DF-C10 LEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
Features
- DC Measurement
- Low current transducer
- Panel mounting
- Bipolar voltage supply
- Extended measuring range Advantages
- Large aperture
- Good performances in harsh EMC environment
- High isolation between primary and secondary circuits
- Easy to mount
- Bipolar
- No insertion losses Options on request
- DIN mounting
Applications
- DC leakage current measurement
- Differential current measurement in DC applica- tions
- Low DC current measurement Notes: 1) Between primary and secondary 2) Excludes the electrical offset LEM Components www.lem.com Primary nominal Primary current Analogue Output Type current range signal IPN (mA.t) IP (mA.t) VOUT (V) 10 16 0-10 DF 0.01 C10 20 38 0-10 DF 0.02 C10 50 80 0-10 DF 0.05 C10 100 160 0-10 DF 0.1 C10 300 480 0-10 DF 0.3 C10 500 800 0-10 DF 0.5 C10 Preliminary
Dimensions DF-C10 (unit : mm, 1mm = 0.0394 inch) Mechanical characteristics
- General tolerance ± 1 mm
- Primary aperture ∅ 25 mm
- Secondary connection Finger safe terminals
- Panel mounting 2 holes ∅ 4.2mm (Distance between holes 38 mm x 55mm) Remarks
- The temperature of the primary bar can not exceed 90°C. LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Output Voltage / Primary Current 4.2 Secondary terminals Terminal 1 : Supply voltage +12...+15VDC Terminal 2 : Supply voltage -12...-15VDC Terminal 3 : Voltage output Vs Terminal 4 : 0V -10VDC 10VDC -20VDC -16VDC 16VDC 20VDC -IPmax IPmaxIPN IPN VOUT(V) IP(A)