P20G LUMEL | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

Export department: +48 68 45 75 139/ 305/ Fax: +48 68 32 54 091 e-mail: export@lumel.com.pl „LUMEL” S.A. ul. Słubicka 1 65-127 Zielona Góra POLAND WWW.LUMEL.COM.PL P20G SEPArAtOr GAlVANIC ISolATIoN: INPUTS: oUTPUTS:

  • Full galvanic isolati on of the input, output and supply.
  • Matching of analog signals in automati on systems.
  • Fully confi gurable through the PD14 programmer. By means of the programmer, one can change the input type, output type, measurement averaging ti me and recalibrate the analog output according to the output individual characteristi c.
  • Small dimensions.
  • 0.2 accuracy class. Eample of Application FeATUReS: Outputs Output kind Properti es Remarks -20...20 mA Rload ≤ 500 Ω Conversion class: 0.2 -10...10 V Rload ≥ 500 Ω Inputs Input: Measuring range: Parameters Overloads Error Current: -20...20 mA -20...20 mA; -5...5 mA; 0...20 mA 0...5 mA 4...20 mA Resistance: 12 Ω ± 1% Short durati on over- load: 5 In Sustained overload 1.1 In Conversion class: 0.2 Voltage: -10...10 V -10...10 V; -5...5 V -1...1 V 0...10 V 0...5 V 0...1 V Resistance: > 1 MΩ Short durati on over- load: 5 Un Sustained overload 1.2 Un Eternal Features Weight < 0.125 kg Dimensions 22.5 x 120 x 100 mm Protecti on grade (acc. to EN 60529) ensured by the housing: IP 40 from the terminal side: IP 20 Fixing on a 35 mm rail acc. to EN 60715 PC Computer/ programming LPConfig P20G - programmable transducer/separator 4...20 mA 4...20 mA PD14 programmer Separati on between PLC analog inputs PLC

Table 1. Ordering codes: Table 2. Coding of the P20G separator kind of input and output