DRU30 CHINFA | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
V V Battery Voltage range 9.6 19.2 14.25 28.5 12V 24V Characteristics Conditions min. typ. max. unit V V V V DC input 12 Nominal input voltage Input voltage range 11 22.5 Current consumption No load Charging Maximum 0.2 3.5 A A A 12V 24V 12V 24V www.chinfa.com
FEATURES
‧BATTERY CONTROLLER FOR DIN RAIL UPS SYSTEM ‧BUILT-IN BATTERY TEST FUNCTION ‧BATTERY POLARITY PROTECTION ‧PARALLEL CONNECTION TO DC BUS ‧RELAY CONTACT SIGNAL OUTPUT LED INDICATOR FOR DC BUS OK, BATTERY FAIL AND BATTERY DISCHARGE ‧BATTERY CONTROLLER FROM 4 TO 12 AH ‧3 YEARS WARRANTY ‧CHARGER FOR LEAD-ACID BATTERIES 30A DC UPS CONTROLLER sales@chinfa.com 2016.05.19 DRU30 SERIES 10.5 ~ 13.5 VDC 22 ~ 27.5 VDC 11 ~ 14 VDC 30A 30A DRU30-12 DRU30-24 22.5 ~ 28 VDC MODEL LIST MODEL NO. INPUT VOLTAGE OUTPUT VOLTAGE OUTPUT CURRENT o All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed SPECIFICATION Isolation voltage Isolation resistance Ambient temperature Input / Relay contact Input / Relay contact, @ 100VDC Operating at Vi nom VDC MΩ100 -40 o C o CNon operational -40 Storage temperature Relative humidity MTBF Vi nom, Io nom % RH 500 Altitude during operation 4,850 m Hours Hours Derating (see derating curve) o % / C2.5o Vi nom, from +51 to +71 C o Bellcore Issue 6 @40 C, GB 24V 12V Dimension mmL90 x W54 x D114Screw terminal type Pollution degree 2 GENERAL Characteristics Conditions min. typ. max. unit 383,000 360,000 IND. CONT. EQ. UL 508 HR UL 60950-1 EN 60950-1 a Free air convectionCooling IEC 60068-2-13 Installation position Vertical ( other direction may derating using ) Degree of protection IP20 INPUT SPECIFICATIONS Single Output Models
Characteristics Conditions min. typ. max. unit Switching threshold Vin < 22.5V Vin < 11V dynamic Vout - 1V / 100ms dynamic Vout - 1V / 100ms 12V 24V INPUT SPECIFICATIONS o All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed SPECIFICATION www.chinfa.com sales@chinfa.com 2016.05.19 DRU30 SERIES Characteristics Conditions DC O.K Battery fail Battery discharge Relay Status : When DC Voltage between 22.5 ~ 28V (24V model), 11 ~ 14V (12V model) relay contacts DC ON Relay Status : When battery fail is observed through the battery test function, relay contacts battery fail. Relay Status : When battery in discharge condition, relay contacts battery discharge. Charge voltage Battery Low-voltage protection for discharge voltage 12V model : 9.6V≦ 24V model : 19.2V≦ Charge voltage protection for Battery Low-voltage NOTE 1) Propose the battery manufacturer and capacity of battery choose the same type to avoid any damage of battery. 12V model : 8V≦ 24V model : 16V≦ 12V model : Nominal 13.6 VDC, Fast 14.25 VDC 24V model : Nominal 27.2 VDC, Fast 28.5 VDC CE EN 61000-6-3, EN 55022 class B, EN 61000-6-2, EN 55024, EN 61204-3 EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-6, EN 61000-4-8 UL / CUL UL 508 Listed, UL 60950-1 Recognized TUV EN 60950-1 Vibration resistance Shock resistance meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis ) meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face) V V DC output 12 Nominal output voltage Selection of charge current 2AH ~5AH 5AH ~10AH >10AH Characteristics Conditions min. typ. max. unit V V mV V V A A A V V V V A Vi - Vout 0.55 Battery - Vout 0.45 Ripple & Noise Battery reverse voltage 100 14.25 28.5 0.5 2.5 Discharge current To suggest discharge current 0.1CA ~ 3CA CA is battery capacity Vi nom, Io nom V V Voltage range 13.5 27.5 ACurrent range 30 V V Output voltage range 13.75 28.0 9.1 18.7 10.5 Battery output Output voltage drop ACurrent range 30 Selection of charge voltage 24V 12V 24V 12V 24V 12V 24V 12V 24V 12V Nominal charge voltage Fast charge voltage Nominal charge voltage Fast charge voltage Battery output fuse Internal 40A fuse Suggest external battery 4AH / 7AH / 12AH 13.6 14.25 27.2 28.5 OUTPUT SPECIFICATIONS APPROVALS AND STANDARDS CONTROL FUNCTION 2) Relay contact rating at 1A 30 VDC.
1, 2 3, 4 5, 6 PIN NO. Designation Description BATT DISCHARGE BATT FAIL DC IN (-) DC IN (+) LOAD (-) LOAD (+) BATT (-) BATT (+) 0.5A / 1A / 2.5A 27.2V / 28.5V (24V model) 13.6V / 14.25V (12V model) BATT FAIL (Red LED) BATT DISCHARGE (Yellow LED) Signal port Signal port Signal port Input voltage Input voltage Output voltage Output voltage Battery mode connection Battery mode connection Battery charge current select switch Battery charge voltage select switch Battery charge voltage select switch Battery low fail indicator LED Battery discharge indicator LED Battery charge indicator LED MECHANISM & PIN CONFIGURATIONmm [inch] 90 x 54 x 114 mm (3.60 x 2.13 x 4.49 inches)Screw terminal type PlasticCase material 370gWeight Packing CASE SIZE PHYSICAL CHARACTERISTICS www.chinfa.com sales@chinfa.com 2016.05.19 P3 CONSTRUCTION Easy snap-on mounting onto the DIN-Rail (TS35/7.5 or TS35/15), unit sits safely and firmly on the rail; no tools required even to remove INSTALLATION Ventilation / Cooling Normal convection All sides 25mm free space For cooling recommended Connector size range 2 IN / OUT : AWG18-8 (0.6~6mm ) flexible / solid cable, connector can withstand torque at maximum 9 pound-inches. 10~11mm stripping at cable end recommends.2 Relay : AWG24-12 (0.2~2.5mm ) flexible / solid cable, connector can withstand torque at maximum 5 pound-inches. 7mm stripping at cable end recommendso Use copper conductors only, 60/ 75 C GENERAL TOLERANCE ±0.30[0.01] ±0.50[0.02] DRU30 SERIES 0.45kg ; 32 / 15.5kg / 1.85CUFT 109.00 [4.29] 114.00 [4.49] 54.00 [2.13] 90.00 [3.60] 2.5A DC O.K BATT DISCHARGE BATT FAIL 0.5A 28.5V 27.2V BATT FAIL BATT DISCHARGE DC O.K IND. CONT. EQ. E196362 2JF4 UL508 LOAD BATTDC IN DRU30 DC O.K DC O.K (Green LED) 6 5 4 3 2 1 7 8 9 10 11 12
+ - DRU30 LOADDC IN BATT - + - + - + Battery + - + - LOAD www.chinfa.com sales@chinfa.com 2016.05.19 P4 CIRCUIT SCHEMATIC DC IN DC OK BATT Discharge +LOAD DC TEST BATT TEST BOOST CIRCUIT CHARGE CIRCUIT DISCHARGE CIRCUIT BATT FAIL BATT ‧Block diagram for DRU30 series DRU30 SERIES Battery open circuit Fuse open circuit Battery reverse polarity Battery over discharge protection DC IN OK Battery charging 12V model : DC IN < 11V, Battery discharge, Batt > 10V 24V model : DC IN < 22.5V, Battery discharge, Batt > 20.5V STATE LED BATT FAIL (RED) BATT DISCHARGE (YELLOW) DC O.K (GREEN) 12V model : DC IN < 11V, Battery discharge, Batt <10V 24V model : DC IN < 22.5V, Battery discharge, Batt < 20.5V 12V model : DC IN < 11V, Batt 9.6V≦ 24V model : DC IN < 22.5V, Batt 19.2V≦ LED INDICATOR STATE ON OFFBattery Status @ DC IN O.K DERATING CURVE o Temperature [ C ] 100 71-40 Output current [ % ] Battery charge voltage select switch Battery charge current select switch DC O.K(Green LED) BATT DISCHARGE(Yellow LED) BATT FAIL(Red LED) ON OFF OFF ON OFF ON OFF ON ON OFF OFF OFF OFF * Please disconnect the battery from DRU30 during transportation to avoid consuming the power of battery.