MAR ATC | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

CONTROL VOLTAGE 120 VAC 50/60 Hz INPUT SPECIFICATIONS Under Voltage: 92 VAC Factor Preset (70-100 VAC Internal Adjust) Restart Voltage: 102 VAC Factor Preset (10 VAC ±10% Above U.V .) OUTPUT SPDT Relay, Pilot Duty B150, 360 VA

10 Amps @ 120 VAC Resistive

30,000 Operations Electrical @ Full Load POWER REQUIRED 3 VA Max TEMPERATURES Operate: 0°C to 55°C Storage: -45°C to 85°C ENCLOSURE Style Extended "A" LEXAN® Dust Cover TERMINATIONS/ FUNCTION

8 Pin Plug-in (Model AAA)

8 Pin Plug-in with OL Relay

L2 Disconnect Feature (Model ABA)

11 Pin Plug-in (Model ACA)

11 Pin Plug-in with OL Relay

L2 Disconnect Feature (Model ADA) The MAR series provides automatic restart to a motor by bypass- ing the start switch to re-energize M1 starter coil following a momentary drop or interruption of the control voltage. When control voltage drops below the under voltage trip point while the motor is running, the under voltage delay begins. If control voltage returns above the restart voltage point before the under voltage delay expires, the adjustable restart delay begins. Upon expiration of the restart delay, the internal relay energizes for the duration of the output interval providing restart. If control voltage fails for longer than the under voltage time delay or the motor was not initially running when control voltage failed, the unit will not restart the motor after restoration of poser. Instead a manual restart is required. This relay distinguishes between control volt - age failures and stop pushbutton operations. A stop pushbutton operation de-energizes the output relay and terminates the timing sequences preventing an automatic restart. .15” max. 3.60” .15” max. 3.60” E55826 MOTOR AUTO-RESTART RELAY

Diversified Electronics 800.727.5646 atcdiversified.com MOTOR AUTO-RESTART RELAY MAR Series

ORDERING INFORMATION

120 VAC 50/60 HZ 120

8 Pin Plug-in

11 Pin Plug-in

D D A or C B DELAY RANGE DESCRIPTIONS Restart Output Interval - Continuous Restart Output Interval - 5.0 sec (fixed) Restart Output Interval - 1.0 sec (fixed) Restart Output Interval - 5.0 sec (fixed) WIRING AAA ACA ABA ADA Note: Wiring must be exactly as shown for proper operation 5 M1 L1 L2 REACCEL CONTROL VOLTAGE AAA AVAIL STOP START 1 8 L1 L2 REACCEL CONTROL VOLTAGE ABA AVAIL STOP START 1 8 M1M1 OL STOP START CONTROL VOLTAGE OL ADA STOP START CONTROL VOLTAGE ACA 5 M1 L1 L2 REACCEL CONTROL VOLTAGE AAA AVAIL STOP START 1 8 L1 L2 REACCEL CONTROL VOLTAGE ABA AVAIL STOP START 1 8 M1M1 OL STOP START CONTROL VOLTAGE OL ADA STOP START CONTROL VOLTAGE ACA Under voltage screwdriver adjustable ranges ± 10% Restart delay screwdriver adjustable ranges ± 10% Under voltage and restart output interval fixed ranges ± 10% Delay Range Diversified Electronics 800.727.5646 atcdiversified.com