It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose'. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. Terminals, including factory fitted, should be checked periodically to ensure correct tightness. Approvals CB. CE & SEMKO UL Standard UL508 International / European Standard IEC & EN 60947-1 and 3 Switch codes DATA Range Units LB204P LB203PSN LB254P LB253PSN LB323P LB324P LB323PSN LB403P LB404P LB403PSN Rated operational voltage Ue IEC & EN Volts V 690 690 690 690 UL Volts V 600 600 600 600 Main switch: Isolating voltage up to Volts V 750 750 750 750 Rated impulse withstand voltage Uimp Volts kV 6 6 6 6 Rated uninterrupted current Iu Amps A 16 20 25 32 Rated operational current Ie IEC & EN AC-22A Up to 690V A 16 20 25 32 AC-21A Up to 690V A 20 25 32 40 AC-1 Up to 690V A 20 25 32 40 Rated operational power AC-23A (50-60Hz) IEC & EN 3 Phase 220-240V kW 7.5 7.5 11 15 380 - 440V kW 11 11 15 18.5 500 - 690V kW 15 15 22 22 Rated operational power AC-3 (50-60Hz) IEC & EN 3 Phase 220-240V kW 4 5.5 7.5 11 440V kW 5.5 7.5 11 11 690V kW 11 11 15 15 UL Power Rating DOL

3 Phase

120V hp 1.5 1.5 3 3 240V hp 3 3 7.5 7.5 480V hp 7.5 7.5 15 20 600V hp 10 10 20 25

1 Phase

120V hp 0.5 0.5 1.5 2 240V hp 1.5 1.5 2 3 UL Short Circuit Ratings Fuse rating, class J Amps A - - 45 45 Fuse rating, class RK5 Amps A 20 20 - - Rated Fused short circuit current Amps kA 10 10 10 10 Short Circuit Capacity (IEC) Max fuse size (Type gl) Amps A 20 20 32 32 Rated Fused short circuit current Amps kA 5 5 30 30 Terminal Specification Single/ Multple strand wire Min-mm2 2.5 2.5 2.5 2.5 Max-mm2 10 10 10 10 Fine strand with sleeve Min-mm2 0.75 0.75 0.75 0.75 Max-mm2 6 6 6 6 American wire gauge AWG 10 10 10 10 Recommended Tightening Torque Nm 1.7 1.7 1.7 1.7 LB_Box_Size_1.qxp_Layout 1 19/09/2014 15:21 Page 1 IP65 Technical Data: LB20, 25, 32, 403PSN / LB32, 403P / LB20, 25, 32, 404P AC-21 Enclosed Switch Disconnectors (Boxed Isolators)

Note: Neutral Contact is Early Make/Late Break Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440 / Fax: 01582 692 450 e-mail: sales@europacomponents.com website: http://www.europacomponents.com Terminal Configuration Enclosure Base Switch Assembly Screw Driver Cover Screw Knob Mounting Cover * Detail B Use screwdriver to pull rail - slide to remove switch from Enclosure base. Switch Rail Slide Knockout (o 16mm)

2 Places

Suitable for M4 ScrewKnockout M20 (4 Places) Procedure to dismantle the cover: n Ensure the switch is in the OFF position n Unscrew the cover screws & remove the cover n For easy wiring the switch can be removed from the base & then clicked back into place once wiring is complete n After wiring ensure the profile orientation of the actuating spindle & knob shaft are in the same position n Replace the cover & take care not to overtighten the screws (recommended tightening torque 0.5 Nm) n Do not install using power driven screwdrivers Please Note: There is no need to remove the switch handle in order to remove the cover. LB_Box_Size_1.qxp_Layout 1 19/09/2014 15:21 Page 2 Technical Data: LB20, 25, 32, 403PSN / LB32, 403P / LB20, 25, 32, 404P AC-21 Enclosed Switch Disconnectors (Boxed Isolators)