GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM DUCT SMOKE DETECTOR DSD SERIES RECTANGULAR SQUARE PRODUCT DESCRIPTION The DSD Series, 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of –20°C to 70°C (–4°F to 158°F), and a humidity range of 0 to 95% (non- condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. The DSD housing provides ample wiring space, a ¾-inch conduit knockout, and built-in short circuit protection to prevent damage to sensitive components during installation. High contrast terminal designations make wiring easy. With its 2:1 sensor-to-power capability, the power board of the DSD may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source. All detectors must be used with a metal sampling tube, DST series. SIZE Rectangular Dimensions: 37cm (14.38in) L, 12.74cm (5in) W, 6.36cm (2.5in) D WEIGHT 1.14kg (2.5lbs) OPERATING TEMPERATURE -20 to 70°C (-4 to 158°F) STORAGE TEMPERATURE -30 to 70°C (-22 to 158°F) OPERATING HUMIDITY 0 to 95 %RH, non-condensing AIR DUCT VELOCITY 0.5 to 20.32 m/sec (100 to 4000 ft/m) ELECTRICAL RATINGS DSD120/240 DSD120/240 DSD120 DSD240 POWER SUPPLY VOLTAGE 20-29 Vdc 24Vac 50-60Hz 120Vac 50-60Hz 240 Vac 50-60Hz INPUT CAPACITANCE 270 µF maximum 270µF minimum N/A N/A RESET VOLTAGE 3.0 Vdc minimum 2.0 Vac minimum 10 Vac minimum 20 Vac minimum REST TIME (BY POWER DOWN) ALARM RESPONSE TIME 15 seconds 15 seconds 15 seconds 15 seconds SENSITIVITY TEST See detector label See detector label See detector label See detector label CURRENT REQUIREMENTS MAX. STANDBY TEST 21 mA @ 24 Vdc 65 mA RMS @ 24 Vac 60 Hz 20 mA RMS @
120 Vac 60 Hz
10mA @ 240 Vac 60 Hz MAX. ALARM CURRENT 65 mA @ 24 Vdc 135 mA RMS @
24 Vac 60 Hz
35 mA RMS @ 18 mA RMS @
240 Vac 60 Hz
CONTACT RATINGS Alarm Initiation Contacts (SPST): 2.0A @ 30 Vdc (resistive) Alarm Auxiliary Contacts (SPST): 10A @ 30 Vdc (resistive); 10A @ 250 Vac (resistive); 1/2 HP @ 240 Vac; 1/4 HP @ 120 Vac Note: Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory Contacts (SPST): 2.0A @ 30 Vdc (resistive); 2.0A @ 125 Vac (resistive) SPECIFICATIONS
PRINTED IN CANADA Copyright © Greystone Energy Systems Inc. All Rights Reserved www.greystoneenergy.com PS-DSDXXX-02 01/20 Greystone Energy Systems, Inc.
150 English Drive, Moncton,
New Brunswick, Canada E1E 4G7 Ph: +1 (506) 853-3057 Fax: +1 (506) 853-6014 North America: 1-800-561-5611 E-mail: mail@greystoneenergy.com 3242-1653:02073033744 WIRING INFORMATION NOTE 1: 24V Power Inputs accept a non-polarized 24 Vdc or 24 Vac 50-60Hz. 120Vac Power Inputs accept only 120Vac 50-60Hz. Connect power source to appropriate terminals of each detector. See specifications for additional power supply information. NOTE1: Auxiliary contacts shown in standby position. Contacts switch during alarm as indicated by arrows. Auxiliary contacts are not to be used for connection to the control panel. See specifications for contact ratings. NOTE 3: Supervisory contacts shown in standby position. Open contacts indicate a trouble condition to the panel. See specifications for contact ratings. NOTE 4: Alarm indication contacts shown in standby position. Closed contacts indicate an alarm condition to the panel. See specifications for contact ratings. PRODUCT DSD Duct Smoke Detector, Photoelectric POWER SUPPLY 120 240
120 Vac, 24 Vac/Vdc
240 Vac, 24 Vac/Vdc
PRODUCT DST- Metal Duct Sampling Tube for DSD Series DUCT SIZE 1.0 1.5 3.0 5.0 10.0 Duct widths up to 305mm (12”) Duct widths between 305mm - 610mm (12” - 24”) Duct widths between 610mm - 1200mm (24” - 48”) Duct widths between 1200mm - 2400mm (48” - 96”) Duct widths between 2400mm - 3700mm (96” - 144”) ORDERING DST- PART NUMBER NOTE: Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NOTE: Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. 24V AC/DC 91 0 AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. (NOTE 2) 16 61 7 8 18 7 16 61 7 8 18 7 SUPERVISORY CONTACTS (NOTE 3) 24V 91 0 AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. (NOTE 2) SUPERVISORY CONTACTS (NOTE 3) SUP N.O. SUP C SU P CSU P N.O. 5ALARM INITIATION CONTACTS (NOTE 4) 5ALARM INITIATION CONTACTS (NOTE 4) ALARM INITIATION LOOP UL/FM LISTED 4-WIRE CONTROL PANEL 120 VAC 120 VAC OR OR AUX A AUX BAUX A AUX B ALARM N.O.ALARM N.O. ALARM CALARM C 3 314 14 FIRST DETECTOR IN THE LOOP POWER INPUTS (NOTE 1) POWER INPUTS (NOTE 1) LAST DETECTOR IN THE LOOP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER