Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±20% Power consumption in operation 1.5 W Power consumption in rest position 0.5 W Transformer sizing 3 VA (class 2 power source) Electrical Connection 18 GA plenum cable, 3 ft [1 m], with 1/2” conduit connector Overload Protection electronic throughout full stroke Input Impedance 600 Ω Stroke 4” [100 mm] Actuating force motor 35 lbf [150 N] Direction of motion motor reversible with switch Manual override external push button Running Time (Motor) 150 s 100 mm Ambient humidity max. 95% r.H., non-condensing Degree of Protection IP54, NEMA 2, UL Enclosure Type 2 Housing material UL94-5VA Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU Noise level, motor 35 dB(A) Servicing maintenance-free Quality Standard ISO 9001 Weight 1.3 lb [0.58 kg] †Rated Impulse Voltage 4kV, Type of Action 1.AA.B, Control Pollution Degree 3. Linear force min. 34 lbf for control of damper surfaces up to 11 sq. ft. Application For on/off and floating point control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer’s specifications. Operation The actuator is not provided with and does not require any limit switches, but is electronically protected against overload. The anti-rotation strap supplied with the actuator will prevent lateral movement. The LHB(X)24-3... series provides 4, 8, or 12 in of linear force. The stroke of the gear rack can be adjusted on both sides in increments of 0.8 in [20 mm] by means of the mechanical end stops. When reaching the damper or actuator end position, the actuator automatically stops. The gears can be manually disengaged with a button on the actuator cover. The LHB(X)24-3… actuators use a sensorless brushless DC motor, which is controlled by an Application Specific Integrated Circuit (ASIC). The ASIC monitors and controls the actuator’s rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in holding mode. Dimensions (Inches[mm]) .69" [17.4] .54" [13.7] 2.64" [67] A A B B 3" [75] 2" [50.8] 1.1" [27.8] 2.6" [66] .16" [4] 0.13" [3.2] Stroke 4" [100] 8" [200] 12" [300] A 9.2" [233.5] 13.1" [333.5] 17.1" [433.5] B 10.4" [264.2] 14.3" [364.2] 18.3" [464.2] LHB24-3-100 Technical Data Sheet On/Off, Non-Spring Return, Linear, 24 V 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 02/10/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.

SH8 Push rod for KG6 & KG8 ball joints (36” L, 5/16” diameter). Z-DS1 Rotary support Z-KSC 3/8”-16 shaft clevis for AHK/AH. ZG-119 Bracket for AHK/AH/LH linear actuators. PS-100 Low voltage and control signal simulator. NSV24 US Battery back-up module for non-spring return actuators. NSV-BAT 12V 1.2AH battery (two required for NSV24 US). ZG-X40 120 to 24 VAC, 40 VA transformer. TF-CC US Cable conduit connector, 1/2”. Typical Specification Floating point, on/off control damper actuators shall be electronic type, with integrated linear stroking arm. Actuators shall have brushless DC motor technology and be protected from overload at all positions of linear stroke. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque. Actuators shall be cUL listed, have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo. Wiring Diagrams A Actuators with appliance cables are numbered. Provide overload protection and disconnect as required. Actuators may also be powered by 24 VDC. Actuators Hot wire must be connected to the control board common. Only connect common to neg. (-) leg of control circuits. Terminal models (-T) have no-feedback. Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed. 1 3 1124 VAC Transformer Blk (1) Common Red (2) + Hot Wht (3) Y Input Line Volts A On/Off 1 3 1124 VAC Transformer Blk (1) Common Red (2) + Hot Wht (3) Y Input Line Volts A Floating Point ComHot 1 3 11A Blk (1) Common Red (2) + Hot Wht (3) Y Input Line Volts

24 VAC Transformer

Floating Point - Triac Source 1 11A Blk (1) Common Red (2) + Hot Wht (3) Y Input Line Volts Floating Point - Triac Sink LHB24-3-100 Technical Data Sheet On/Off, Non-Spring Return, Linear, 24 V 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 02/10/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.