G680C BELIMO | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Fluid chilled or hot water, up to 60% glycol, steam Flow characteristic equal percentage Controllable flow range stem up - open A – AB Valve Size [mm] 3” [80] Pipe connection 125 lb flanged Housing Cast iron - ASTM A126 Class B Stem stainless steel Stem seal NLP EPDM (no lip packing) Seat Stainless steel AISI 316 Valve plug brass Body Pressure Rating ANSI Class 125, up to 175 psi below 150°F ANSI Class 125 Number of Bolt Holes 4 Maximum Inlet Pressure (Steam) 35 psi [241 kPa] Max Differential Pressure (Steam) 15 psi [103 kPa] Rangeability Sv 91:1 Cv 90 Weight 74.97 lb [34 kg] Leakage rate ANSI Class III Servicing repack/rebuild kits available Flow/Mounting Details Flow arrow shown on rear of valve Application This valve is typically used in large air handling units on heating or cooling coils. This valve is suitable for use in a hydronic system with variable flow. Bronze or stainless steel trim valves can be used for steam applications, depending on actuator and close-off combination. Suitable Actuators Non-Spring Spring Electronic fail-safe G680C EVB(X) AF AVKB(X) Dimensions (Inches [mm]) D B C A FE EVB, EVX, RVB, RVX A B C D E F Safety Notes WARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov Piping The valves should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. The preferred mounting position of the valve is with the valve stem vertical above the valve body, for maximum life. However, the assemblies can be mounted with valve stem vertical above the valve or up to 45° in relation to the horizontal pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. Do not reverse flow direction. G680C Technical Data Sheet 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 12/20/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.

Dimensions (Inches [mm]) D B C AFE AFB, AFX A B C D E F Dimensions (Inches [mm]) D B C AFE AVKB, AVKX A B C D E F G680C Technical Data Sheet 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 12/20/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.

Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power consumption in operation 5 W Power consumption in rest position 2 W Transformer sizing 9.5 VA (class 2 power source) Electrical Connection 18 GA plenum cable, 3 ft [1 m], with 1/2” conduit connector, degree of protection NEMA 2 / IP54 Overload Protection electronic throughout full stroke Electrical Protection actuators are double insulated Ω, 1/4 W resistor), variable (VDC, PWM, on/ off, floating point) Operating range Y variable Start point 0.5...30 V End point 2.5...32 V Input Impedance 100 kΩ for 2...10 V (0.1 mA), 500 Ω for 4...20 mA, 1500 Ω for PWM, On/Off and Floating point Position Feedback 2...10 V Stroke 1.25” [32 mm] Actuating force motor 450 lbf [2000 N] Direction of motion motor selectable with switch Direction of motion fail-safe reversible with switch Position indication Mechanically, with pointer Manual override 5 mm hex crank (3/16” Allen), supplied Running Time (Motor) default 90 s, variable 90...150 s Running time fail-safe <35 s Bridging time 2 s delay before fail-safe activates Pre-charging time 5...20 s Ambient humidity max. 95% r.H., non-condensing Degree of Protection IP54, NEMA 2, UL Enclosure Type 2 Housing material Die cast aluminium and plastic casing Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU Noise level, motor 60 dB(A) Noise level, fail-safe 60 dB(A) Servicing maintenance-free Quality Standard ISO 9001 Weight 6.39 lb [2.9 kg] † Use flexible metal conduit. Push the listed conduit fitting device over the actuator’s cable to butt against the enclosure. Screw in conduit connector. Jacket the actuators input wiring with listed flexible conduit. Properly terminate the conduit in a suitable junction box. Rated impulse Voltage 800V. Type of action 1. Control pollution degree 3. AVKX24-MFT Technical Data Sheet Modulating, Fail-Safe Operation, Linear, 24 V, Multi-Function Technology® 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 01/27/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.

Actuators may be connected in parallel. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC. A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC. Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. For triac sink the common connection from the actuator must be connected to the hot connection of the controller. Contact closures A & B also can be triacs. A & B should both be closed for the triac source and open for triac sink. Actuators with plenum cable do not have numbers; use color codes instead. Meets cULus requirements without the need of an electrical ground connection. ! WARNING! LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk (1) - Common Red (2) Hot Wht (3) Y1 Input Org (5) U Output Line Volts

24 VAC Transformer

Feedback Signal (+) (–) 3 18 On/Off Line Volts (–) (+) Blk (1) – Common Red (2) + Hot Wht (3) Y1 Input Pnk (4) Y2 Input Org (5) U Output AB AB Direction of rotation switch A B Feedback Signal 2 to 10 VDC 2 18 Floating Point Blk (1) - Co mmon Red (2) + Hot Wht (3) Y1 Input Org (5) U Output (–) (+) Line Volts /uni03A9500/uni03A9 1/4 W VDC / 4 to 20 mA Functions 50% 100% Control mode acc. to Y Min Mid Max Normal ab c 500 Blk (1) - Co mmon Red (2) + Hot Org (5) U Output Wht (3) Y1 Input (–) (+) Line Volts

24 VAC Transformer (AC Only)

B C A 1/4 W VDC/mA Control Signal /uni03A9 /uni03A9 Override Control Min, Mid, Max Positions AVKX24-MFT Technical Data Sheet Modulating, Fail-Safe Operation, Linear, 24 V, Multi-Function Technology® 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 01/27/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.