EDS1235-003 EUROPA | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
This document must be retained for future reference. It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should also be inspected periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Data Sheet EDS1235-003 Page 1 of 3 EUR PA LB100 - 1254PME - 3PSNME AC-22
4 Pole & 3 Pole + Switched Neutral
IP65 Steel Enclosed Switch Disconnectors UL Standard UL508(switch only) International/European Standard IEC & EN 60947-1 and 3 Data Range Units LB1004PME LB1003PSNME LB1254PME LB1253PSNME Rated operational voltage Ue IEC & EN Volts V 690 690 UL Volts V 600 600 Main switch: Isolating voltage up to Volts V 750 750 Rated impulse withstand voltage Uimp Volts kV 6 6 Rated uniinterrupted current Iu Amps A 100 125 Rated operational current Ie IEC & EN AC-22A Up to 690V A 100 125 AC-21A Up to 690V A 100 125 AC-1 Up to 690V A 100 125 Rated operational power AC-23A (50-60Hz) IEC & EN 3 Phase 230(240)V kW 45 55 400(415)V kW 55 75 690V kW 90 90 Rated operational power AC-3 (50-60Hz) IEC & EN 3 Phase 230(240)V kW 37 45 400(415)V kW 45 55 690V kW 55 55 UL Power Rating DOL
3 Phase
120V hp 7.5 7.5 240V hp 20 30 480V hp 30 40 600V hp 40 50
1 Phase 120V hp 3 3
240V hp 7.5 7.5
Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Data Sheet EDS1235-003 Page 2 of 3 EUR PA UL Short Circuit Ratings Fuse rating, class J Amps A 125 125 Fuse rating, class RK5 Amps A - - Rated Fused short circuit current Amps kA 10 10 Short Circuit Capacity (IEC) Max fuse size (Type gl) Amps A 125 125 Rated Fused short circuit current Amps kA 30 30 Terminal Specification Single/Multiple strand wire Min-mm² 2.5 2.5 Max-mm² 50 50 Fine strand with sleeve Min-mm² 4 4 Max-mm² 50 50 American wire gauge AWG 1 1 Recommended Tightening Torque Nm 2.5 2.5 LB100 - 1254PME - 3PSNME AC-22 IP65 Steel Enclosed Switch Disconnectors Terminal Configuration Dimensions Note: Neutral Contact is early make/late break
This document must be retained for future reference. It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should also be inspected periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS Europa House, Airport Way, Luton, Bedfordshire, LU2 9NH Technical: 01582 692 444 technical@europa-plc.com www.europa-plc.com Data Sheet EDS1235-003 Page 3 of 3 EUR PA MAINTENANCE OF EUROPA STB ENCLOSURES The Europa range of STB enclosures will require regular maintenance. This is due to light surface corrosion that may form on the surface of the enclosure from airborne or other sources of contaminates. Failing to remove the surface corrosion will result in the degradation of the paint finish. The timescale for maintenance will depend on the environment and the location of the installation. For example, if the enclosure has been installed externally and exposed to all weather conditions, the unit will require more frequent maintenance that a unit that has been installed in a sheltered location. In either case it is recommended that regular inspection is carried out to maintain the integrity of the enclosure. Maintenance consists of wiping off suspected residual surface rust and contaminates and if necessary, cleaning and then applying a rust inhibitor and touch up paint (colour RAL 7035) if required. Where enclosures are in exposed or harsh environments or in difficult to access areas such as roof tops and remote locations, Europa would always recommend the ATLAS range of GRP enclosures which requires minimal maintenance.