DH100ACDCLWP SYSTEMSENSOR | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Features

NEMA Type 4 UL listed for non-hazardous indoor and outdoor

applications

Air velocity rating from 100 to 4000 feet-per-minute (0.5 to 20.32 m/sec.) Patented interconnectability for multi-fan shutdown (up to 10 air handlers) Patented telescopic sampling tube Patented cover tamper trouble signal

24 VAC/DC or 120/240 VAC operation

Equipped with two DPDT Form C relay contacts Built-in reset button Outside mounting tabs Easy and quick mounting to round or rectangular ducts from 1´–12´ (0.3–3.7 meters) wide Easy to clean UL recognized field-replaceable power and sensor boards Remote test station option Remote sounder option UL 268A listed 3 year warranty The DH100ACDCLWP is UL listed as a watertight enclosure providing protection against falling dirt, rain, windblown dust, splashing and hose directed water. Additionally, this detector features advanced Low-Flow technology, capable of sensing smoke in air velocities from 100 to 4,000 feet-per-minute (0.5 to 20.3 meters-per-second). The DH100ACDCLWP can be directly mounted to rooftop HVAC equipment or used in other environmentally harsh applications that fall within its specified temperature limits. Since the unit is NEMA 4 rated, no additional enclosure is needed. The Watertight Innovair provides the same form, fit and wiring terminations as the standard Innovair but meets the NEMA 4 requirements, providing unsurpassed environmental protection. In addition to being the only watertight duct smoke detector on the market, the revolutionary Innovair solves many difficult low airflow duct applications where reliable smoke detection is critical. Innovair with Low-Flow technology can detect smoke in air speed velocities as low as 100 feet-per-minute or as high as 4,000 feet-per-minute. The Innovair family is designed for simplified installation and easy maintenance. The modular construction allows for easy cleaning and simple field replacement of the UL-recognized power and sensor boards. System Sensor has again set the standard for HVAC smoke detection technology. WARNING: Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector. NOT a substitute for early warning detection. NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72 and 90A for additional information about the proper application of duct smoke detectors. NOTE: To maintain the watertight properties of this duct smoke detector, watertight conduit and fittings must be used. Mount the product with the conduit holes facing downwards, if possible. S911 3240-1653:119 199-01-E 2091

Innovair Duct Smoke Detector Specifications Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor Model DH100ACDCLWP series watertight duct smoke detector. The detector shall meet the NEMA 4 standard for enclosures for electrical equipment. It shall be UL listed for non-hazardous locations for installation and use in both indoor and outdoor applications. The detector shall be constructed so as to provide a degree of protection against falling dirt, rain, windblown dust, splashing water, hose-directed water and incidental contact. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.3 m/sec.). The unit shall be capable of controlling up to ten (10) air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using the SSK451 Multi-Signaling Accessory or the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or remote test station. The duct smoke detector housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall either be telescoping or be easily installed by passing through the duct housing after the housing is mounted to the duct. The unit shall provide a spatial separation of no less than ¼˝ (6.4 mm) and/or a physical barrier between the high and low voltage terminals. The enclosure shall meet all applicable NEC and NFP A standards regarding electrical junction boxes. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Physical Specifications Size 143⁄8˝ (37 cm.) Length; 5½˝ (14 cm.) Width; 2¾˝ (7 cm.) Depth Shipping Weight 3¾ lbs. (1.7 kg.) Operating Temperature Range 32° to 131°F (0° to 55°C) Storage Temperature Range –22° to 158°F (–30° to 70°C) Operating Humidity Range 10% to 93% relative humidity non-condensing NEMA Enclosure Rating Type 4 – Watertight Indoor/Outdoor Power supply voltage: 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 µF max. 270 µF max. N/A N/A Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. Sensitivity Test: See detector label See detector label See detector label See detector label Current Requirements (Using No Accessories) Max. standby current 15 mA 35 mA RMS 25 mA RMS 15 mA RMS* Max. alarm current 70 mA 125 mA RMS 35 mA RMS* 25 mA RMS* Contact Ratings Alarm initiation contacts (SPST) 2.0A @ 30 VAC/DC (0.6 power factor) Alarm auxiliary contacts (DPDT) 10A @ 30 VDC; 10A @ 250 VAC Note: Alarm auxiliary contacts must switch 100mA minimum at 5VDC. Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Trouble contacts (SPDT) 2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive) Accessory Current Loads at 24 VDC Device Standby Trouble Alarm AP A451 12.5 mA Max. n/a 30 mA Max. P A400 0 mA n/a 15 mA Max. RA400Z 0 mA n/a 10 mA Max. RTS451/RTS451KEY 12 mA* n/a 7.5 mA Max. SSK451 5 mA Max. 9 mA Max. 30 mA Max. *Note: When a unit is powered at the 120 VAC or 220/240 VAC input, any combination of accessories may be used such that the given accessory loads are: 60 mA or less in the standby state; 110 mA or less in the alarm state.

System wiring diagram for 4-wire duct smoke detectors Wiring diagram for DH100ACDCLWP to SSK451: 20 1 2Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power – NOTE: Wiring diagram shown is for DH100ACDCLWP 4-wire duct smoke detector system equipped without a control panel. Alarm Power Common APA451DH100ACDCLWP NOTE: A trouble condition is indicated when the green LED is not illuminated. Important Interconnect Notes

  • When using the interconnect feature, all interconnected units must be powered with the same, independent supply.
  • Polarity must be maintained throughout the interconnect wiring. Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit 2 and so on.
  • Up to 10 units may be interconnected. Wiring diagram for the RTS451/RTS451KEY: COMMON 3 TEMPORAL SELECT 2 ALARM SIGNAL 1 SUPERVISORY SIGNAL 4 RESET 7 TEST 8 POWER (–) 6 POWER (+) 5

15 ALARM SIGNAL

2 RESET

11 TEST

20 AUX. POWER (–) 19 AUX. POWER (+) SSK451 FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN SUPERVISORY CONTACTNO FIELD INSTALLED JUMPER DH100ACDCLWP UNIT 1 1Alarm Signal Aux. Power + Sup. N. O. Sup. COM Aux. Power – Reset Test (Red LED) Alarm (Green LED) Power DH100ACDCLP RTS451/RTS451KEY For RTS451KEY only without a control panel. Wiring diagram for DH100ACDCLWP to APA451: 24V 120 VAC VAC 9 10 A B C AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 16 6 1 7 7 18 8 ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. 24V VAC 9 1 0 A B C AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 16 6 17 7 1 8 8 ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS. SUPERVISORY TROUBLE CONTACTS TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. 14 3 314 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM. ALARM INITIATION LOOP UL LISTED 4-WIRE CONTROL PANEL FIRST DETECTOR IN THE LOOP DH100ACDCLWP LAST DETECTOR IN THE LOOP DH100ACDCLWP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION. FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER. NOTE: THE SUPERVISORY RELAY NOW PROVIDES A "FORM C" CONTACT FOR CUSTOMIZED APPLICATIONS. FOR STANDARD APPLICATIONS, ONLY THE "NO" CONTACT IS USED POWER INPUTS ACCEPT

24 VDC, 24 VAC 50-60 HZ,

120 VAC 50-60 HZ, OR

220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. AUX. CONTACT RATINGS 10A @ 30 VDC RESISTIVE 10A @ 250 VAC 100mA MINIMUM @ 5 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS. TROUBLE CONTACT RATING

2.0 A @ 30 VDC resistive

2.0 @ 125 VAC (resistive) 120 VAC

3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2007 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. A05-0286-007 • 1/07 • #1753

Ordering Information

Part No. Description DH100ACDCLWP Watertight 4-wire photoelectric duct smoke detector with low-flow technology A5190 Replacement 4-wire photoelectric detector board A5064 Replacement 4-wire power board Accessories ST-1.5 Metal sampling tube duct widths 1´–2´ (0.3–0.6 m) MOD400R Sensitivity test module ST-3 Metal sampling tube duct widths 2´–4´ (0.6–1.2 m) RA400Z Remote annunciator alarm LED ST-5 Metal sampling tube duct widths 4´–8´ (1.2–2.4 m) F36-09-11 Replacement air filters (two per package) ST-10 Metal sampling tube duct widths 8´–12´ (2.4–3.7 m) M02-04-00 Test magnet T80-71-00 Replacement telescoping sampling tube P48-21-00 End cap for metal sampling tubes P48-55-00 Replacement end cap for T80-71-00 S08-39-01 Photo replacement screen SSK451 Multi-Signaling accessory P A400W Mini-Alert sounder RTS451KEY Remote test station with key lock PS24LOW Mini-Alert add-on strobe RTS451 Remote test station PS12/24SLENSW Wall-mount “SMOKE” lens AP A451 Remote annunciator with piezo alarm Accessories System Sensor provides system flexibility with a variety of accessories, including three remote test devices and several different means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed. SSK451 Multi-Signaling Accessory (UL 268A) SSK451 Multi-Signaling Accessory (UL 268A) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available) APA451 Piezo Annunciator (UL S4011) RTS451KEY Remote Test Station with Key (UL S2522) PA400W Mini-Alert Sounder (UL S3593) shown with PS24LOW add-on strobe (PS12/24SLENSW smoke lens option available) RTS451 Remote Test Station (UL S2522) RA400Z Remote Annunciator (UL S2522)