It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should be checked periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS Technical Data: MCCB125-160 (S160-SCJ) IP4X Enclosed MCCBs 300
225 FIXING CENTRES
4 x HOLES 8.5 DIA TOP AND BOTTOM GLAND PLATES 2mm THICK NOTE: TERMINAL SHROUDS NOT SHOWN FOR CLARITY 130 155 3535 M8 BOLT 8 - 12Nm M8 BOLT 8 - 12Nm 203 182 87MAXIMUM CABLE SIZE 2 x 95mm sq. WARNING: All connections (including factory made) must be checked for the correct tightness prior to the commissioning of the electrical installation MCCB125-160-3PNL-MC
450 FIXING CENTRES
6Nm Max.
EDS1205-001Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440 / Fax: 01582 692 450 e-mail: sales@europacomponents.com / website: http://www.europacomponents.com Technical Data: MCCB125-160 (S160-SCJ) IP4X Enclosed MCCBs 300 4 x HOLES 8.5 DIA TOP AND BOTTOM GLAND PLATES 2mm THICK NOTE: TERMINAL SHROUDS NOT SHOWN FOR CLARITY 182 105 35 35 M8 BOLT 8 - 12Nm 130 155 MAXIMUM CABLE SIZE 2 x 95mm sq. WARNING: All connections (including factory made) must be checked for the correct tightness prior to the commissioning of the electrical installation MCCB125-160-4P-MC
Standard Optional - Not Available TB2 Lite 160 DATA SHEET: TEMBREAK 2 S160-SCJ MCCB Frame Reference Quantity Unit Condition Max in ( A) of Frame Model S160 Number of Poles 3, 4 Type SCJ Nominal current ratings 100,125,160 0 40,50,63,80, 100,125,160
Electrical characteristics
Rated operational voltage U e (V) AC 50/60 Hz 525 DC 250 Rated insulation voltage Ui (V) 690 Rated impulse withstand voltage Uimp (kV) 8 Ultimate breaking capacity Icu (kA) 690V AC - 6 6 (IEC, JIS, AS/NZS) 525V AC 7.5 440V AC 15 400/415V AC 25 220/240V AC 35 250V DC 20 Service breaking capacity Ics (kA) 690V AC - 3 3 (IEC, JIS, AS/NZS) 525V AC 4 4 440V AC 7.5 400/415V AC 13 220/240V AC 18 250V DC 10 Rated breaking capacity (NEMA) (kA) 480V AC 7.5 240VAC 35 Protection Fixed thermal, fixed magnetic - Adjustable thermal, fixed magnetic Utilisation category A A A Installation Front connection (FC) Extension bar (FB) Cable clamp (FW) Rear connection (RC) Plug-in (PM) - - - DIN rail mounting (DA) Dimensions height (mm) 130 width (mm) 3 pole, (1 pole) 75 4 pole 100 depth (mm) 68 Weight weight (kg) 3 pole, (1 pole) 0.8 4 pole 1.0 Operation Direct Opening Action Toggle operation Door mounted (HS) / Breaker mounted handle (HB) Motor operation - - - Endurance Electrical cycles 415V AC 10,000 cycles 20,000 0 20,000 20,000 Page 1 of 3Factory-fit at time of order 14,000 ≤125A 160
Drilling plan (front view) M4 0.7 Tapped hole M4 0.7 Mounting screw Panel cutout (front view)Detail of connecting part Mounting plate (max. t3.2) Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon. Studs are horizontal direction only CD E A 111 114 ø20 37.5 3P 4P 37.5 38.5 77 102 38.5 25 25 25 B CD A B 102 114 102 F 7.7 25 25 25 102 CL CL CL CLCL LH LH LH LH LH Preparation of conductor With extension bars (optional) Drilling plan (front view) M4 0.7 Tapped hole Interpole barrier (removable) Mounting hole M4 0.7 Mounting screw M5 0.8 screw (25-40A) M8 screw (63-160A) 102 7.7 3P22 10.5 100 50130 111 N P 4P 3 8.5 5 . 6 3 1735 114 Note: For the extension bars: Straight bars or spread bars can be supplied depending on current rating. Refer to order codes for details. LH 25 25 252 5 25 ø8.3 178.5 36.5 35 35ø8.3 Rated current (A)A B C D E 16-50 10 .56 .5 41 3 16 63-160 12 .58 .5 41 3 16 F 6.5(max.) 9(max.) 16.5(max.) max.t5 14(max.) max.t5 ø5.5(25-40A) ø9(63-160A) ø5.5(25-40A) ø9(63-160A) DATA SHEET: TEMBREAK 2 S160-SCJ MCCB Outline Dimensions S160-SCJ ASL: Arrangement Standard Line HL: Handle Frame Centre Line CL: Handle Centre Line Page 2 of 3
Time/Current Characteristic Curves S160-SCJ Page 3 of 3 DATA SHEET: TEMBREAK 2 S160-SCJ MCCB
Innovators in Protection Technology /g73/g110/g115/g116/g114/g117/g99/g116/g105/g111/g110/g32/g77/g97/g110/g117/g97/g108 /g32 /g102/g111 /g114 /g77/g111/g117/g108/g100/g101/g100/g32/g67/g97/g115/g101 /g32 /g67/g105/g114 /g99/g117/g105/g116 /g66/g114/g101/g97/g107/g101/g114 /g115 (Typ es) Please retain this manual for future reference.The Manufacturer assumes no responsibility for damages resulting from non-application or incorrect application of the instructions provided herein. 7-2-10 Kamihigashi, Hiranoku, Osaka 547-0002, Japan TEL: 81-6-6791-9323/ FAX: 81-6-6791-9274 URL: www.terasaki.co.jp E-mail: int-sales@terasaki.co.jp 5470002 721 0 06(6791)9320 06(6791)9274 www.terasaki.co.jp E-mailɿkiki-info@terasaki.co.jp - - Safety Notices Be sure to read these Instructions and other associated documents accompanying the product thoroughly to be familiarize yourself with the product handling, safety information, and all other precautions before mounting, using, servicing, or inspecting the product. In these Instructions, safety notices are divided into "Warning" and "Caution" according to the hazard level: : A warning notice with this symbol indicates that neglecting the suggested procedure or practice could result in lethal or serious personal injury. : A caution notice with this symbol indicates that neglecting the suggested procedure or practice could result in moderate or slight personal injury and/or property damage. Note that failing to observe notices could result in serious results in some cases. Because safety notices contain important information, be sure to read and observe them. ˙Mounting Precautions (For detailed mounting dimensions, refer to the TemBreak2 catalogue.) ˔Electrical work should only be undertaken by suitably qualified persons. ˔Do not place the product in an area that is subject to high temperature, high humidity, excessive dusty air, corrosive gas, strong vibration and shock, or other unusual conditions. Mounting in such areas could cause a fire or malfunction. ˔Be careful to prevent foreign objects (debris, concrete powder, iron powder, etc.) and rainwater from entering product. These materials inside the product could cause a fire or malfunction. Prior to commencing any work on the product, open an upstream circuit breaker or isolator to ensure that no voltage is applied to the product. Otherwise, electrical shock may result. ˔For 4-pole breakers, be sure to connect a neutral conductor to the N pole. Otherwise, an over-current may hinder the product from tripping, thus resulting in a fire. Caution Warning Caution Caution ŝOther Precautions ĂDo not carry this product by accessory leads, as this may cause damage to the product. ĂUnauthorised opening of the breaker cover will invalidate product warranty. ĂWhen installing the product, use wires or conductors, the cross sectional areas of which accommodate the rated current of the product. Using wires or conductors with inadequate cross sectional areas may cause false tripping and overheat. ŝHandling Precautions ŘNever touch terminals. Otherwise, electric shock may result. Warning ŘWhen the breaker trips open automatically, remove the cause, then return the handle to the | (ON) position. Should a fault be interrupted, the breaker must be inspected. Otherwise, a fire may result. Caution ŘWhen connecting cable or busbar to the product, tighten terminal screws to the torque specified in this manual. Otherwise, a fire could result. ŘEven when tightening the terminal screws and after conductor connection, do not apply excessive force to the terminals. Otherwise, a fire may result. ŘFor front-connected breakers, Insulate all bare conductors of the line side until the breaker end. If interpole barriers are packed, be sure to use the barriers; moreover, insulate all bare conductors by insulating tape or the like so that the tape overlaps with the barriers. Insufficient insulation may result in short- circuit. ŘDo not block the arc gas vents of the product to ensure adequate arc space. Blocking these vents could result in failure of circuit interruption. ŝMaintenance Precautions ŘService and/or inspection of the product must be done by persons having expert knowledge. ŘBefore servicing or inspecting the product, open an upstream circuit breaker or the like to isolate all sources of power. Otherwise, electric shock may result. ŘRegularly check that the breaker terminal screws are tightened to torque values shown within this manual, failure to do so may result in fire. Caution interpole barriers insulating tubes or insulating tape Qty S50-SF, S125-SF, E160-SF, S160-SCF, S160-SF, E160-SJ, S160-SCJ, S160-SJ Type M 4 x 61 M 5 x 123P M 8 x 14 Connections/ Poles 2P 2 2P 2 4P 2 Front Connection 4P 2 Mounting screw Qty 2P 4 2P 4 4P 8 4P 8 Connecting screw M 4 x 61 Rear Connection (RC) M 4 x 61 M 4 x 75 M 5 x 15 Plug-in Connection 4P 4 4P 8Where Applicable Flush Plate (FP) M 6 x 22 M 8 x 23 M 6 S50-SF Others M 6 x 22 M 8 x 23 S50-SF Others 60∼160A 15∼50A Packaged Items / Assembly Tools Breaker: 2P: 1 3P: 2 4P: 3 Instruction Manual: 1 (This document) Interpole Barrier (Only FC) Instruction 413 19 Fix Types Fix Types Operating Instructions Trip Button TRIPPED RESET Handle Operation Operation effort ( OFF) (O N) 44,1 N (O N) ( OFF) 37,2 N TRIP ( OFF) 78,4 N AX AL SH UV V In case of fiting one (or two) auxiliary switch, fit in an order from a left sideslot. or 2 pole (ON) (OFF) (ON) (OFF) (ON) (OFF) ϦϯάϚʔΫ Symbols of Accessories Ring Mark ˎ T2AX00L T2AL00L T2SH00L T2UV00L Alarm Switch Shunt Trip Undervoltage Trip ˎ ˎ ˎ ˎ Auxiliary Switch ิॿεΠον Auxiliary Switch ใεΠον Alarm Switch a a contact b b contact a a contact b b contact 11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 94/ALa 91/ALc 92ALb 21/AXc-24/AXa 21/AXc- 22/AXb 31/AXc-34/AXa 31/AXc-32/AXb ݯ Shunt Trip power source C1-C2 ݯ Undervoltage Trip power source D1-D2 10 mm (OFF) Fitting Internal Accessories 2 Pole After fitting, verify the function of the Accessory. Combination Pull Out Leads on Load Side Removal 2G0944SAA(KRB-0602)
In case of fiting one (or two) auxiliary switch, fit in an order from a left sideslot.3 pole4 pole (ON) (OFF) (ON) (OFF) Ring Mark Symbols of Accessoriesˎ Auxiliary Switch Alarm Switch a a contact b b contact a a contact b b contact 11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 94/ALa 91/ALc 92ALb 21/AXc-24/AXa 21/AXc-22/AXb 31/AXc-34/AXa 31/AXc-32/AXb Shunt Trip power source C1-C2 Undervoltage Trip power source D1-D2 T2AX00M T2AL00M T2SH00 T2UV00 Alarm Switch Shunt Trip Undervoltage Trip ˎ ˎ ˎ ˎ Auxiliary Switch 10 mm M type (OFF) PS
5 Fitting Internal Accessories 3-4 Pole
After fitting, verify the function of the Accessory. Combination Pull Out Leads on Load Side Removal A M 4 x 61 1.3 ~ 1.7 Nm A Breaker Mounting Procedure for FC C T2PM12LE Plug-in Base 1.3 ~ 1.7 NmC M 4 x 75 Breaker Mounting Procedure for PM A D Breaker Mounting Procedure for FP D M 5 x 15 3.6 ~ 4.4 Nm 2G0944SAA(KRB-0602) E 7.8 ~ 11.8 Nm M 5 x 14 2.3 ~ 2.8 NmE 15~50A 60~125A M 6 x 18 Flat bar stud T2RP05L SS50-SF E125-SF S125-SCF S125-SF T2RP12L S 11.8 ~ 18.6 Nm F M 8 x 23 2.7 ~ 4.5 Nm M 6 x 22S50-SF Others F Conductor Connection Procedure for RC/F.P (Where Applicable) Arrangement Set G 16,5 mm H 9 mm J 16,5 mm K 9 mm L 5 mm M 9 mm max Flat Bar T2FB12LˎB M 8 x 30 11.8 ~ 18.6 Nm M 5 x 12 15 ~ 50 A M 8 x 14 60 ~ 125 A 2.3 ~ 3.4 Nm 4.9 ~ 6.9 Nm P M 6 6 ~ 8 NmQ N Ø M Ø M H GJ K L Conductor Connection Procedure for FC Insulate all bare conductors of the line side until the breaker end. N P N Q 1 2 Interpole Barrier T2BA16L Terminal Cover T2CR16L T2CF16L SLNG SG Connection RC FC ( Short Type ) Connection FC ( Long Type ) T erminal Cover T2CF16L SSNG SH Mounting Procedure Mounting Procedure Interpole Barrier Terminal Cover When removing, remove the items in reverse order of mounting. When removing, remove the items in reverse order of mounting. Handle holder/ lock can be fitted in any position of When you use this item as the handle lock, please fit padlocks in the procedure of When removing, remove the items in reverse order of mounting. Ø 5 x 3 max. Handle Handle Holder/Lock T2HH25L Handle Holder / Lock Mounting Procedure (ON) and (OFF). (OFF) PS Adjustment procedure for adjustable Thermal Magnetic Types B M 4 x 61 1.3 ~ 1.7 Nm B DIN Rail Adaptor (Optional) 3-4 Pole