EDS1046-004 EUROPA | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
This document must be retained for future reference. It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should also be inspected periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Data Sheet EDS1046-004 Page 1 of 3 EUR PA
- IP65
- EN 60947-1 & 3 Compliant LBF160-2003PSNME/PNLME AC-23@400V(415V) Enclosed Door Interlocked BS88 Switch Fuses Data Range Units LBF1603PNLME / -NF LBF1603PSNME / -NF LBF2003PNLME / -NF LBF2003PSNME / -NF BS88 Fuse size - - A4 B1-B2 Rated thermal current Ith at 40°C Amps A 160 200 Rated insulation voltage Ui Volts V 800 800 Rated dielectric strength Volts kV 6 6 Rated impulse voltage Uimp Volts kV 8 8 Rated operational current Ie at 400V AC-22 Amps A 160 200 Rated operational current Ie at 400V AC-23 Amps A 160 200 Rated operational power Pe at 400V AC-23 Watts kW 90 110 Rated breaking capacity Amps A 1280 1600 Rated making capacity Amps A 1600 2000 Rated short circuit making current (rms) with fuses fitted Amps kA 80 80 Rated short circuit withstand current (rms) with fuses fitted Amps kA 80 80 Minimum number of mechanical operations - Cycles 10,000 10,000 Minimum number of electrical operations @ 400V AC-23 - Cycles 1,000 1,000 Terminal Capacity (rigid copper cable) - mm² 120 120 Lug bolt size - - M8 M8 Maximum size of busbar connection - mm 5x25 5x25 Tightening torque - Nm 13 13
Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Data Sheet EDS1046-004 Page 2 of 3 Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Page 2 of 3 EUR PA Enclosure Dimensions Terminal Configuration Note: Neutral Contact is Early Make/Late Break LBF160-2003PSNME/PNLME AC-23@400V(415V) Enclosed Door Interlocked BS88 Switch Fuses Maximum BS88 Fuse Sizes
Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Data Sheet EDS1046-004 Page 3 of 3 EUR PA Handle Assembly: 1. Ensure that the handle is in the off position and locate the handle on to the door with the handle showing the off position at 9 o’ clock 2. Tighten the four M5, flange nuts to 1.5Nm Shaft Assembly: 3. Ensure that the switch is in the off position and fully insert the shaft into the switch with the cross pin in a horizontal position 4. Tighten the M5 shaft grub screw to 1.2Nm using a 2.5mm A/F allen key Fuse Shroud Assembly: (SWITCH FUSE ONLY) 5/6. Install the four upright shrouds into the corresponding clips 7. Install fuse shroud into the corresponding clips Padlock Operation Door Interlock Defeat Mechanism (For Authorised Personnel Only); WARNING! ACCESS TO LIVE PARTS
- Ensure that the door is closed and the handle is in the on position
- Locate the hole on the right side of the handle, then push and hold a small pin into the hole to activate the defeat mechanism
- The door can now be opened in the on position. Remove pin and close the door to reset the mechanism LBF160-2003PSNME/PNLME AC-23@400V(415V) Enclosed Door Interlocked BS88 Switch Fuses