GFA202570 GPSEMI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
Easy paralleling for increased filter capacity LINE VOLTAGE UP TO 690V TRANSFORMER POWER UP TO 2700kVA Line to line voltage Characteristic Conditions SMAX Maximum transformer power 1500 kVA 2500 kVA 2700 kVA VINS (rms) Insulation voltage 1 min @ 25°C 2500 V DC 2500 VDC 2500 VDC PL Power losses 20 W 25 W 50 W COMPONENTS RATINGS CF Total filter capacitance 25 µF 25 µF 25 µF RD Discharge resistance 20 kΩ 20 kΩ 20 kΩ LEC Capacitor life expectancy @URMS >30000 h >30000 h >30000 h MECHANICAL AND THERMAL CHARACTERISTICS W Width 300 mm 300 mm 300 mm D Depth 185 mm 185 mm 185 mm H Height 281 mm 281 mm 281 mm M Mass 5k g 5k g 5k g Ta max Max amb. op. Temp. 50 °C 50 °C 50 °C Tstg Storage temperature 60 °C 60 °C 60 °C Document GFA202570T002 Z CC< 5%; f=50Hz; I0<1%; VRRM = 1200V for
400 VAC Line, 1600V for 500VAC Line, 2200V
Via Greto di Cornigliano 6R - 16152 Genova , Italy Phone: +39-010-659 1869 Fax: +39-010-659 1870 Web: www.gpsemi.it E-mail: info@gpsemi.it
LINE FILTER FOR PHASE CONTROLLED CONVERTERS GFA202570 All dimensions are in mm Customisations are available on request. Please contact factory. Document GFA202570T002 In the interest of product improvement Green Power Solutions reserves the right to change any specification given in this data sheet without notice. RD2 10k RD1 10k 2 ohm 2 ohm 2 ohm 50u 50u