22RT-59-1 BELIMO | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Technical data sheet 22RT-59-1 www.Belimo.US 22RT-59-1 • en-us • 2020-07-20 • Subject to change 1 / 4 Room Sensor Temperature Active room temperature sensor with incorporated NFC technology. Selectable MP-Bus. NFC capabilities allow for easier setup, commissioning and troubleshooting. Type Overview Type Communication Output signal active temperature 2...10 V, MP-Bus Technical Data Electrical Data Nominal voltage AC/DC 24 V Power consumption AC 1 VA Power consumption DC 0.5 W Cable entry Wire openings at the backside (for In-wall wiring) and top-/bottom side (for On-wall wiring) Functional Data Communicative control MP-Bus Application air Measuring Data Measuring values Temperature Accuracy temperature active ±0.9°F @ 77°F [±0.5°C @ 25°C] Time Constant τ (63%) in the room typical 960 s Wall Coupling Factor 52 % Materials Housing white, RAL 9003

Technical data sheet 22RT-59-1 www.Belimo.US 22RT-59-1 • en-us • 2020-07-20 • Subject to change 2 / 4 Safety Data Ambient humidity max. 95% r.H., non-condensing Protection class IEC/EN III Protective extra-low voltage (PELV) EU Conformity CE Marking Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-9 Degree of protection IEC/EN IP30 Degree of protection NEMA/UL NEMA 1 Quality Standard ISO 9001 Safety Notes This device has been designed for use in stationary heating, ventilation and air-conditioning systems and must not be used outside the specified field of application. Unauthorised modifications are prohibited. The product must not be used in relation with any equipment that in case of a failure may threaten humans, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment. Only authorised specialists may carry out installation. All applicable legal or institutional installation regulations must be complied during installation. The device contains electrical and electronic components and must not be disposed of as household refuse. All locally valid regulations and requirements must be observed. Remarks The measuring result is influenced by the thermal characteristics of the wall. A solid concrete wall responds to thermal fluctuations within a room in a much slower than a light- weight structure wall. Room temperature sensors installed in flush-mounted boxes have a longer response time to thermal variations. In extreme cases they detect the radiant heat of the wall even if the air temperature in the room is lower for example. The quicker the dynamics of the wall (temperature acceptance of the wall) or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are. Temperature sensors with electronic components always have a dissipative power which affects the temperature measurement of the ambient air. The dissipation in active temperature sensors shows a linear increase with rising operating voltage. This dissipative power should be taken into account when measuring temperature. As Belimo transducers work with a variable operating voltage, only one operating voltage can be taken into a standard setting at an operating voltage of DC 24 V. That means, that at this voltage, the expected measuring error of the output signal will be the least. For other operating voltages, the offset error will be increased by a changing power loss of the sensor electronics. If a re- calibration should become necessary later directly on the sensor, this can be done by means of a trimming potentiometer on the sensor board. Auxiliary Digital Input can be used with third-party sensors and switches (window alarm, occupancy detector, etc.). The input values are monitored and transmitted only through the MP-Bus communication protocol. Scope of delivery Screws Accessories Service tools accessories Description Type Belimo Assistant App, Smartphone app for easy commissioning, parameterising and maintenance Belimo Assistant App Converter Bluetooth / NFC ZIP-BT-NFC General Remarks Concerning Sensors Build-up of Self-Heating by Electrical Dissipative Power Digital input

Technical data sheet 22RT-59-1 www.Belimo.US 22RT-59-1 • en-us • 2020-07-20 • Subject to change 3 / 4 Service Belimo equipment marked with the NFC logo can be operated and parameterized with the Belimo Assistant App. Requirement: - NFC- or Bluetooth-capable smartphone - Belimo Assistant App (Google Play & Apple AppStore) Align NFC-capable smartphone on the sensor so that both NFC antennas are superposed. Connect Bluetooth-enabled smartphone via the Bluetooth-to-NFC Converter ZIP-BT-NFC to the sensor. Technical data and operation instructions are shown in the ZIP-BT-NFC data sheet. Wiring Diagram GND = 1 AC/DC 24 V = 2 MP Bus = 5 Output Temperature = 8 Output Humidity (22RTH / 22RTM) = 9 GND = 10 Digital Input, e.g. occupany sensor = 12/13 Output CO₂ (22RTM) = 14 GND = 15 Operating controls and indicators

Technical data sheet 22RT-59-1 www.Belimo.US 22RT-59-1 • en-us • 2020-07-20 • Subject to change 4 / 4 Dimensions Type Weight 22RT-59-1 0.31 lb [0.14 kg]