Photoelectric n/a n/a 0.12 n/a System Sensor 2800TH A Photo/ Thermal n/a n/a 0.12 n/a System Sensor 2851B A Photoelectric B101B A 0.12 n/a System Sensor 2851B A Photoelectric B107B A 0.12 n/a System Sensor 2851BTH A Photo/ Thermal B101B A 0.12 n/a System Sensor 2851BTH A Photo/ Thermal B107B A 0.12 n/a System Sensor 1151 A Ionization B401/ B110LP/ B116LP A 0.12 15/15/1 System Sensor 2151 A Photoelectric B401/ B110LP/ B116LP A 0.12 15/15/1
Appendix B: Compatible Devices Four-wire Smoke Detectors, UL Listed
40 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Four-wire Smoke Detectors, UL Listed Use the four-wire detectors listed below. Table 4 Four-wire Smoke Detectors FM Approved Releasing Devices (System Sensor’s PDRP-1001/PDRP-1001A/PDRP-1001E) Note: Refer to the FM approval guide for automatic water control valves which are compatible with solenoids listed. Table 5 Solenoid Release Valves Detector/Base Type Max Standby Current (mA) Max Alarm Current (mA) System Sensor 2424 Photoelectric 0.10 41 System Sensor 2424TH Photoelectric 0.10 41 System Sensor 2451 Photoelectric 0.10 39 System Sensor 2451TH w/B402 Base Photoelectric 0.10 39 System Sensor 1424 Ionization 0.10 41 System Sensor 1451 w/B402 Base Ionization 0.10 39 System Sensor 2412 Photoelectric 0.12 77 System Sensor 2412AT Photoelectric 0.12 58 System Sensor 2412TH Photoelectric 0.12 77 System Sensor 2312/24TB Photoelectric 0.12 50 System Sensor B112LP Base See Note 39 System Sensor B114LP Base See Note 75 System Sensor B404B Base See Note See Note System Sensor 6424 Projected Beam 10 28.4 System Sensor DH400ACDCI Ionization Duct 25 95 System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112/24 Ionization 0.05 50 System Sensor 2112/24 Photoelectric 0.05 50 System Sensor 2112/24B Photoelectric 0.05 65 System Sensor 2112/24T Photoelectric w/135° Thermal 0.05 50 System Sensor 2112/24TSRB Photoelectric w/135° Thermal Supervisory Relay 15 45 Note: Contact manufacturer for currents. Manufacturer Model Voltage Watts Amps NPS Orfice Solenoid Group A Skinner LV2LBX25 24 VDC 11 458 mA 1/2” 5/8” Solenoid Group B These valves are interchangeable ASCO T8210A107 24 VDC 16.8 700 mA 1/2” 5/8” ASCO R8210A107 24 VDC 16.8 700 mA 1/2” 5/8” ASCO 8210A107 24 VDC 16.8 700 mA 1/2” 5/8” Solenoid Group C Star Sprinkler Corp. p/n 5550 24 VDC part of Model D Deluge Valve Kidde-Fenwal p/n 890181 24 VDC 2.0 Kidde-Fenwal p/n 899175 24 VDC 2.0 Kidde-Fenwal p/n 48650001 24 VDC 0.2 Kidde-Fenwal p/n 897494 24 VDC 33.0 1.5
Notification Appliances, UL Listed Appendix B: Compatible Devices PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 41 Notification Appliances, UL Listed Control panels suppling Special Application (FWR, Filtered) power must use the Notification Appliances listed below.
- Rated V oltage is nominal operating voltage
- All currents are in millamp eres and worst case average. Product Rated Voltage FWR DC Filtered DC System Sensor MA-12/24D Electronic Sounder 24VDC 73 46 System Sensor SS24 Strobe 24VDC * 30 System Sensor SS24LO Strobe 24VDC 45 25 System Sensor SS24LOC Ceiling Strobe (SS24LOBC - beige) 24VDC 45 25 System Sensor SS24M Strobe 24VDC 125 75 System Sensor SS24MC Ceiling Strobe 24VDC 125 75 System Sensor MASS24D Electronic Sounder/Strobe 24VDC 118 71 System Sensor MASS24LO Electronic Sounder/Strobe 24VDC 118 71 System Sensor MASS24LOC Electronic Ceiling Sounder/Strobe 24VDC 118 71 System Sensor MASS24LOLA Electronic Sounder/Strobe w/Fuego lens 24VDC 118 71 System Sensor MASS24M Electronic Sounder/Strobe 24VDC 198 121 System Sensor MASS24MC Electronic Ceiling Sounder/Strobe 24VDC 198 121 System Sensor PA400R Sounder 24VDC * 15 System Sensor PS24LO Add-on Strobe 24VDC 45 25 System Sensor SS2415ADA Signaling Strobe 24VDC 90 75 System Sensor SS2475ADA Signaling Strobe 24VDC 200 170 System Sensor SS24110ADA Signaling Strobe 24VDC 245 210 System Sensor SS241575ADA Signaling Strobe 24VDC 120 93 System Sensor SS2415ADAS Signaling Strobe with Synch. Circuit 24VDC 125 106 System Sensor SS241575ADAS Signaling Strobe with Synch. Circuit 24VDC 180 115 System Sensor MASS24110ADA Sounder/Signaling Strobe 24VDC 163 121 System Sensor MASS2475ADA Sounder/Signaling Strobe 24VDC 273 216 System Sensor MASS24110ADA Sounder/Signaling Strobe 24VDC 318 256 System Sensor MASS241575ADA Sounder/Signaling Strobe 24VDC 193 139 System Sensor MASS24110ADAS Sounder/Signaling Strobe w/Sync. Ckt. 24VDC 163 121 System Sensor MASS241575ADAS Sounder/Signaling Strobe w/Sync. Ckt. 24VDC 193 139 System Sensor PS2415ADA Mini-Sounder/Strobe 24VDC 110 90 System Sensor PS2475ADA Mini-Sounder/Strobe 24VDC 135 108 System Sensor PS24110ADA Mini-Sounder/Strobe 24VDC 240 225 System Sensor PS241575ADA Mini-Sounder/Strobe 24VDC 135 108 System Sensor SP1R2415ADA Speaker/Signaling Strobe 24VDC 90 75 System Sensor SP1R2475ADA Speaker/Signaling Strobe 24VDC 200 170 System Sensor SP1R24110ADA Speaker/Signaling Strobe 24VDC 245 210 System Sensor SP1R241575ADA Speaker/Signaling Strobe 24VDC 120 93 System Sensor V4R2415ADA Speaker/Signaling Strobe 24VDC 90 75 System Sensor V4R2475ADA Speaker/Signaling Strobe 24VDC 200 170 System Sensor V4R24110ADA Speaker/Signaling Strobe 24VDC 245 210 System Sensor V4R241575ADA Speaker/Signaling Strobe 24VDC 120 93 System Sensor SP100W24LOC Ceiling Speaker/Strobe, 8” round grill 24VDC 45 25 System Sensor SP101R24LO Speaker/Strobe, 5” square grill 24VDC 45 25
Appendix B: Compatible Devices Notification Appliances, UL Listed
42 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Table 6 Notification Appliances System Sensor SP101R24M Speaker/Strobe, 5” square grill 24VDC 125 75 System Sensor SP100W24MC Ceiling Speaker/Strobe, 8” round grill 24VDC 125 75 System Sensor MA12/24EH Multi Alert Horn with Mechanical Tone 12VDC/ 24VDC 20/64 38/43 System Sensor MAEH24LO Multi Alert Horn with Mechanical Tone/Strobe 24VDC 109 68 System Sensor MAEH24LOC Multi Alert Horn with Mechanical Tone/Strobe 24VDC 109 68 System Sensor MAEH24LOLA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 153 96 System Sensor MAEH24M Multi Alert Horn with Mechanical Tone/Strobe 24VDC 189 118 System Sensor MAEH24MC Multi Alert Horn with Mechanical Tone/Strobe 24VDC 189 118 System Sensor MAEH1215ADA Multi Alert Horn with Mechanical Tone/Strobe 12VDC 240 191 System Sensor MAEH121575ADA Multi Alert Horn with Mechanical Tone/Strobe 12VDC 310 246 System Sensor MAEH2415ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 278 216 System Sensor MAEH2475ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 273 216 System Sensor MAEH241575ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 343 271 System Sensor MAEH24110ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 318 256 System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone/Strobe 24VDC 198 152 System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical Tone/Strobe 24VDC 253 241 System Sensor H12 SpectrAlert Horn 12VDC 25 14 System Sensor H24 SpectrAlert Horn1 24VDC 42 37 System Sensor S1215 SpectrAlert Strobe 12VDC 159 133 System Sensor S121575 SpectrAlert Strobe 12VDC 182 168 System Sensor S2415 SpectrAlert Strobe1 24VDC 142 83 System Sensor S241575 SpectrAlert Strobe1 24VDC 132 76 System Sensor S2475 SpectrAlert Strobe1 24VDC 170 145 System Sensor S24110 SpectrAlert Strobe1 24VDC 220 169 System Sensor P1215 SpectrAlert Horn/Strobe 12VDC 173 144 System Sensor P121575 SpectrAlert Horn/Strobe 12VDC 196 179 System Sensor P2415 SpectrAlert Horn/Strobe1 24VDC 165 94 System Sensor P241575 SpectrAlert Horn/Strobe1 24VDC 177 111 System Sensor P2475 SpectrAlert Horn/Strobe 24VDC 215 180 System Sensor P24110 SpectrAlert Strobe1 24VDC 265 214 System Sensor RP1215ADAA Retrofit Strobe Plate 12VDC 200 170 System Sensor RP121575ADAA Retrofit Strobe Plate 12VDC 240 255 System Sensor RP2415ADAA Retrofit Strobe Plate 24VDC 90 75 System Sensor RP241575ADAA Retrofit Strobe Plate 24VDC 120 93 System Sensor RP2475ADAA Retrofit Strobe Plate 24VDC 200 170 System Sensor RP24110ADAA Retrofit Strobe Plate 24VDC 245 210 Note 1: Refer to manufacturer’s installation instructions for more information. Contact manufacturer for currents. Product Rated Voltage FWR DC Filtered DC
Door Holders, UL Listed Appendix B: Compatible Devices PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 43 Door Holders, UL Listed Use the Door Holders listed below. Table 7 Door Holders
24 VDC Relays, UL Listed
Use the Relays listed below. Table 8 24 VDC Relays Model Type Current (mA) FM-980-24 Floor Mount, Single 68 FM-986-24 Wall Mount, Surface Wiring 68 FM-998-24 Wall Mount, Concealed Wiring 68 DH150A Floor Mount 96 DH154A Flush Mount 96 DH158A Surface Mount 96 Vendor Model Current (mA) System Sensor A77-716B 20 Air Products & Controls, LTD MR-101/C MR-201/C
Appendix B: Compatible Devices 24 VDC Relays, UL Listed
44 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 45 Appendix C: NFPA Standard-Specific Requirements Minimum System Requirements The control panel has been designed for use in commercial, industrial, and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this appendix. The minimum system components required for compliance with the appropriate NFPA standard are listed below.
- Fire Alarm Control Panel. Contains the main control board, cabinet (backbox and door), main supply transformer and power supply.
- Batteries. Refer to "Appendix A: Secondary Power Calculations" on page 37
- Initiating Devices. Connected to one of the control panel's Initiating Device Circuits.
- Notification Appliances. Connected to one of the control panel's Notification Appliance Circuits.
- Releasing Devices. Connected to one of the control panel’s Releasing Circuits. Additional Requirements The following additional equipment is needed for compliance with the NFPA standards listed below. The relay contacts of this control panel may be used to trip any dialer that is UL listed for Central Station/Remote Station services. The illustrations in this appendix provide examples of possible system configurations. Note: Applications which require the the NOTI-FIRE 911AC are not FM approved. NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
- NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter (DACT) connected to a compatible listed Central Station DACR or Protected Premises Receiving Unit. See "Digital Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 46 for installation instructions for this unit.
- 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central Station DACR or Protected Premises Receiving Unit. See "Universal Digital Alarm Communicator - 411UDAC" on page 47 for installation instructions for this unit. NFPA 72 - Auxiliary Fire Alarm System
- 4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box. See "Local Energy Municipal Box" on page 48 for installation instructions for this unit. NFPA 72 - Remote Station Fire Alarm System
- Fire•Lite RS82-9 Remote Station Receiver connected to a 4XTM Transmitter Module. See "Remote Station Receiver - RS82-9" on page 49 for installation instructions for this unit.
- NOTI-FIRE 911AC DACT connected to a compatible listed Central Station DACR. See "Digital Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 46 for installation instructions for this unit
- 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 47 for installation instructions for this unit.
Appendix C: NFPA Standard-Specific Requirements Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
46 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC Note: This application is not FM approved Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises Receiving Unit.
- AC Wiring for DACT/FACP must be connected to the same circuit.
- If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less than 20 ft. (609.6 cm) in length in the same room.
- For additional information refer to the Noti-Fire 911AC Instruction manual. Figure 24 DACT Connections GEN ALM2 TB3 TB4 JP1 SUPV 1 SUPR 2 GEN ALM1 OPT1 IN #1 B+ A+ A– B– IN #2 B+ A+ A– B– IN #3 B+ A+ A– B– IN #4 B+ A+ A– B– TB1 LATCH DISABLE STD DACT TB3 MS44-911ac.cdr Place jumper over pins as shown when employing a DACT. This directs the control panel to transmit all trouble conditions except AC LOSS. To Central Station PS 1270 12Volt 7AH BatteryTo AC Power See Below for Terminal Connections Control Panel 4XZM Zone Relay Module To Common Terminal of RelayJumper
Universal Digital Alarm Communicator - 411UDAC Appendix C: NFPA Standard-Specific Requirements PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 47 Universal Digital Alarm Communicator - 411UDAC The following figure illustrates an example of Central Station/Remote Station Receiver or Protected Premises Receiving Unit reporting using a 411UDAC. The relay contacts of the MRP-4424 may be used to trip any dialer listed for Central Station/Remote Station services. For additional information refer to the Instruction Manual for the 411UDAC.
- All connections between the control panel and the 411UDAC must be in conduit, less than 20 feet (6.1 meters) in length in the same room.
- The PDRP-1001 Series is non suitable for transmission of a supervisory signal to the DACT.
- Any zone of the 411UDAC can be wired to function as alarm or trouble; the unit must be programmed accordingly. In this example, Zone 1 is wired to the control panel’s alarm relay, Zone2 is wired to the control panel’s trouble relay, and Zone 3 is wired to the optional module’s supervisory relay.
- AC power is supplied directly to the 411UDAC, not through the control panel. AC wiring for both the 411UDAC and the control panel must be connected to the same AC branch circuit.
- End-of-Line Resistors must termin ate all circuits. In this example, Zone 4 is unused and is terminated at the board.
- When employing a DACT, place the JP1 jumper, on the control panel, as shown below. This directs the panel to transmit all trouble conditions except AC LOSS. The DACT must be configured to transmit AC power loss to the central station. Figure 25 411UDAC Connections TB2TB4TB1 RELAY 1 NO NC C RELAY 2 NO NC C NAC B+ B- ZONE 1 B+ B- ZONE 4 B+ B- ZONE 2 B+ B- ZONE 3 B+ A+ A- B- +12V PWR + - PH1 PH2 Trouble Alarm Secondary Phone Line Primary Phone Line Modular Cable P/N MCBL-6 Supervisory Control Panel 4XZM Zone Relay Module MS44-411.cdr Zone 1 Zone 2 Zone 3
411 UDAC
Appendix C: NFPA Standard-Specific Requirements Local Energy Municipal Box
48 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Local Energy Municipal Box Using the 4XTM Transmitter Module for connection to a Local Energy Municipal Box.
- The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for direct short between two wires. It is not a power-limited circuit.
- This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
- Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms. Figure 26 Municipal Box Connection TB1 TBL FIRE Local Energy Municipal Box Municipal Box Circuit 4XTM Transmitter Module (activated polarities shown) MS44-4xtmfmb.cdr
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 49 Remote Station Receiver - RS82-9 Using the 4XTM Transmitter Module for connection to a Fire•Lite RS82-9 Remote Station Receiver.
- Intended for connection to a polar ity reversal circuit of a remote station receiving unit having compatible ratings.
- All connections are power-limited and supervised with the exception of the reverse polarity loop.
- Supervision of the loop is the responsibility of the receiver. Figure 27 RS82-9 Connections TB1 TBL Fire•Lite RS82-9 Remote Station Receiver MS44-rs82.cdr 4XTM Transmitter Module + – + – Remote Trouble Remote Alarm
Appendix C: NFPA Standard-Specific Requirements Remote Station Receiver - RS82-9
50 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 51 Appendix D: Testing & Maintenance Testing Inspection Perform the following prior to applying power to the system.
- Check the actual wiring hookup with the wiring diagrams.
- Insure that no pieces of wire have fallen into the circuitry.
- Check for missing or damaged parts. Alarm Test An initial alarm test should be conducted following installation to determine that all parts of the system are functioning properly. The panels should remain powered for 24 to 36 hours proir to connecting the releasing solenoids. This precaution will avoid false discharges of gas in case of faulty or improperly placed detectors. To perform an alarm test on the panel follow this procedure 1. Disconnect AC power and battery power. 2. Disconnect the installed solenoid valve circuit l eads an connect spare solenoid valves, or connect an end-of-line device to serve as a dummy load. 3. Reconnect AC power and battery power. 4. Initiate a first zone alarm condition by blowing smoke into one of the Zone 1 smoke detectors. This should cause the first zone alarm condition.
- The alarm relay will energize.
- The red zone alarm LED will be illuminated.
- The remote Indicating Circuit #1 audible alarm and the local piezo will start sounding. Maintenance A regular schedule of inspection, testing, and maintenance is vital to insure proper and reliable operation of the control panel. The procedures should be performed as required by the local authority having jurisdiction. Refer to NFPA for further details. Troubleshooting A troubleshooting table is included on the following page which provides for symptoms, problems and their solutions.
Appendix D: Testing & Maintenance Troubleshooting
52 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Table 9 Troubleshooting Table Symptom Problem Solution AC Power LED ON System trouble LED ON Circuit trouble LED ON Notification appliance circuit trouble 1. Check TB2 for proper connections. 2. Remove all field wiring and install dummy ELR at output circuit. Check for supervisory voltage across it, (Normal -2.3 V), if problem persists, replace circuit board. 3. Removed dummy ELR, reconnect field wiring and measure voltage across output; (trouble-5V , short 0V). 4. Check for ELR at last device. 5. Check field wiring. Any of the right column yellow LEDs flashing Initiating zone open circuit trouble 1. Check TB4 for proper connections. 2. Remove field wiring for zone in trouble and install dummy ELR (4.7K). If problem persists, replace circuit board. 3. Check for ELR at last device. 4. Check field wiring. Any of the right column yellow LEDs steady ON Zone disable 1. Check installation manual. Power trouble LED ON Battery trouble Batt yellow LED ON Missing or Disconnected 1. Check battery connections. Low or damaged battery 1. Remove batteries, check voltage across charger output (17 to 19V), otherwise replace circuit board. 2. Reconnect batteries, measure battery voltage at battery terminals. If voltage is less than 85% of rated voltage, allow them to charge for 48 hours. 3. If problem persists, replace batteries. Ground fault trouble Earth yellow LED ON 1. Remove field wiring from main panel and optional module(s) (if installed). Install dummy ELR (4.7K). 2. Remove both battery leads. 3. If trouble clears, connect one circuit at the time to pin point the problem. 4. If trouble doesn’t clear, replace circuit board. Yellow LED on 4XTM ON 4XTM 1. Move Municipal Box disconnect switch SW1 up. OPT1, OPT2 jumper cut 1. Install optional module(s) or replace jumper if module(s) is not used. Municipal Box open circuit 1. Install dummy load if Municipal Box option isn’t used. 2. Check Municipal Box wiring. Any of the right column red LEDs ON Short on initiating circuit wiring 1. Remove field wiring and install ELR. If trouble clears, look for faulty or incorrectly wired devices. Disconnecting Municipal Box switch ON 4XTM does not create a trouble Jumper for optional modules isn’t cut 1. Cut associated jumper OPT1 or OPT2. 4XZM: associated LED doesn’t activate for alarm, trouble or supervisory conditions Optional module trouble 1. Make sure module is properly installed. 2. Move disable switch SW1 on 4XZM to the left. RZA-4X piezo doesn’t sound for alarm, trouble or supervisory conditions 4XLM 1. Make sure that 4XLM module is installed on J8. 2. Check field wiring. Micro Fail yellow LED ON Microprocessor damaged 1. Replace circuit board. All RZA-4X LEDs stay ON Power wasn’t removed prior to installation 1. Press system reset. AC Power LED OFF System trouble LED ON Loss of main power 1. Check incoming power (TB5). Damaged circuit breaker 1. Replace circuit board. Micro Fail yellow LED ON Microprocessor damaged 1. Replace circuit board.
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 53 Index Numerics 110/120 VAC 12 220/240 VAC 12 411UDAC 45, 47 4XLM LED Interface Module 11, 23 4XMM Meter Module 11, 15 4XTM Transmitter Module 10, 23, 45, 48, 49 4XZM Zone Relay Module 10, 23 911AC DACT 45, 46 A AC branch circuit 47 AC power 31, 47, 51 accidential discharge 21 acknowledge 32 additional equipment 45 alarm 31, 47 Alarm Relay 35 alarm relay 22, 51 allowable resistance 19 ammeter 11 annunciator wiring 11 audible alarm 51 authority having jurisdiction 51 B backbox 13 backbox rail 13, 14 Batteries 16, 45 battery cable 17 capacity 38 charger 38 interconnect wire 16, 17 power 51 BB-17 12, 38 black wire 17 Brownout circuitry 35 buffer 34 C Canadian 28, 33, 34 Central Station 45, 46, 47 charging current 15 circuit Remote Alarm 25 Remote Trouble 25 reverse polarity 10 circuit board 13 circuit breaker 16 Combined Release 28 conductors 13 conduit 13, 47 Cross Zone 28, 35 current 12, 21 current draw 35 D DC power connections 22 detector, four-wire smoke 32 detectors, type of 18 devices 21 devices, supplementary 22 dialer 45, 47 DIP switch 20, 28, 29 DIP switch functions 10 direct short 48 disable switch 26 disabled zone 33 discharge timer 29 discharge, accidential 21 Disconnect LED 25 Disconnect Switch 25 dry contacts 26 Dual Hazard 28 dummy load 20, 21 dummy load resistor 18 duplicate modules 23 E earth fault 31 ELR 18, 19, 20, 21 End-of-Line Resistor 12, 47 energize 35 event 31 exterior dimensions 14 external battery cabinet 12 external devices 12 F Fire Alarm Control Panel 45 first alarm 35 first zone 51 FM approved 45, 46 Form-C contacts 10, 12 four-wire smoke detector 12, 32 G ground fault 31, 48 I Indicating Circuit #1 51 initial alarm test 51 initiating circuits 32 initiating device 35, 45 Initiating Device Circuit 34
54 PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
interconnect wire, battery 30 Interface Module 11 interruption of circuits 34 J J1 connector 13, 14 J2 Connector 15 J3 Connector 15 J9 Connector 17 JP1 jumper 47 jumper 23, 24 LATCH 26 K keyhole 13 knockouts 13, 17 L label Protected Premises Unit 26 terminal identification 23, 24 LAMP TEST function 32 latch 32, 33 LATCH jumper 26 latching operation 33, 34 LED Disconnect 25 System Trouble 25 LED Interface Module 11, 23 LEDs Alarm, Trouble and Supervisory 31 Local Energy Municipal Box 10 loop resistance 48 lower position 23, 24 M main breaker panel 16 maintenance 51 Manual Pull Stations 18 maximum allowable resistance 21 Maximum Battery Capacity 12 Maximum Charging Circuit 12 maximum resistance 19 Meter Module 11, 15 microprocessor 31 minimum clearance 13 minimum voltage 21 module connectors 23 motherboard 31 mounting hole locations 14 mounting holes 13 Municipal Box 25, 48 N NACs 20 National Electrical Code, Article 760 16 National Fire Protection Association 45 negative 17 NFPA 51 NFPA standards 45 non-latching 26, 32 nonpower-limited 17, 21, 26 nonresettable power 19, 22 non-silenceable service 20 Notification Appliance Circuit 32 Notification Appliances 45 O opens 48 operating mode 28 operating voltage 19 optional boards 32 Out of Service 30 output circuits 32 overcurrent protection 16 P paper labels 11 piezo 32, 33, 34, 35, 51 piezo tones 32 polarity 17, 18, 30 polarity reversal circuit 49 polarized devices 18, 20 positive 17 power connection 16 Power Supervision Relay 19 power-limited 17, 20, 26, 49 power-limited power supply 22 previous panel status 34 primary power 16, 30 programmed 47 Protected Premises Receiving Unit 45, 46, 47 R rail 24 rail, backbox 13, 14 red wire 17 regulated power 22 relay contacts 47 Relay, System Alarm 32 release 31 releasing 21 Releasing Circuit 20, 21 releasing device 35 Releasing Devices 45 Remote Alarm circuit 25 Remote Annunciator 11 Remote Station 45, 47 Remote Station Service 10 Remote Trouble circuit 25 reset switch 35
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01 55 resettable power 19, 22 resistance, allowable 19 resistor 47 resound 32 reverse polarity 25 reverse polarity circuit 10 reverse polarity loop 49 RS82-9 Remote Station Receiver 45, 49 RZA-4X Remote Annunciator 11 S second alarm 35 Secondary Power 30 secondary power source 37 self-restoring 32 separate transmission 48 short circuit 33 silence switch 11 Single Hazard 28 Slide-in paper labels 11 solenoid valve 35, 51 Split Release 28 sprinkler 33, 34 sprinkler supervisory 48 Standby Battery Current 37 stand-off 14, 23, 24 Style B (Class B) 18 Style D (Class A) 18 Style Y (Class B) 20, 21 Style Z (Class A) 20 sulfuric acid 30 supervised 20 supervisory device 31, 33 Supervisory LED 33 supervisory signal 47 supplementary devices 22 switch, disable 26 system alarm 31 System Alarm Relay 32 System Trouble LED 25 T tag, “Out of Service” 30 terminal identification label 23, 24 testing 51 timer, watchdog 31 tone patterns 33 tones, piezo 32 tracking operation 33, 34 transformer wires 13, 14 Transmitter Module 10, 23, 48, 49 trim ring 14 trouble 47 condition 31, 34, 48 relay 22 trouble sounder 11 troubleshooting 51 Two Zone 28 U UL listed 45 unused circuits 20, 21 upper position 23 V visual inspection 30 voltage 15 voltage drop 12 voltmeter 11 W watchdog timer 31 Waterflow 18 wire, primary power 16 wires, transformer 13 Z zone 47 Zone Relay Module 10, 23
System Sensor® warrants its products to be free from defects in materials and workman- ship for eighteen (18) months from the da te of manufacture, under normal use and ser- vice. Products are date stamped at time of manufacture. The sole and exclusive obligation of System Sensor® is to repair or replace, at is option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under System Sensor® manufacturing date-stamp control, the warranty is eighteen (18) months fr om date of original purchase by System Sensor® dis- tributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired or serviced by anyone other than System Sensor® or its authorized distributors or if there is a failure to maintain the products and systems in which they operate in proper and work- able manner. In case of defect, secure a Return Authorization Number from our Customer Service Department. Return product, transportation prepaid, to System Sensor Repair Department, RA #_____, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. This writing constitutes t he only warranty made by System Sensor ® with respect to its products. System Sensor® does not represent that its products will prevent any loss by fire or otherwise, or that it s products will in all cases prov ide the protection for which they are installed or intended. Buyer acknowledges that System Sensor® is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident or similar incident. SYSTEM SENSOR ® GIVES NO WARRANTY , EXPRESSED OR IMPLIED, OF MER- CHANTABILITY, FITNESS FOR ANY PART ICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE D ESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL SYSTEM SENSOR ® BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE SYSTEM SENSOR® PRODUCTS. FUR- THERMORE, SYSTEM SENSOR ® SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by System Sensor®. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. St. Charles, IL 60174 1-800-SENSOR2 Fax: (630) 377-6495